Bronx · Block 3049 · Lot 37 · 10457

2195 Bathgate Avenue

5 floors · 51,500 sq ft · built 1931 · class W1 · owner of record: Nyc Department Of Education

28open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
67dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 67 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 67 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 51,500 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 188 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 188 days
Annual filing
Energy audit and retro-commissioning (2029) Likely applies
Local Law 87 · Calendar year 2029
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 3049). Agency page

Dec 31, 2029
in 1163 days
Next due 2029
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-22 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (21)
IssuedViolationHearingBalance
May 20, 2026Construction CLASS - 2
REISSUE: 35721558R DATE OF ISSUE; 07/29/25. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED EXP #4 RETAINING WALL HAS SPALLED/MISSING AREAS OF CONCRETE ALONG
#35733017M
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE #35721554J DATE OF ISSUE: 07/29/2025. EXIT DOORS NOT SELF-CLOSING PROPERLY. AT THE TIME OF INSPECTION WHEN TESTED AT EXOT #7, 6, 4, 3, 2 AND 1 WERE NOT PROPERLY SELF-CLOSING. REMEDY: REPAIR OR REPLACE A
#35733020N
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE: 35721556N DATE OF ISSUE: 07/29/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME TIME OF INSPECTION OBSERVEDAND NOTED INTERIOR STEEL STEPS AT STAIRWELL "D" LEADING TO EXIT-4 WERE
#35733018Y
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE #35721553H DATE OF ISSUE: 07/29/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGESAND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT THE TIME OF INSPECTION
#35733021P
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE #35721552X DATE OF ISSUE: 07/29/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT THE TIME OF INSPECTION FPSE DOORS ARE NOT SELF-CLOSING PROPER
#35733022R
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE #35721555L DATE OF ISSUE: 07/29/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED SPALLING AND CRUMBLING PLASTER ON WALL AT STAIRWELL 'D' BULKHEAD
#35733019X
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE #35684930Y DAET OF ISSUE: 09/27/2024. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES AT YARD 2ND FLOOR WINDOW SECTION OF BRICKS CRACKED ABOVE 4TH AND 5TH FLOOR WALL CRACKED. EXPOSURE 1(FRONT) CRA
#35733023Z
Jun 26, 2026
POP/IN-VIO
$0
Jul 29, 2025Construction CLASS - 2
REISSUE #35684931X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED EMERGENCY LIGHTS NOT WORKING WHEN TESTED: (3)
#35721553H
Sep 5, 2025
POP/IN-VIO
$0
Jul 29, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED EXP #4 RETAINING WALL HAS SPALLED/MISSING AREAS OF CONCRETE ALONG THE TOP. REMEDY: REPAIR AND/OR REPLACE.
#35721558R
Sep 5, 2025
POP/IN-VIO
$0
Jul 29, 2025Construction CLASS - 2
REISSUE #35684933J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED INTERIOR FPSC DOORS NOT CLOSING PROPERLY AT: 4TH FL CORRIDOR SMOKE DOOR BY 404A, 3RD FL SMOKE DOOR BY 303, CLASSROOM DOORS #303 A
#35721552X
Sep 5, 2025
POP/IN-VIO
$0
Jul 29, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED INTERIOR STEEL STEPS AT STAIRWELL D, LEADING TO EXIT #4, WERE HEAVILLY CORRODEDWITH LARGE HOLE ALONG STEP RISER(4TH FROM BOTTOM). REMEDY: REPAIR AND/
#35721556N
Sep 5, 2025
POP/IN-VIO
$0
Jul 29, 2025Construction CLASS - 2
REISSUE #35684932H. EXIT DOOR NOT SELF-CLOSING. EXTERIOR DOORS AT EXIT#7, 6, 4, 3, 2 AND 1 WERE NOT PROPERLY SELF-CLOSING WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.
#35721554J
Sep 5, 2025
POP/IN-VIO
$0
Jul 29, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED SPALLING AND CRUMBLING PLASTER ON WALL AT STAIRWELL D BULKHEAD AND AT EXIT #7 VESTIBULE ABOVE THE EXIT DOORS. REMEDY: REPAIR AND/OR REPLACE.
#35721555L
Sep 5, 2025
POP/IN-VIO
$0
Sep 27, 2024Construction CLASS - 2
REISSUE#35663466R DATE OF ISSUE:07.12.2023 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER AT THE TIME OF INSPECTION OBSERVED AND NOTED AT 5TH FLOOR STAIR B SMOKE BY ROOM 501,4TH FLOOR SMOKE BY STAIR B AT
#35684933J
Dec 6, 2024
POP/IN-VIO
$0
Sep 27, 2024Construction CLASS - 2
REISSUE#35663472N DATE OF ISSUE:07.12.2024 FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCES AT YARD 2ND FLOOR WINDOW SECTION OF BRICKS.CRACKED ABOVE 4TH & 5TH FLOOR WALL CRACKED.REM:REPAIR OR REPLACE WINDOW
#35684930Y
Dec 6, 2024
POP/IN-VIO
$0
Sep 27, 2024Construction CLASS - 2
REISSUE#35663467Z DATE OF ISSUE:07.12.2023 EXIT DOOR NOT SELF CLOSING PROPERLY AT THE TIME OF INSPECTION AT STAIR B 3RD FLOOR ONE EXIT DOOR STAIR B 5TH FL ONE EXIT DOOR & STAIR D 4TH FLOOR ONE EXIT DOOR,AT STAI
#35684932H
Dec 6, 2024
POP/IN-VIO
$0
Sep 27, 2024Construction CLASS - 2
REISSUE:35663469M DATE OF ISSUE:07.12.2023 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.AT THE TIME OF INSPECTION NOTED
#35684931X
Dec 6, 2024
POP/IN-VIO
$0
Jul 12, 2023Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. NOTED AT DOORS 2,4,6,7 DOORS ARE RUBBING AND FUNCTIONING PROPERLY REMEDY: REPAIR/REPLACE DOOR
#35663467Z
Nov 3, 2023
POP/IN-VIO
$0
Jul 12, 2023Construction CLASS - 2
REISSUE #35654779N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT WALL(S) OR APPURTENANCES. AT YARD 2 FLOOR WINDOW SECTION OF BRICKS. CRACKED, ABOVE 4 & 5 WALL CRACKED, EXPOSURE 1 (FRONT) CRACKS IN LIMESTONE AB
#35663472N
Nov 3, 2023
POP/IN-VIO
$0
Jul 12, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 5 FLOOR STAIR B SMOKE BY ROOM 501, 4 FLOOR SMOKE BY STAIR B AT ROOM 401, 402, 405, 3 FLOOR, 302A, 303, 2 FLOOR AUDITORIUM LEFT MAIN ENTRANCE DOORS
#35663466R
Nov 3, 2023
POP/IN-VIO
$0
Jul 12, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. AT 4 FLOOR EXIT SIGN STAIR B BY ROOM 402, 3 FLOOR EXIT SIGN BY 302, 2FL
#35663469M
Nov 3, 2023
POP/IN-VIO
$0
DOB (2)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06373
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#06374
DOB VIOLATION - ACTIVE
DOB NOW Safety (5)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 25, 2026, 6:07 PM ET. BBL 2030490037.