4 floors · 249,473 sq ft · built 1944 · class Q6 · owner of record: Nyc Department Of Homeless Services
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 50 days | Keep the report on file (not filed with DOB) |
| Annual boiler inspection (3 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2023-08-09 (Accepted). Agency page | Dec 31, 2026 in 50 days | 3 of 3 without an accepted 2026 report yet |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 249,473 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 171 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 171 days | Annual filing |
| Gas piping inspection (2027 cycle) Likely applies Local Law 152 · During 2027 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2027 in 415 days | Next cycle year 2027 |
| Energy audit and retro-commissioning (2028) Likely applies Local Law 87 · Calendar year 2028 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2138). Agency page | Dec 31, 2028 in 781 days | Next due 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 17, 2026 | Boilers CLASS - 3 SERVICING THIS BUILDING THE MOBILE BOILER> THE DOB PERMIT IS NOT DISPLAYED, MAINTAIN BOILER; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION #39185036Z | May 20, 2026 POP/IN-VIO | $0 |
| Dec 23, 2025 | Construction CLASS - 2 OBSERVED ON THE FIRST FLOOR A BOLT MISSING ON THE SPRINKLER SYSTEM, TRAP WRAP INSULATION IS MISSING ON TRAPS UNDER THE SINKS IN BATHROOMS. KITCHEN SINK WASTE LINE BACKING UP WHICH IS CONTRARY TO CODE SECTION PC #39171454Y | Dec 24, 2025 POP/IN-VIO | $0 |
| Dec 23, 2025 | Elevators CLASS - 1 CLASS 1 RTS CONT: WHEELCHAIR PLATFORM LIFT IS NOT READILY OPERABLE. REQUIRED OPERATING KEY WAS NOT AVAILABLE ON PREMISES UPON INSPECTION AND WAS IN POSSESSION OF ELEVATOR CONTRACTOR. DEVICE THEREFORE NOT AVAILA #39171444K | Feb 6, 2026 POP/IN-VIO | $0 |
| Dec 23, 2025 | Construction CLASS - 2 SPRINKLER HEADS ARE OBSTRUCTED THROUGHOUT THE BUILDING. ON THE SECOND FLOOR, SPRINKLER HEADS ARE DAMAGED, AND PVC WASTE LINES ARE INSTALLED BEHIND WASHING MACHINES. ON FIRST FLOOR STEAM LINE INSTALLED IN THE DE #39171453M | Dec 24, 2025 POP/IN-VIO | $0 |
| May 13, 2025 | Construction CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT THE TIME OF INSPECTION OBSERVED ITEMS STORED AT FIRE ESCAPE LANDING AT EXPOSURE 3.REMEDY: REMOVE EGRESS OBSTRUCTION. #35693758X | Jul 9, 2025 POP/IN-VIO | $0 |
| Apr 3, 2025 | Elevators CLASS - 2 CLASS 2 ITEMS: IN-CAR EMERGENCY LIGHT INOPERATIVE. PROVIDE AN UPDATED MAINTENANCE LOG. PROVIDE A MAINTENANCE PROGRAM. #39143803P | Apr 10, 2025 POP/IN-VIO | $0 |
| Apr 3, 2025 | Elevators CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11 #39143802N | Apr 10, 2025 POP/IN-VIO | $0 |
| Mar 31, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DENIED ACCESS TO ROOF LEVEL. COULD NOT CHECK PARAPET WALLS NOR THE ROOF DOOR. POTENTIAL FIRE HAZARD., PROVIDE LEGAL HARDWARE #39143295H | Apr 10, 2025 POP/IN-VIO | $0 |
| Mar 31, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED UNPERMITTED PLASTIC ACCESS PANELS AT 2ND FLOOR ADJACENT TO DEPT OF HOUSI #39143294X | Apr 10, 2025 POP/IN-VIO | $0 |
| Mar 31, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSE #39143296J | Apr 10, 2025 POP/IN-VIO | $0 |
