| Requirement | Due | Status |
|---|---|---|
| Annual property registration Applies HPD registration · September 1 each year What this isResidential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page | Overdue | Registration expired 2026-09-01 |
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 65 days | Keep the report on file (not filed with DOB) |
| Bedbug annual filing Applies Local Law 69 · December 1 to 31 each year What this isOwners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page | Dec 31, 2026 in 65 days | Annual |
| Annual boiler inspection (1 boiler) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2023-01-20 (Accepted). Agency page | Dec 31, 2026 in 65 days | 1 of 1 without an accepted 2026 report yet |
| Annual notice: window guards and lead paint Applies HPD / Health Code · January 1 to 16 each year What this isDeliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page | Jan 16, 2027 in 81 days | Annual |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 77,740 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 186 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 186 days | Annual filing |
| Energy audit and retro-commissioning (2027) Likely applies Local Law 87 · Calendar year 2027 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1777). Agency page | Dec 31, 2027 in 430 days | Next due 2027 |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 796 days | Next cycle year 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Sep 9, 2025 | Elevators CLASS - 1 CLASS 1 ITEM: DISC BRAKE MONITOR TURNED OFF. CLASS 2 ITEM: MAINTENANCE LOG MISSING ENTRIES. MISALIGNED CAB MIRROR. REPLACE WORN GIBS WHERE NEEDED. #39159745M | Nov 19, 2025 DEFAULT | $6,250 |
| Jul 16, 2024 | Elevators CLASS - 2 CLASS 2: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS PRESENTS A SAFETY HAZZARD TO RESIDENTS. RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. WHEN SERVICE RESTORED CONTACT NYCDOB AT EIR@BUI #39119171X | Sep 25, 2024 DEFAULT | $3,125 |
| Mar 18, 2022 | Boilers CLASS - 2 INOPERABLE FRESH AIR FAN NOT INTERLOCKED WITH BOILER, SAIL SWITCH BYPASSED. REPLACE SAIL SWITCH. #39058323J | Jul 20, 2022 IN VIOLATION | $0 |
| Apr 26, 2018 | Elevators CLASS - 2 59BB7,5E1,10H11,16E1,17H11,3D6,67L10,56Y2,56Y13-59BB7)MACHINE BRAKE MAINTENANCE TAG EXPIRED, PROVIDE. 5E1)CAR DOOR RUBBING, ADJUST. 10H11)CAR DOOR GIBS WORN, REPLACE. 16E1)HOISTWAY DOOR RUBBING, ADJUST. 17H11)H #38262977K | Jun 25, 2018 STIPULATION/IN-VIO | $0 |
| Apr 5, 2018 | Elevators CLASS - 1 97X17 THE ONLY ELEVATOR IN BLDG OUT OF SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE4 CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. RMDY: RESTORE TO SERVICE IMMEDIATELY AND NOTIFY NYCD #38262129H | Jun 4, 2018 IN VIOLATION | $0 |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #15331 | DOB VIOLATION - ACTIVE |
| Jun 30, 2023 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION #42311 | DOB VIOLATION - ACTIVE |
| Jun 20, 2023 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION #42642 | DOB VIOLATION - ACTIVE |
| Apr 25, 2023 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION #16164 | DOB VIOLATION - ACTIVE |
| Oct 7, 2021 | ELEVATOR #9027/708926 | DOB VIOLATION - ACTIVE |
| Sep 11, 2020 | ELEVATOR #9027/690637 | DOB VIOLATION - ACTIVE |
| Sep 6, 2019 | ELEVATOR #9027/655985 | DOB VIOLATION - ACTIVE |
| May 30, 2014 | (OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST #05401 | DOB VIOLATION - ACTIVE |
| Aug 16, 1993 | LOCAL LAW 62/91 - BOILERS #32598 | DOB VIOLATION - ACTIVE |
| Aug 16, 1993 | LOCAL LAW 62/91 - BOILERS #32599 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction | Active |
| Oct 23, 2023 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction | Active |
| Jun 30, 2023 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Jun 20, 2023 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Apr 25, 2023 | Boiler LBLVIO VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2022 INSPECTION REPORT | Active |
| May 30, 2014 | Elevators ACC1 | Active |