Queens · Block 13655 · Lot 1 · 11422

253-50 149 Avenue

2 floors · 213,338 sq ft · built 1965 · class W1 · owner of record: Nyc Department Of Parks And Recreation

32open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
62dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 62 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-12-15 (Accepted). Agency page

Dec 31, 2026
in 62 days
2 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 213,338 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 183 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 183 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1158 days
Next cycle year 2029
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 13655). Agency page

Dec 31, 2035
in 3349 days
Next due 2035

Open violations

ECB / OATH (15)
IssuedViolationHearingBalance
Feb 13, 2026Construction CLASS - 2
REISSUE#35643129H ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY.UPON REVIEW OF DOB RECORDS TEMPORARY CERTIFICATE OF OCCUPANCY#401345594 EXPIRED 09/15/2004.REM:OBTAIN VALID COFO.
#35727119M
Mar 12, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. NOTED: EXIT DOOR #6 NOT SELF-CLOSING. REMEDY: REPAIR AND/OR REPLACE.
#35727122N
Mar 12, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
REISSUE ECB #35678897K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT MECHANICAL ROOF PAST TOP APPROX. 200FT OF PARAPET PROTECTIVE RAILING MISSING. REMEDY: PROVIDE PROTECTIVE RAILING.
#35727120J
Mar 12, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
REISSUE ECB #35678896Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: WATER LEAKS EXISTS AT: FRONT OF ELEVATOR ON 2ND FLOOR, CLASSROOM AND 228, CEILING 2D FLOOR BY STAIR D, INSIDE STAIR D HALLWAY
#35727121L
Mar 12, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: SEVERAL EXIT LIGHTS NOT WORKING THROUGHOUT SCHOOL. REMEDY: REPAIR AND/OR REPLACE.
#35727123P
Mar 12, 2026
POP/IN-VIO
$0
Sep 18, 2025Boilers CLASS - 2
FOUND BURNHAM GAS FIRED STEAM BOILER NOT OPERATING BECAUSE OF FLOODING OVER SUMMER MONTHS,ALL WIRING IN BURNER CABINET HAS WIRE AND CONTROL DAMAGE CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECT
#39160983X
Oct 20, 2025
POP/IN-VIO
$0
Feb 26, 2025Construction CLASS - 2
REISSUE #35643129H. ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2. NOTED C OF O TEMP. EXPIRED 09/15/2004. NO #401345594. REMEDY: OBTAIN VALID C OF O OR
#35692445K
Apr 18, 2025
POP/IN-VIO
$0
Mar 11, 2024Construction CLASS - 2
REISSUE #35665285R. ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-NOTED: TEMPORARY C OF O #401345594 EXPIRED ON 09/15/2004-BUILDING IS OCCUPIED AS A PUBLIC SCHOOL(
#35678895R
May 13, 2024
POP/IN-VIO
$0
Mar 11, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT MECHANICAL ROOM ROOF TOP, APPROX. 200FT. OF PARAPET/PROTECTIVE RAILING MISSING. REMEDY: PROVIDE PROTECTIVE RAILLING.
#35678897K
May 13, 2024
POP/IN-VIO
$0
Mar 11, 2024Construction CLASS - 2
REISSUE #35665287K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 2ND FLOOR VARIOUS CLASS ROOMS HAVE WATER PENETRATION THROUGH DEFECTIVE ROOF: CLASS ROOM #228, 229, 230, 231, 232, 233, 234, 2
#35678896Z
May 13, 2024
POP/IN-VIO
$0
Feb 13, 2023Construction CLASS - 2
REISSUE#35643128X(3/24/22)FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:AT 2ND FLOOR CLASSROOMS(ENTIRE)WINDOW HAS WATER PENETRATION ONTO WALLS,SILLS,CEILING.REM:REPAIR AND OR/REPLACE.
#35665286Z
May 30, 2023
POP/IN-VIO
$0
Feb 13, 2023Construction CLASS - 2
REISSUE#35643129H ALTERED/BUILDING OCCUPIED WITHOUT VALID COFO AS PER 28-118.3.1,28-118.3.2 COFO RECORDS#401345594 TEMPORARY EXPIRED ON 12/08/2004 AT 1 PERMIT ISSUED ON 2004 NOT SIGNED OFF.REM:OBTAIN VALID COFO
#35665285R
May 30, 2023
POP/IN-VIO
$0
Feb 13, 2023Construction CLASS - 2
REISSUE#35643129Y(3/24/2022)FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:AT ROOF TOP IN SEVERAL AREA WATER PUDDLE AND LEAKS AND 2NDFLOOR CLASSROOM(S).REM:REPAIR AND OR REPLACE.
#35665287K
May 30, 2023
POP/IN-VIO
$0
Mar 24, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED DURING INSPECTION OF 2ND FLOOR ROOMS 228,229,230,231,232,233,234,235,236,237,238,239,240,241,242,243,244,245,246,247 BY THE WINDOWS HAVE WATE
#35643128X
Jul 19, 2022
POP/IN-VIO
$0
Mar 24, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED ROOF LEVEL OVER(NEW)ROOM 231 IS POOLING WATER ABOUT 1/2 INCH OF WATER ACROSS THE ENTIRE ROOF.REM:REPAIR AND/OR REPLACE.
#35643127Y
Jul 19, 2022
POP/IN-VIO
$0
DOB (4)
IssuedViolationStatus
Jun 30, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
#08802
DOB VIOLATION - ACTIVE
Jun 30, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
#24292
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#29700
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#45369
DOB VIOLATION - ACTIVE
DOB NOW Safety (13)
IssuedViolationStatus
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Jun 30, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 30, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2020 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 30, 2026, 2:37 PM ET. BBL 4136550001.