| Apr 30, 2024 | Construction CLASS - 1 OBSERVED IN THE SPRINKLER ROOM LOCATED ON THE MAIN FLOOR, FIRE PUMP TRANSFER SWITCH AND ELECTRIC FIRE PUMP CONTROLLER ARE IN THE OFF POSITION. ABSOLUTELY NO WAY OF KNOW IN STREET PRESSURE IS ADEQUATE. AS PER 10 #39113026M | Jun 13, 2024 POP/IN-VIO | $0 |
| Apr 30, 2024 | Elevators CLASS - 1 DEVICE FOUND OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB . AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION. #39113057P | Jun 13, 2024 POP/IN-VIO | $0 |
| Apr 29, 2024 | Construction CLASS - 2 OBSERVED IN THE KITCHEN LOCATED ON THE FIRST FLOOR ACTIVE LEAK UNDER THE SINK ON THE WASTE PIPING. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PRO #39112971M | Jun 5, 2024 POP/IN-VIO | $0 |
| Mar 22, 2023 | Elevators CLASS - 1 97/X/17,RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB. #39082232Y | Mar 27, 2023 POP/IN-VIO | $0 |
| Dec 27, 2022 | Elevators CLASS - 1 LIFT IS CURRENTLY OUT SERVICE AND NEEDS TO BE REPAIRED #39076437R | Jan 10, 2023 POP/IN-VIO | $0 |
| Nov 19, 2021 | Boilers CLASS - 2 FOUND CORRODED WATER COLUMN, GLASS GAUGE GUARDS MISSING, BODY DRAINS MISSING AT SAFETY RELIEF VALVES. #39051482P | Dec 13, 2021 POP/IN-VIO | $0 |
| Nov 19, 2021 | Boilers CLASS - 2 FOUND TO HAVE CORRODED COIL PLATE AND CORRODED PIPING AT COIL, EXPOSED WIRING AT BURNER, GLASS GAUGE GUARDS MISSING. BODY DRAINS MISSING ON SAFETY RELIEF VALVES. #39051481N | Dec 13, 2021 POP/IN-VIO | $0 |
| Sep 23, 2021 | Construction CLASS - 2 NOTED: OBSERVED FIREPROOF SELF-CLOSING DOORS AT 2ND. FLOOR B-WING CORRIDOR "G" NOT SELF-CLOSING, 1ST. FLOOR ENTRANCE FPSC DOORS TO THE "A" AND "B" WINGS DO NOT SELF-CLOSE DUE TO MISSING DOOR DOOR CLOSING HARDWA #39047997M | Oct 15, 2021 POP/IN-VIO | $0 |
| Sep 30, 2019 | Construction CLASS - 2 NOTED: OBSERVED THROUGHOUT BOILER ROOM/GAS METER ROOM/SPRINKLER SHUT OFF VALVE ROOM. HORIZONTAL STEEL BEAMS ARE EXPOSED DUE TO FIREPROOFING COATINGS FALLING OFF, PIPE PENETRATING THROUGH CONCRETE SLAB CEILING A #39010370J | Oct 4, 2019 POP/IN-VIO | $0 |
| Sep 30, 2019 | Construction CLASS - 2 NOTED: OBSERVED FIREPROOF SELF CLOSING DOORS AT STAIR A2, 2ND FLOOR CORRIDOR AT B WING, 1ST FLOOR WEST WING, 1ST FLOOR B WING, B WING DOOR LEADING TO ARMORY AREA, 1ST FLOOR A WING, AND CAFETERIA DOOR ALL REMAIN #39010369M | Oct 4, 2019 POP/IN-VIO | $0 |
| Sep 16, 2019 | Construction CLASS - 2 LEAK ON CAST IRON FITTING IN THE BOILER ROOM, REPAIR AND/OR REPLACE #39009602L | Sep 20, 2019 POP/IN-VIO | $0 |
| Apr 1, 2019 | Construction CLASS - 2 FAILURE TO MAINTAIN BDLG IN CODE COMPLIANT MANNER.NOTED:OBSERVED AT FLFIRST FLOORS BOILER ROOM SPALLING CONCRETE,CRACKS AND MISSING FALLEN SECTIONS OF CONCRETE THROUGHOUT CEILING AT VARIOUS LOCAITONS.EXPOSED B #35383822H | May 30, 2019 POP/IN-VIO | $0 |
| Apr 1, 2019 | Construction CLASS - 2 EXIT DOOR NOT SELF CLOSING.NOTED:OBSERVED AT 2ND FLOOR STARR EXIT DOOR2A IS RUBBING ON FLOOR AND DOES NOT SELF CLOSE AT THE BWING OF THE 2NDFL.FIRST FLOOR FPSC DOORS AT BWING IS RACKED AND DETACHED FROM THE TOP #35383821X | May 30, 2019 POP/IN-VIO | $0 |
| Apr 1, 2019 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANCE MANNER. OBSERVED ON 4/01/19 @ ABOVE ADDRESS ACTIVE LEAK OF HOT WATER LINES IN BOILER ROOM LOCATED IN MAIN FLOOR. REMEDY: REPAIR &/OR REPLACE. #35415300Y | Jul 18, 2019 POP/IN-VIO | $0 |
