4 floors · 67,840 sq ft · built 1961 · class W1 · owner of record: Nyc Department Of Parks And Recreation
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 65 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 67,840 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 186 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 186 days | Annual filing |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1161 days | Next cycle year 2029 |
| Energy audit and retro-commissioning (2034) Likely applies Local Law 87 · Calendar year 2034 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 7054). Agency page | Dec 31, 2034 in 2987 days | Next due 2034 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-11 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Jun 5, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THE CONCRETE PAVEMENT AT THE FRONT COURTYARD,EXPOSURE 1,AT THE BASE OF THE FLAGPOLE IS SEVERLY CRACKED CAUSING A DANGEROUS TRIP HAZARD.REM:REPAIR/REPL #35731997H | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THERE WERECLASSROOMS,CORRIDORS AND OFFICES THAT HAVE HANGING COMBUSTIBLE MATERIAL AS DECORATIONS AND DISPLAY.REM:REMOVE ALL HANGING MATERIALS. #35731999L | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THE ENTRY STAIRS AT EXPOSURE 1 AND 3 ARE IN NEED OF REPAIR.CONCRETE CHIPPED,FALLING OUT AND THE STEEL NOSING TREADS ARE LOOSE CAUSING TRIP HAZARDS.REM #35731998J | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 REISSUE#35721175J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:A LEAK IN THE ROOF IS CAUSING WATER DAMAGE TO CEILINGS AND WALLS AT CORRIDORS AND ROOMS BY STAIRWELL B AND D.REM:REPAIR/REPLACE FIX #35731994M | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 REISSUE#35720999H FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED: THE RAILING PARAPET AT ROOF LEVEL ON THE 27TH STREET SIDE EXP3 IS IN DISREPAIR DANGEROUS TO ANYONE ON THE ROOF.REM:REPAIR/REPLACE.X #35731995Y | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 REISSUE#35721176L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THERE WERE SEVERAL BROKEN WINDOWS AT T.O.I.OUTSIDE CLASSROOM 309 AND 333.REM:REPAIR/REPLACE. #35731993K | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 REISSUE#35721177N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT 2ND FLOOR,AUDITORIUM ENTRANCE DOOR NOT CLOSING PROPERLY.REMREPAIR/REPLACE. #35731992Z | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 REISSUE#35721179R FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:IN BOILER ROOM AT BASEMENT LEVEL,THE COLUMNS,CEILINGS AND WALLS ARE CRACKED,CHIPPED,AND FLAKING OFF.REM:REPAIR/REPLACE. #35731991R | Jul 27, 2026 POP/IN-VIO | $0 |
| Jun 5, 2026 | Construction CLASS - 2 REISSUE#35720998X NOTED:THE BULKHEAD AT STAIR B ALLOWS WATER PENETRATION WHEN RAINING.REM:REPAIR/REPLACE-FIX THE LEAK. #35731996X | Jul 27, 2026 POP/IN-VIO | $0 |
| Jul 7, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 2 FLOOR CORRIDOR BY 239, 221, AUDITORIUM ENTRANCE, STAGE FRONT LEFT, 1 FL. 127, 129, KITCHEN 163 AND CAFETERIA BY EXIT6 DOORS ARE NOT CLOSING PROP #35721177N | Aug 19, 2025 POP/IN-VIO | $0 |
| Jul 7, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT BULKHEAD STAIR B WATER PENETRATION IN STAIRWELL. REMEDY: REPAIR AND/OR REPLACE. #35720998X | Aug 19, 2025 POP/IN-VIO | $0 |
| Jul 7, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT ROOF FENCING ON 27 STREET SIDE DISCONNECTED AND ANGLED IN DISREPAIR. REMEDY:REPAIR AND/OR REPLACE. #35720999H | Aug 19, 2025 POP/IN-VIO | $0 |
| Jul 7, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 4 FLOOR AND STAIRWELL B AND D HALLWAYS, CLASSROOMS ROOF LEAKING WATER PENETRATION; SPALLING. REMEDY: REPAIR AND/OR REPLACE. #35721175J | Aug 19, 2025 POP/IN-VIO | $0 |
| Jul 7, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT GAS, ELECTRICAL AND BOILER ROOM. CEILINGS, WALLS AND COLUMNS RUNNING CRACKS.REMEDY: REPAIR AND/OR REPLACE. #35721179R | Aug 19, 2025 POP/IN-VIO | $0 |
| Jul 7, 2025 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT OUTSIDE CLASSROOMS 309 AND 333 14 BROKEN WINDOWS. REMEDY: REPAIR AND/OR REPLACE. #35721176L | Aug 19, 2025 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Aug 29, 1995 | LOCAL LAW 62/91 - BOILERS #23246 | DOB VIOLATION - ACTIVE |
| Aug 29, 1995 | LOCAL LAW 62/91 - BOILERS #23247 | DOB VIOLATION - ACTIVE |
| Aug 16, 1993 | LOCAL LAW 62/91 - BOILERS #21202 | DOB VIOLATION - ACTIVE |
| Aug 16, 1993 | LOCAL LAW 62/91 - BOILERS #21203 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Sep 18, 2025 | Gas Piping - LL152 FTF-PL-PER Cycle 1, Sub-cycle B (premises is in Community District 13) | Active |
None open.