4 floors · 100,674 sq ft · built 1951 · class W1 · owner of record: Nyc Department Of Parks And Recreation
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 69 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 100,674 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 190 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 190 days | Annual filing |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1165 days | Next cycle year 2029 |
| Energy audit and retro-commissioning (2031) Likely applies Local Law 87 · Calendar year 2031 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2091). Agency page | Dec 31, 2031 in 1895 days | Next due 2031 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-09-14 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Feb 6, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT THE TIME OF INSPECTION, EMERGENCY LIGHTS IN AUDITORIUM WERE NOT WORK #35728804P | Mar 5, 2026 POP/IN-VIO | $0 |
| Feb 6, 2026 | Construction CLASS - 2 RE-ISSUED 35691881M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, ELECTRICAL METER ROOM HAS WATER STAINS AND SPALLING ON WALL AND CEILING. OIL TANK ROOM HAD WATER STAIN MARK #35728803N | Mar 5, 2026 POP/IN-VIO | $0 |
| Feb 6, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). AT THE TIME OF INSPECTION, THE FOLLOWING DOORS HAD TURN KNOB HARDWARE:-325, 324, 322, 32 #35728806Z | Mar 5, 2026 POP/IN-VIO | $0 |
| Feb 6, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, THE FOLLOWING ROOM DOORS WERE NOT SELF-CLOSING, 322, 320, 319, 317, 316, 315, 310, 307, 308, 306, 301, 201, 202. 204, 203, 206, #35728805R | Mar 5, 2026 POP/IN-VIO | $0 |
| Feb 6, 2026 | Construction CLASS - 2 28-301.1. RE-ISSUED 3569188Y. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE), FGC APPENDIX E(E4)(2014 CODE). AT THE TIME OF INSPECTION, THE GAS METER IN CELLAR HAS NE MEANS OF VENTILATIO #35728802L | Mar 5, 2026 POP/IN-VIO | $0 |
| Mar 19, 2025 | Construction CLASS - 2 28-301.1. REISSUE: 35672435Z-CELLAR LEVEL BOILER ROOM. THE LEVERS FOR AIR HAS BEEN BOARDED UP. AIR VENTS FOR GAS METER. REMEDY: COMPLY WITH CODE. #35691882Y | Apr 23, 2025 POP/IN-VIO | $0 |
| Mar 19, 2025 | Construction CLASS - 2 REISSUE #35672432N-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: CELLAR ELECTRICAL ROOM HAS SPALLING ON WALLS. REMEDY: COMPLY WITH CODE. #35691881M | Apr 23, 2025 POP/IN-VIO | $0 |
| Feb 8, 2024 | Construction CLASS - 1 REISSUE: 35671813M-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: (CELLAR LEVEL ELECTRICAL ROOM, CEILING WALLS HAVE SPALLING AND BOILER ROOM CEILING. REMEDY: COMPLY WITH CODE. #35672432N | Apr 22, 2024 POP/IN-VIO | $0 |
| Feb 6, 2024 | Construction CLASS - 2 28-301.1. REISSUE: 3565093Y-CELLAR LEVEL BOILER ROOM. THE LEVEL NEXT TO GAS METER HAVE BEEN REMOVED AND BOARDED UP. REMEDY: COMPLY WITH CODE. #35672435Z | Apr 22, 2024 POP/IN-VIO | $0 |
| Feb 2, 2023 | Construction CLASS - 2 REISSUE#35650693Y.NOTED AT CELLAR LEVEL BOILER ROOM,THE LEVERS NEXT TOI THE GAS METER HAVE BEEN REMOVED AND BOARDED UP WITH PLYWOOD.REMEDY:COMPLY WITH NOTICE OF VIOLATION.28-301.1 #35671808H | May 10, 2023 POP/IN-VIO | $0 |
| Feb 2, 2023 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT CELLAR LEVEL ELECTRICAL METER ROOM CEILING AND OIL BOILER ROOM WALLS BOTH HAVE SPALLING MASONRY IN VARIOUS AREAS THROUGHOUT.REMEDY:REPAIR AND/OR RE #35671813M | May 10, 2023 POP/IN-VIO | $0 |
| Mar 30, 2022 | Construction CLASS - 2 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P.115.6 (1968 CODE) FG+C APPENDIX E(E4)(2014 CODE)NOTED OBSERVED AT CELLAR BOILER ROOM/GAS METER ROOM LOUVERS FROM MECHANICAL VENTS ADJACENT TO GAS #35650693Y | Sep 14, 2022 POP/IN-VIO | $0 |
| May 10, 1999 | Construction Non-Hazardous WORK WITHOUT A PERMIT WORK NOTED AWING HAS BEEN CONSTRCUTED ABOVE THE 1ST FL LEVEL NORTH AND WEST SIDES OF BLDG REMEDY OBTAIN PERMITS APPROVALS FOR DOB A ERSTORE PREMISES TO PRIOR LEGAL CONDITION REMOVE #34209713Z | Jun 28, 1999 WRITTEN OFF | $0 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Sep 18, 2025 | Gas Piping - LL152 FTF-PL-PER Cycle 1, Sub-cycle B (premises is in Community District 2) | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)