| Feb 11, 2019 | Boilers CLASS - 2 B254,15,34B,50A,50B,50C,50D,50E,50F. B254. 50A-STORAGE IN BOILER ROOM50B-FRESH AIR FAN NOT WORKING; 50C-WRONG DIVERTER ON DUEL FUEL BOILER;50D-SMOKE ALARM NOT WORKING; 50E-F() DEVERTER ON FLUE TO BE REMOVED; #32098369R | Jun 13, 2019 POP/IN-VIO | $0 |
| Oct 17, 2018 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345. NOTED:OBSERVED WITHIN BOILER ROOM-PIPE PENETRATIONS AND HOLES IN WALLS AND CEILING W/ NO FIRE STOPPING PROVIDED AT VARI #35361468R | Dec 20, 2018 POP/IN-VIO | $0 |
| Oct 17, 2018 | Construction CLASS - 2 FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35326114X ISSUED ON 4/12/18, AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FOR OCCUPANCY CONTRARY OF #35361467P | Dec 20, 2018 POP/IN-VIO | $0 |
| Jul 17, 2018 | Boilers CLASS - 2 50A-H. AS PER CLASS 2(B254)28-301.1,FAILURE TO MAINTAIN.(50A)INSULATION FAILING OFF BOILER O2.(50B)EXPOSED ELECTRICAL WIRES NEAR FRESH AIR FAN.(50C)NO FUEL OIL SHUT-OFF VALVE & ANTISIPHONE ON SUPPLY LINE.(50D)F #32097273H | Oct 11, 2018 POP/IN-VIO | $0 |
| Apr 12, 2018 | Construction CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO OR BUILDING DEPARTMENT RECORDS.NOTED:AT 2ND STORY ROOMS DESIGNATED FOR OFFICE SPACE NOW BEINGUSED AS SLEEPING QUARTERS(DORM SETUP)REM:DISCONTINUE ILLEGAL OCCUPANCY #35326114X | Jun 7, 2018 POP/IN-VIO | $0 |
| Jan 4, 2018 | Construction CLASS - 2 FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35294392M ISSUED ON 11/27/17 & TO FILE A CERT OF CORRECTION PURSUANT TO 28-201.1 & 1RCNY 102-01.FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.R #35282978L | May 17, 2018 POP/IN-VIO | $0 |
| Dec 12, 2017 | Elevators CLASS - 1 CEASE USE. 5X10,48Y13. (5X)DOOR RESTRICTOR INOPERATIVE. THIS DEVICE IS TO ENSURE THE SAFETY OF ITS REGISTER, REGISTER. (48Y)CONNECTIONS OF PIPING FROM OIL TANK IS LEAKING OIL, SEAL. #38260275R | Feb 8, 2018 POP/IN-VIO | $0 |
| Nov 29, 2017 | Boilers CLASS - 2 15,32A,42,50A-D. (50)NEED TO CLEAN DEBRIS FROM FRESH AIR FAN & REPLACE SCREW. (50A)NEED TO INSTALL SAIL SWITCH ON FRESH AIR FAN. (50B)MISSING NUTS FOR REAR DOOR OF BOILER. (50C)WEED TO HAVE GLASS PUT ON REAR DO #32092075Y | Feb 8, 2018 POP/IN-VIO | $0 |
| Nov 27, 2017 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. 1ST FLOOR LEVEL BOILER ROOM, LEAKED AND RUSTED PIPE ON WEST SIDE, ON EASTSIDE MAIN WATER LINES AND PRESSURE PUMPS ARE DETERIORATED AND LEAKING NON-STOP. RE #35294392M | Jan 25, 2018 POP/IN-VIO | $0 |
| Nov 4, 2017 | Construction CLASS - 1 RE ISSUED #35286783J DATED 7/25/17 OCCUPANCY CONTRARY TO THAT ALLOWED ON DOB RECORDS AND 2ND FLOOR OFFICES BEEN USED AS A SLEEPING AREA. REMEDY: DISCONTINUE ILLEGAL OCCUPANCY OR AMEND C OF O #35289846L | Mar 1, 2018 POP/IN-VIO | $0 |
| Oct 16, 2017 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.1ST FL. LEVEL B OILER ROOM LEAKED AND RUSTED PIES ON WEST SIDE PIPE LEAKED CONTINALLY BEHIND WATER TANK ON EAST SIDE MAIN WATER LINES PRESSURE-PUMPS IS #35289831Z | Dec 14, 2017 POP/IN-VIO | $0 |
| Sep 5, 2017 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER;NO FIRE STOPPING PER BS 712.3;27-345,NOTED (GROUND FL) ELECTRICAL ROOM HOLES IN FL & WOOD FLS,ELECTRICAL ROOM BY (KITCHEN) HOLES IN WALLS BOILER ROOM HOLES IN W #35290666M | Dec 21, 2017 POP/IN-VIO | $0 |
| Jul 25, 2017 | Construction CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O OR DOB RECORDS.2ND FL OFFICES BEING USED AS SLEEPING AREAS.REM DISCONTINUE ILLEGAL OCCUPANCY #35286783J | Aug 17, 2017 POP/IN-VIO | $0 |
