Bronx · Block 3158 · Lot 5 · 10457

2240 Grand Concourse

5 floors · 16,510 sq ft · built 1915 · class HR · owner of record: Concourse Residence Corp.

12open violations
$6,125ECB/OATH penalties owed
3HPD class C (immediately hazardous)
1165dto Gas piping inspection (2029 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 69 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1165 days
Next cycle year 2029
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-22 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (9) · $6,125 owed
IssuedViolationHearingBalance
Apr 30, 2026Construction CLASS - 1
OBSERVED LACK OF SPRINKLER COVERAGE ON FLRS 1 THROUGH 5 PER BC 28-301.1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2; 27-954., REPA
#39186710X
Feb 19, 2027
$2,500
Jan 3, 2024Construction CLASS - 1
UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS STATED IN ECB# 39094408R ISSUED ON 09/08/2023. PURSUANT TO 28-201.1 AND1RCNY 102-01., COMPLY WITH COMMISSIONER'S ORDER; FILE A CERTIFICATE OF CORRECTI
#39102621N
Mar 15, 2024
IN VIOLATION
$2,500
Sep 8, 2023Construction CLASS - 3
OBSERVED THROUGHOUT BUILDING ESCUTCHEON PLATES ARE NOT FLUSH WITH CEILING., REPAIR AND OR REPLACE
#39094410X
May 17, 2024
IN VIOLATION
$500
May 4, 2022Construction CLASS - 2
AT ROOF LEVEL, FENCE INSTALLED ON PARAPET WALL, EXP # 2, IS PARTIALLY COLLAPSED TOWARDS THE BUILDING., REPAIR AND/OR REPLACE
#39061579K
Aug 5, 2022
IN VIOLATION
$625
Jun 8, 2018Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED AT CELLAR LEVEL WATER SERVICE STORAGE ROOM, A 3"WATER SERVICE FOR MORE THAN 150 FIRE SPRINKLERS HEAD IT IS SUFFICIENT SIZE (3" TO 60 HEADS, 3 1/2"
#35331758H
Aug 22, 2018
IN VIOLATION
$0
Mar 28, 2018Construction CLASS - 1
FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NOTED: AT FRONT OF BLDG,NO FIRE DEPT CONNECTION INSTALLED AS IN REQUIRED OF A BLDG THAT HAS MORE THAN 35 HEADS. THIS BLDG HAS MORE THAN 35 SPRINKLER HEADS.
#35325772N
May 18, 2018
IN VIOLATION
$0
Mar 17, 2018Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT CELLAR LEVEL,A 3"WATER SERVICE FOR MORE THAN 150 FIRE SPRINKLER HEADS IT IS INSUFFICIENT SIZE OF SERVICE FOR THE FIRE-SPRINKLER SYSTEMS IN THIS BUILDING
#35322573R
May 4, 2018
IN VIOLATION
$0
Dec 2, 2017Construction CLASS - 1
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN CELLAR A 3" WATER SERVICE FOR MORE THAN 150 FIRE SPRINKLER HEADS WHICH IS AN INSUFFICIENT SIZE OF SERCICE FOR THE FIRE SPRINKLER SYSTEM IN THIS BLD
#35297554J
May 11, 2018
IN VIOLATION
$0
Oct 20, 2017Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED IN CELLAR A 3'WATER SERVICE FOR MORE THAN 150 FIRE SPRINKLER HEADS SHICH IS INSUFFUCIENT SIZE OF SERVICE FOR THE SPRINKLER SYSTEM IN THIS BUILDING
#35294421M
Dec 29, 2017
IN VIOLATION
$0
DOB (1)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06502
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
HPD (5) · C 3 · B 2 · A 0
IssuedClassViolationCorrect by
Feb 7, 2024BApt 408 · § 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT B-ROOM 408, 4th STORY, 5th B-ROOM FROM EAST AT SOUTHMar 13, 2024
Feb 7, 2024BApt 410 · § 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT B-ROOM 410, 4th STORY, 3rd B-ROOM FROM EAST AT SOUTHMar 13, 2024
Jan 22, 2024CApt 211 · § 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.Jan 26, 2024
Jan 22, 2024CApt 211 · § 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.Jan 26, 2024
Jul 24, 2012CApt 211 · § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) CEILING IN THE BATHROOM LOCATED AT B-ROOM 211, 2nd STORY, 2nd B-ROOM FROM EAST AT SOUTHAug 19, 2012

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 23, 2026, 8:29 PM ET. BBL 2031580005.

Look up another building