Manhattan · Block 774 · Lot 19 · 10011

233 West 24 Street

11 floors · 400,000 sq ft · built 1938 · class W1 · owner of record: Nyc Department Of Education

31open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
47dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 47 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 400,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Energy audit and retro-commissioning (2034) Likely applies
Local Law 87 · Calendar year 2034
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 774). Agency page

Dec 31, 2034
in 2969 days
Next due 2034
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. Agency page

On fileCycle 10 filing on record: SWARMP (2025-07-14)

Open violations

ECB / OATH (22)
IssuedViolationHearingBalance
Apr 23, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.FROM 9TH FLOOR TO 1ST FLOOR ALL 1 CORRIDOR DOORS NOT CLOSING PROPERLY.ALSO FROM 9TH TO1ST EXIT TO STAIR DOOR ALL HAVE KNOBS AND NO PUSH BAR.REM:COMPLY WITH
#35732358X
May 21, 2026
POP/IN-VIO
$0
Apr 23, 2026Construction CLASS - 2
REISSUE:35720692N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ROOF LEVEL ROOFING MATERIAL HAS BUBBLES,BLISTER THROUGHOUT.REM:COMPLY WITH CODE.
#35732357Y
May 21, 2026
POP/IN-VIO
$0
Apr 23, 2026Construction CLASS - 2
28-301.1 REISSUE:35720694R MISCELLANEOUS VIO-GAS METER ROOM HAS NO VENTILATION.REM:COMPLY WITH CODE.
#35732356M
May 21, 2026
POP/IN-VIO
$0
Jul 3, 2025Construction CLASS - 2
28-302.1. REISSUE #35684886X DATE OF ISSUE: 09-27-2024. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE) FGC APPENDIX E(E4)(2014 CODE). AT THE TIME OF INSPECTION OBSERVED AND NOTED AT CELL
#35720694R
Aug 28, 2025
POP/IN-VIO
$0
Jul 3, 2025Construction CLASS - 2
REISSUE #35684888J DATE OF ISSUE: 09-27-2024. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT ROOF LEVEL(THE ROOF ABOVE THE 10TH FLOOR). THERE ARE LARGE BU
#35720692N
Aug 28, 2025
POP/IN-VIO
$0
Sep 27, 2024Construction CLASS - 2
28-301.1. RE-ISSUE #35674736L. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE), FGC APPENDIX E(E4)(2014 CODE). NOTED;OBSERVED AT CELLAR, THE GAS METER ROOM HAS NO FRESH AIR VENTILATION. R
#35684886X
Oct 30, 2024
POP/IN-VIO
$0
Sep 27, 2024Construction CLASS - 2
RE-ISSUE #35674738P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AT ROOF LEVEL(THE ROOF ABOVE THE 10 FLOOR), THERE ARE LARGE BUSTERS AT VARIOUS LOCATION, THROUGHOUT. REMEDY: REPAIR AN
#35684888J
Oct 30, 2024
POP/IN-VIO
$0
May 23, 2023Construction CLASS - 2
28-301.1 REISSUE#35643325P NOTED:THE GAS METER ROOM AT CELLAR LEVEL DOES NOT HAVE NATURAL OR MECHANICAL VENTILATION INSTALLED.REM:COMPLY WITH NOTICE OF VIOLATION.
#35674736L
Sep 14, 2023
POP/IN-VIO
$0
May 23, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:THE ROOF OVER THE 10TH FLOOR LEVEL GYMNASIUM HAS LARGE BLISTERS IN VARIOUS AREASTHROUGHOUT.REM:REPAIR AND/OR REPLACE.
#35674738P
Sep 14, 2023
POP/IN-VIO
$0
May 6, 2022Construction CLASS - 2
28-301.1 REISSUE35561086H FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6@BSMT LEVEL IN GAS METER RM NO FRESH AIR VENTILATION AS PER CODE.COMPLY W/NOTICE OF VIOLATION.COMPLY W/NOTICE OF VIOLATION.
#35643325P
Sep 1, 2022
POP/IN-VIO
$0
May 7, 2021Construction CLASS - 2
