Bronx · Block 3067 · Lot 1 · 10458

2502 Lorillard Place

5 floors · 135,985 sq ft · built 1912 · class W1 · owner of record: Nyc Department Of Education

28open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
69dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 69 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 69 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 135,985 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 190 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 190 days
Annual filing
Energy audit and retro-commissioning (2027) Likely applies
Local Law 87 · Calendar year 2027
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 3067). Agency page

Dec 31, 2027
in 434 days
Next due 2027
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-27 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (14)
IssuedViolationHearingBalance
May 19, 2026Construction CLASS - 2
REISSUE#35721379L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FPSC INTERIOR DOORS DO NOT SELF-CLOSE PROPERLY AT 2ND FLR-STAIRCASE C,G.1ST FLR-STAIRCASE A.BASEMENT STAIRCASE A,E.CLASSROOM DOORS D
#35731734X
Jul 10, 2026
POP/IN-VIO
$0
May 19, 2026Construction CLASS - 2
REISSUE#35721385H FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ON MAIN ROOF BRICKS ARE DISCOLORED AND MORTAR MISSING IN BETWEEN JOINTS IN SOME AREAS AT WEST & SOUTH ELEVATIONS.REM:REPAIR AND/OR R
#35731730Z
Jul 10, 2026
POP/IN-VIO
$0
May 19, 2026Construction CLASS - 2
REISSUE#35721382M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THROUGHOUT CELLAR METAL CEILING IS RUSTED & PEELING DUE TO WATER PENETRATIONS.STEEL BEAMS ARE ALSO IN DISREPAIR.REM:REPAIR AND/OR RE
#35731732M
Jul 10, 2026
POP/IN-VIO
$0
May 19, 2026Construction CLASS - 2
REISSUE#35721378J EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR DOORS DO NOT SELF-CLOSE PROPERLY WHEN TESTED AT EXIT 3 & EXIT 1.REM:REPAIR/REPLACE DOOR.
#35731735H
Jul 10, 2026
POP/IN-VIO
$0
May 19, 2026Construction CLASS - 2
REISSUE#35721384X FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:IN THE CELLAR IN FRONT OF MUSIC ROOM THE CEILING AND WALLS ARECRACKED AND IN DISREPAIR DUE TO WATER PENETRATIONS.REM:REPAIR AND/OR R
#35731731K
Jul 10, 2026
POP/IN-VIO
$0
May 19, 2026Construction CLASS - 2
REISSUE#35721380Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXTI DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY LIGHTS#S 21,24,27,26,22,15 & 14 WERE NOT
#35731733Y
Jul 10, 2026
POP/IN-VIO
$0
Aug 5, 2025Construction CLASS - 2
REISSUE#35692333Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.EMERGENCY LIGHTS NOT WORKING WHEN TESTED AT 1ST FL BOX#19
#35721380Z
Sep 5, 2025
POP/IN-VIO
$0
Aug 5, 2025Construction CLASS - 2
REISSUE#35692231P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT CELLAR LEVEL SPALLING & CRUMBLING PLASTER OR CEILING & WALLS OUTSIDE THE MUSIC ROOM DUE TO PAST WATER INFILTRATION FROM EXTERIOR EXPOSI
#35721384X
Sep 5, 2025
POP/IN-VIO
$0
Aug 5, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:THROUGHOUT CELLAR LEVEL CORRUGATED TIN CEILING ARE DETERIORATING & DETACHING. FIREPROOFING CRUMBLING AROUND STEEL BEAMS.SEVERAL STEEL BEAMS BEGUN TO CORROD
#35721382M
Sep 5, 2025
POP/IN-VIO
$0
Aug 5, 2025Construction CLASS - 2
REISSUE#356922232R FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.INTERIOR FPSC DOORS NOT CLOSING PROPERLY AT 3RD FL STAIR E 1ST FL STAIR A & E BASEMENT LEVEL KITCHEN ENTRY B60 CAFETERIA SMOKE DOORS BY E
#35721379L
Sep 5, 2025
POP/IN-VIO
$0
Aug 5, 2025Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING EXTERIOR DOORS AT EXIT#1,3,2,6 & 9 NOT PROPERLY SELF CLOSING WHEN TESTED.MENTIONED DOOR RUB ON FRAMES OR SCAFFOLDREM:REPAIR/REPLACE DOOR.
#35721378J
Sep 5, 2025
POP/IN-VIO
$0
Aug 5, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT ROOF LEVEL EAST MASONRY SMOKE STACK HAS WASHED OUT MORTAR BETWEEN BRIDES THROUGHOUT WEST & SOUTH ELEVATION.REM:REPAIR AND/OR REPLACE.
#35721385H
Sep 5, 2025
POP/IN-VIO
$0
Oct 4, 2024Construction CLASS - 2
REISSUE#35677129N DATE OF ISSUE:07.14.2024 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED SUB CELLAR LEVEL MUSIC ROOM FLOORING AND SPALLING EXPOSED REBAR AT CEILING GAS ROOM HAS PUDDLE OF WATER.REM
#35692231P
Dec 20, 2024
POP/IN-VIO
$0
Jul 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED SUB CELLAR MUSIC ROOM FLOODING AND SPALLING ON WALLS, OUTSIDE MUSIC ROOM SPALLING + EXPOSED REBAR AT CEILING, GAS ROOM HAS PUDDLE OF WATER, ELECTRIC
#35677129N
Nov 3, 2023
POP/IN-VIO
$0
DOB (5)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06394
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06393
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06392
DOB VIOLATION - ACTIVE
Dec 21, 2016ELEVATOR

#9028/591609
DOB VIOLATION - ACTIVE
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#02137
DOB VIOLATION - ACTIVE
DOB NOW Safety (9)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 23, 2026, 8:36 PM ET. BBL 2030670001.