Brooklyn · Block 7261 · Lot 201 · 11235

25 Brighton 4 Road

3 floors · 332,328 sq ft · built 1960 · class W1 · owner of record: Nyc Department Of Education

25open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
188dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 67 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 332,328 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 188 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 188 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1163 days
Next cycle year 2029
Energy audit and retro-commissioning (2031) Likely applies
Local Law 87 · Calendar year 2031
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 7261). Agency page

Dec 31, 2031
in 1893 days
Next due 2031
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-01-20 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (23)
IssuedViolationHearingBalance
Jun 16, 2026Construction CLASS - 2
REISSUE#35719819N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THERE ARE 2 GLASS WINDOW PANELS THAT ARE CRACKED IN THE GYM.REM:REPAIR/REPLACE THE CRACKED,BROKEN GLASS.
#35732540M
Jul 20, 2026
POP/IN-VIO
$0
Jun 16, 2026Construction CLASS - 2
REISSUE#35719927K FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCESNOTED:AT ROOFTOP AND ABOVE THE CHIMNEY AND FAN ROOM HAVE CRACKS IN THEBRICK VENEER IN A STAGGERED/VERTICAL DESIGN.REM:REPAIR/REPLACE-FIX CRA
#35732542X
Jul 20, 2026
POP/IN-VIO
$0
Jun 16, 2026Construction CLASS - 2
REISSUE#35719822Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:CONCRETE RAMP AT EXPOSURE 2 HAS CRACKED AND FAILING CONCRETE ON THE UNDER SIDE ABOVE PARKING SPOT#53.REM:REPAIR/REPLACE.
#35732538N
Jul 20, 2026
POP/IN-VIO
$0
Jun 16, 2026Construction CLASS - 2
REISSUE#35719821M FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THE CHAIN LINK FENCE AT ATHLETIC FIELD IN NEED OF SERIOUS REPAIRS.THE VERTICLE POSTS ARE BENT WAY OUT OF PLUMB,AND THE BASE WALL IS
#35732539P
Jul 20, 2026
POP/IN-VIO
$0
Jun 16, 2026Construction CLASS - 2
REISSUE#35719817J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT T.O.I.THERE WERE SEVERAL EMERGENCY LIGHTS THAT WERE NOT OPERABLE WHEN TESTED.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CO
#35732541Y
Jul 20, 2026
POP/IN-VIO
$0
Jul 11, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXOTS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED EMERGENCY LIGHTS NOT OPERATIVE WHEN TESTED: AT 2ND FL CORRIDOR BY
#35719817J
Aug 19, 2025
POP/IN-VIO
$0
Jul 11, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED CHAIN LINK FENCE AND BASE WALLS IN STATE OF DISREPAIR. AT EXP #3 ATHLETIC FIELD12' TALL CHAIN LINK FENCE HAD VERTICAL POST BENT SEVERLY WITH CROSS BR
#35719821M
Aug 19, 2025
POP/IN-VIO
$0
Jul 11, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT EXP #2, RAMP, UNDERSIDE HAD CRACKED AND SPALLING AREA AT CONCRETE ALONG HORIZONTAL BEAM WHICH WAS LOCATED DIRECTLY ABOVE PARKING SPOT #53. REMEDY:
#35719822Y
Aug 19, 2025
POP/IN-VIO
$0
Jul 11, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED TWO CRACKED/BROKEN WINDOW GLASS PANELS INSIDE GYMNASIUM ADJACENT TO NORTH-EAST FACING WALL CORNER. REMEDY: REPAIR AND/OR REPLACE.
#35719819N
Aug 19, 2025
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 2
REISSUE #35672931H: WORK WITHOUT A PERMIT AT 3RD FLOORS LEVEL PARTITIONS INSTALLED FROM ROOM 342, 328, AND 356 TO ONE SMALLER CLASSROOMS. NORECORDS OR PERMIT AT TIME OF INSPECTION. REMEDY: OBTAIN PERMIT.
#35719928M
Jul 14, 2025
POP/IN-VIO
$0