| Jul 25, 2017 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.CELLAR-BOILER ROOM LEAKING/RUSTED PIPES.REM REPAIR/REPLACE #35286782H | Aug 17, 2017 POP/IN-VIO | $0 |
| Apr 14, 2017 | Construction CLASS - 1 OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS.NOTED:AT 2ND FLOOR LEVEL OFFICE IS BEING OCCUPIED AS ROOM FOR LIVING PURPOSE,CONTRARY TO BUILDING RECORDS JOB #35235947R | Aug 17, 2017 POP/IN-VIO | $0 |
| Mar 30, 2017 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN THE BOILER ROOM A RETURN CONDENSATE LINE RUSTED & LEAKING IN SEVERAL PLACES & FLOODING THE BOILER ROOM. REMEDY: REPAIR &/OR REPLACE. #35236075N | May 4, 2017 POP/IN-VIO | $0 |
| Mar 30, 2017 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED: 1)IN A ROOM ON 1ST FL A HOSE LOCK(BOILER DRAIN)INSTALLED ON THE FD CHECK VALVUEINSTEAD OF THE REQUIRED BALL DRIPS & 2)ON TWO FLOORS NO PRESSURE GAUGE #35235499M | May 4, 2017 POP/IN-VIO | $0 |
| Mar 30, 2017 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. OBSERVED IN THE BOILER ROOM. 1)A FUTURE CONNECTION INSTALLED ON GAS PIPING CONTRARY TO CETION 408.2 OF THE FUEL GAS CODE & 2)NO SHUT OFF VALVE INSTALLED W/I #35236076P | May 4, 2017 POP/IN-VIO | $0 |
| Jul 21, 2016 | Construction CLASS - 2 OCCUPANCY CONTRARY TO DOB RECORDS. NOTED: ROOM 102- DINING ROOM- AS A PLACE OF ASSEMBLY W/ MAXIMUM OCCUPANCY SIGN POSTED FOR 78 PERSONS. ROOM ARRANGED W/ SEATING FOR 106 PERSONS. ROOM HAS ONE EXIT DOOR W/ ILLUM #35200986J | Sep 15, 2016 POP/IN-VIO | $0 |
| Jul 21, 2016 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NOTED: @ WEST 168 ST THE 9TH WINDOW RIGHT OF 651 ENTRY, CRACKED, BULGING, LOOSE BRICK MASONRY OF WINDOW GUARD ANCHOR POINT. ALSO LOOSE HAND CAP RAMP HAND RAILING OFFERIN #35200987L | Sep 15, 2016 POP/IN-VIO | $0 |
| Mar 11, 2016 | Construction CLASS - 2 EXIT DOOR NOT SELF-CLOSING.THE FOLLOWING DOORS NOT SELF-CLOSING:2ND FLR STAIRWAY EXIT DOOR "B",1ST FLR "A" WING EXIT DOORS(ROOM 126-130),1STFLR "A" WING EXIT DOORS (ROOM 108-111),BOILER ROOM DOOR#124 & 1ST FLR #35177258Z | Jul 14, 2016 POP/IN-VIO | $0 |
| Aug 12, 2014 | Elevators CLASS - 2 /42L09/05L10/ 42L09-JUMPERS ON CONTROLLER TOP. 05L10-ZONE RESTRICTOR. #38231946X | Oct 30, 2014 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| May 13, 2025 | CONSTRUCTION OBSERVED AT EXOSURE 1 MULTIPLE DEFECT ALONG PARAPET AREA CRACK & SPALLED STONES, CRACK AT 1ST FLOOR. EXP 2 CRACK, DAMAGED JOINTS AND CRACK PANE. EXP3 CRACK 1FL CORNER OF EXPOSURE 4. EXPOSURE 4 BROKEN WINDOW PANE, AND CRACK AT CORNER AT EXPOSURE 1. OBSERVED CORROSION OF GATES. REMEDY: MAINTAIN BUILDI #SR1203NS | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Oct 2, 2026 | Elevators FTF-VT-CAT1-NJ Violation Issued-Failure To File 2025 Cat1 Test Report | Active |
| Oct 10, 2025 | Elevators FTC-VT-CAT1-NJ Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
| Jan 31, 2025 | Gas Piping - LL152 FTF-PL-PER Cycle 1, Sub-cycle D (premises is in Community District 12) | Active |
| Oct 11, 2024 | Elevators FTC-VT-CAT1-NJ Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 2, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Cat1 Test Report | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 11, 2026, 5:20 PM ET. BBL 1021380079.