Brooklyn · Block 2408 · Lot 32 · 11211

243 South 2 Street

4 floors · 9,413 sq ft · built 2003 · class I5 · owner of record: Nyc Department Of Education

14open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
781dto Gas piping inspection (2028 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 50 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 1 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 781 days
Next cycle year 2028
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-08-04 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (9)
IssuedViolationHearingBalance
Jun 17, 2025Boilers CLASS - 2
#1 AO SMITH BTP-200 GAS HOT WATER HEATER HAS WATER LEAKING FROM SAFETY VALVE+BOTH HW RE CIRCULATORS DEFECTIVE+BOILER ROOM DOOR DOES NOT CLOSE INTO FRAME, MAINTAIN BOILER; CORRECT VIOLATION AND SUBMIT CERTIFICAT
#39151269Y
Jun 30, 2025
POP/IN-VIO
$0
Apr 27, 2022Boilers CLASS - 2
#2 BOILER BAROMETRC DAMPER NOT WORKING,SPILL SWITCH IN WRONG PLACE,MISSING CLEAN OUT AT BASE OF CHIMNEY
#39061155R
May 11, 2022
POP/IN-VIO
$0
Mar 16, 2021Construction CLASS - 1
POWERE FLAME BURNER JR15A-10ATI REPLACES ON HB SMITH BOILER WITHOUT A PERMIT. ACQUIRE A PERMIT & REGISTER BURNER
#39037681R
Apr 16, 2021
POP/IN-VIO
$0
Mar 16, 2021Boilers CLASS - 1
IMPROPER COMBUSTION ON HB SMITH BOILER 19HE-03 BOILER. CARBONIZING. CEASE USE. CCORRECT HAZARDOUS CONTION IMMEDIATELY&DO NOT OPERATE. CALL DOB TO LIFT C/U 2123932784
#39037684M
Apr 16, 2021
POP/IN-VIO
$0
Mar 16, 2021Boilers CLASS - 1
IMPROPER COMBUSTION ON HBSMITH 19HE-3 BOILER BOILER CARBONIZING. CORRECT HAZARDOUS CONDITION IMMEDIATELY. DO NOT OPERATE, CALL DOB TO LIFT C/U 2123932784
#39037682Z
Apr 16, 2021
POP/IN-VIO
$0
Mar 16, 2021Construction CLASS - 1
POWER FLAME BURNER MODEL JR15A-10ATI REPLACED ON HB SMITH BOILER WITHOUT A PERMIT. ACQUIRE A PERMIT & REGISTER BURNER.
#39037683K
Apr 16, 2021
POP/IN-VIO
$0
May 25, 2018Boilers CLASS - 2
24B,32A,50,50A,50B,50C,50D,50E,50F. 50-POOR FLUE CONNECTION AT BOILER 50A-GAS REGULATOR SPRING COVER IS MISSING; 50B-GAS VENT PIPE HAS OPEN END; 50C-FRESH AIR FAN AIR PORVING SWITCH MISSING AND INTERLOCKED WITH
#32096799H
Aug 13, 2018
POP/IN-VIO
$0
May 25, 2018Boilers CLASS - 2
5B,24B,34B,50,50A,50B,50C,50D,50E. 50-SPILL SWITCH IS DEFECTIVE; 50A-POOR FLUE CONNECTION AT BOILER; 50B- GAS VENT PIPE HAS OPEN END; 50C-FRESH AIR FAN AIR PROVING SWITCH IS MISSING AND INTERLOCKED WITH
#32096798X
Aug 13, 2018
POP/IN-VIO
$0
Feb 4, 2015Construction CLASS - 2
OCCUPANCY CONTRARY TO THAT ALLOWED BY CERTIFICATE OF OCCUPANCY OR BLDGDEPT RECORDS. CERTIFICATE OF OCCUPANCY 300994306 EFFECTIVE 11-16-2005 DOES NOT REFLECT CREATION OF ROOF TOP PLAY AREA.RMDY:DISCONTINUE ILLEG
#35119789M
Mar 23, 2015
POP/IN-VIO
$0
DOB (1)
IssuedViolationStatus
Aug 16, 1993LOCAL LAW 62/91 - BOILERS

#39111
DOB VIOLATION - ACTIVE
DOB NOW Safety (4)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Jan 8, 2026Gas Piping - LL152 FTF-PL-PER
Cycle 2, Sub-cycle A (premises is in Community District 1)
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 11, 2026, 5:37 PM ET. BBL 3024080032.