May 28, 2025Construction CLASS - 2
REISSUE #35677336X: FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES: AT ROOFTOP LEVEL OBSERVED AT CHIMNEY AND TANS ROOM STAGGERING CRACKS IN VERTICALLY LINES. REMEDY: MAINTAIN EXTERIOR BUILDING WALL(S).
#35719927K
Jul 14, 2025
POP/IN-VIO
$0
Jul 29, 2024Construction CLASS - 2
REISSUE #35672930X. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT ROOF LEVEL CHIMNEY AND FANS ROOM CRACK IN WALL IN VERTICALLY AND STAGGERED CRACKS. REMEDY: MAINTAIN EXTERIOR WALL(S)
#35677336X
Sep 25, 2024
POP/IN-VIO
$0
Apr 3, 2023Construction CLASS - 2
REISSUE #35655220R FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.ROOF LEVEL CHIMNEY & FAN RM HAVE CRACKS IN WALL.REMEDY:MAINTAIN EXTERIOR BUILDING WALL.
#35672930X
Jul 5, 2023
POP/IN-VIO
$0
Apr 3, 2023Construction CLASS - 2
REISSUE #35128575L WORK W/O PERMIT.RM 356, 328 & 342 A&B WALL MADE MAKING 3 RM OUT OF ONE.REMEDY:OBTAIN ALL REQUIRED PERMITS.
#35672931H
Jul 5, 2023
POP/IN-VIO
$0
Jun 2, 2022Construction CLASS - 2
REISSUE#35561184L FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. NOTED:OBSERVED DURING INSPECTION OF ROOF LEVEL,CHIMNEY AND FAN ROOMSTRUCTURE HAS CRACKS THROUGHOUT. REMEDY: MAINTAIN EXTERIOR BLDG WALL
#35655220R
Nov 9, 2022
POP/IN-VIO
$0
May 19, 2021Construction CLASS - 2
REISSUE:352356698P.FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES.NOTED:CHIMNEY AND SO.EAST CORNER HAS VERTICAL CRACKS.SE CORNER APPROX 8FT IN LENGTH.REMEDY:COMPLY WITH CODE.
#35561184L
Oct 27, 2021
POP/IN-VIO
$0
Apr 22, 2020Construction CLASS - 2
REISSUE#35386598X FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES NOTED AT ROOF LEVEL BRICK CHOMNEY HAS VERTICAL CRACK APPROX 8 FT LONG REPAIR THE CRACK
#35473475L
Oct 14, 2020
POP/IN-VIO
$0
May 9, 2019Construction CLASS - 2
RE-ISSUE #35324785H.FAILURE TO MAINTAIN BLD.WALLS & APPURTENANCES.NOTED,AT ROOF LEVEL CHIMNEY SMOKE STACK HAS A VERTICAL CRACK 8' LONG THRO UGH BRICK.REM:MIANTAIN EXTERIOR BUILDING WALLS.
#35386598X
Sep 23, 2019
POP/IN-VIO
$0
Mar 14, 2018Construction CLASS - 2
REISSUE#35235698P FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT ROOF LEVEL CHIMNEY SMOKE STACK HAVE VERTICAL CRACK THROUGH THE BRICK MASONRY APPROX 8FT LONG. REMEDY: MAKE NECESSARY REPAIRS.
#35324785H
Jun 11, 2018
POP/IN-VIO
$0
Apr 19, 2017Construction CLASS - 2
FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. NOTED: @ TIME OF INSP OBSERVED ON THE ROOF LEVEL, CHIMNEY SMOKE STACK HAVE A VERTICAL CRACK THROUGH THE BRICK MASONRY @ SOUTH-EAST CORNER APPROX 8FT IN LENGTH.
#35235698P
Jul 17, 2017
POP/IN-VIO
$0
May 6, 2015Unknown CLASS - 2
WORK W/O PERMIT. INSTALLED FULL HEIGHT PARTITIONS. REISSUE ECB # 35023804P IN ROOMS 356,328 AND 342A&B, INSTALLED FULL HEIGHT PARTITIONS. RMDY: COMPLY WITH NOV.
#35128575L
Jun 15, 2015
POP/IN-VIO
$0
Sep 29, 2011Unknown CLASS - 2
REISSUE # 34861740L DIVIDED CLASS ROOMS INSTALLED NON FIRE PROOF WOOD PARTITIONS W/ SUSPENDED LIGHTS PASSING THROUGH @ ROOMS 342, 337, C34 CREATING C36, 328 CREATING 356. NOTE : 328 TO 356 W/ ROOM TO ROOM VENT
#34928049K
Dec 5, 2011
POP/IN-VIO
$0
Jun 5, 2009Unknown CLASS - 2
REISSUE: 34698560R, 35Y,32N,77X,99N. WORK W/O PERMIT. NOTED: FULL PARTITIONS WALL IN PLACE AT ROOM C-34, C-32, C-36, 337-A, 337-B, 342A, 342B, 356, AND 328 WHICH HAS NO VENTILATION. REMEDY: LEGALIZE WALLS
#34779773P
Aug 10, 2009
WRITTEN OFF
$0
DOB (1)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#14061
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 25, 2026, 9:58 PM ET. BBL 3072610201.