28-301.1 REISSUE35495251J DOI4.27.20 VENTILATION TO GAS METER RM PER P115.6(1968CODE) FGC APPENDIXE(E4)(2019CODE) NOTE:@BSMT LEVEL IN GAS METER RM NO FRESH AIR VENTILATION AS PER CODE.COMPLY W/NOTICE OF V.
#35561086H
Aug 12, 2021
POP/IN-VIO
$0
Apr 27, 2020Construction CLASS - 2
BC283011-REISSUE 35415552K.FAILURE TO PROVIDE VENTILATION TO GAS METERROOM PER P115.6(1968 CODE)FGC APPENDIX E(E4)(2014 CODE)NOTE:AT BASEMENT LEVEL IN GAS METER ROOM NO FRESH AIR VENTILATION AS PER CODE.REMEDY:
#35495251J
Aug 13, 2020
POP/IN-VIO
$0
Apr 15, 2019Construction CLASS - 2
28-302.1 REISSUED#35297398R FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6(1968 CODE) FGC APPENDIX E(E4)(2014 CODE). NOTE AT BASEMENT LEVEL IN GAS METER ROOM NO FRESH AIR VENTILATION OR NATURAL AI
#35415552K
Jun 27, 2019
POP/IN-VIO
$0
Feb 14, 2018Construction CLASS - 2
REISSUED #35234945Z,3-16-17. NO VENTILATION OR NATURAL AIR INTAKE FOR GAS METER ROOM. REMEDY: NEED PROPER VENTILATION OR NATURAL AIR INTAKE FOR GAS ROOM.
#35297398R
May 3, 2018
POP/IN-VIO
$0
Mar 16, 2017Construction CLASS - 2
REISSUE#35177489X FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER.NO VENTILATION OR NATURAL AIR INTAKE FOR GAS METER ROOM AT CELLAR LEVEL CONTRARY TO 27-766. REMEDY: COMPLY W/SUMMONS PROVIDE VENTILATION.
#35234945Z
Apr 27, 2017
POP/IN-VIO
$0
Jun 6, 2016Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FRESH AIR VENT IN GAS METER ROOM. @ CELLAR GAS METER ROOM, NO FRESH VENTILATION VENT OBSERVED. RE-ISSUE ECB# 35119906M. REM: COMPLY W/ NOV.
#35177489X
Sep 15, 2016
POP/IN-VIO
$0
Jan 29, 2015Unknown CLASS - 2
27-766. REISSUE #35094227M NO FRESH AIR INLET (FAI) AT CELLAR GAS METER ROOM. RMDY: PROVIDE FAI.
#35119906M
Mar 19, 2015
POP/IN-VIO
$0
Apr 15, 2014Unknown CLASS - 2
27-766. RE-ISSUE # 35015680M. NO FRESH AIR INLET (FAI). AT CELLAR GAS METER ROOM. REMEDY: PROVIDE F.A.I.
#35094227M
Jun 19, 2014
POP/IN-VIO
$0
Apr 3, 2013Unknown CLASS - 2
SEC. 27-766. REISSUE 34941678J. NO FRESH AIR VENTILATION GAS METER RM.REMEDY: PROVIDE VENTILATION.
#35015680M
May 16, 2013
POP/IN-VIO
$0
Apr 17, 2012Unknown CLASS - 2
SEC. 27-766 REISSUE 34923280K,34847784M FAILURE TO PROVIDE F.A.I. IN GAS METER ROOM BASEMENT. REMEDY: PROVIDE F.A.I.
#34941678J
Jun 14, 2012
POP/IN-VIO
$0
Jul 20, 2011Unknown CLASS - 2
SEC. 27-766. REISSUE #34847784M. NO FRESH AIR VENT. AT CELLAR LEVEL GAS METER ROOM, NO FRESH AIR VENTILATION. REMEDY: PROVIDE FRESH AIR VENT.
#34923280K
Sep 15, 2011
POP/IN-VIO
$0
Apr 16, 2010Construction CLASS - 2
FAILURE TO MAINTAIN OBSERVED NO FRESH AIR VENTILATION IN GAS METER ROOM REM: PROVIDE VENTILATION
#34847784M
Jul 15, 2010
WRITTEN OFF
$0
DOB (4)
IssuedViolationStatus
Dec 13, 2016CONSTRUCTION
THE BORO-COMM HAS ORDER ALL WORK STOPPED FOR APPLICATION #122058290, THE APPLICANT OF RECORD HAS WITHDRAWN AS A PERMIT HOLDER - STOP WORK REMEDY: STOP WORK, PROVIDE ALL REQUIRED INFORMATION FORTHWITH
#0402MS
DOB VIOLATION - ACTIVE
Mar 10, 2016CONSTRUCTION
BORO-COMM
#0401EH
DOB VIOLATION - ACTIVE
Mar 31, 2008EMERGENCY POWER

#NRF00263
DOB VIOLATION - ACTIVE
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#00528
DOB VIOLATION - ACTIVE
DOB NOW Safety (5)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Feb 22, 2022Facades FISPNRF
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
Active
Mar 31, 2008Emergency Power FTF-EL-ENRF
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 11:03 AM ET. BBL 1007740019.