Bronx · Block 3037 · Lot 79 · 10457

2147 Washington Avenue

4 floors · 80,000 sq ft · built 1992 · class W1 · owner of record: Nyc Department Of Education

24open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
65dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 65 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 65 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 80,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 186 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 186 days
Annual filing
Energy audit and retro-commissioning (2027) Likely applies
Local Law 87 · Calendar year 2027
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 3037). Agency page

Dec 31, 2027
in 430 days
Next due 2027
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-22 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (12)
IssuedViolationHearingBalance
May 20, 2026Construction CLASS - 2
REISSUE: 35693232L DATE OF ISSUE: 08/26/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FPSC DOOR, CORRIDORS EXIT DOORS ARE NOTCLOSING PROPERLY DUE TO DEFECTIVE HARDWARE AT 4TH FL. ST. WAY 'C' 3RD
#35733016K
Jun 26, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE: 35693237K DATE OF ISSUE: 08/26/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED AT CELLAR LEVEL BOILER ROOM THE MASONRY SMOKE STACK HAD AN APPRO
#35733011L
Jun 12, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE: 35693235 DATE OF ISSUE: 08/26/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED MASONRY FENCE AT EXP-4 HAVE SPALLED/LOOSE BRICK PILLAR BY EXP #4
#35733013P
Jun 12, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE: 35693234P DATE OF ISSUE: 08/26/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED SPALLING AND CRUMBLING INTERIOR PLASTER DUE TO WATER LEAKS AT MA
#35733014R
Jun 12, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE:35593236Z DATE OF ISSUE: 08/26/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED EXP #3 4 STEPS DOWN TO ASPHALT PLAY YARD WERE MISSING HANDRAILS W
#35733012N
Jun 12, 2026
POP/IN-VIO
$0
May 20, 2026Construction CLASS - 2
REISSUE: 35693233N DATE OF ISSUE: 08/26/2025. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OBSERVED AND NOTED BROKEN WINDOW GLASS PANEL AT EXP #1 AT 3RD FLOOR LEVEL ABOVE MAI
#35733015Z
Jun 26, 2026
POP/IN-VIO
$0
Aug 26, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. INTERIOR FPSC SMOKE DOORS HAVE DEFECTIVE MAGNETIC DOOR CATCHES AT: 4TH FL STAIR C, 3RD FL STAIR D, 2ND FL STAIR D AND C, 1ST FL STAIR D AND CAFETERIA ENTRA
#35693232L
Sep 12, 2025
POP/IN-VIO
$0
Aug 26, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED MASONRY FENCE AT EXP#2 HAVE SPALLED/LOOSE BRICK FORCES ALONG THE BRICK PILLARS.ALSO BRICK FENCE PILLAR BY EXIT#4 WAS OUT OF PLUMB,LEANING APPROX.5 WIT
#35693235R
Sep 5, 2025
POP/IN-VIO
$0
Aug 26, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT CELLAR LEVEL BOILER ROOM,THE MASONRY SMOKE STACK HAD AN APPROX.15 FT VERTICALCRACK,WITH SEPARATION OF BRICKS PRESENT.REM:REPAIR AND/OR REPLACE.
#35693237K
Sep 5, 2025
POP/IN-VIO
$0
Aug 26, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED SPALLING AND CRUMBLING INTERIOR PLASTER DUE TO WATER LEAKS AT MAIN ENTRANCE VESTIBULE AROUND WINDOWS AND AT GYMNASIUM CEILING. REMEDY: REPAIR AND/OR
#35693234P
Sep 12, 2025
POP/IN-VIO
$0
Aug 26, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED BROKEN WINDOW GLASS PANEL AT EXP #1, 3RD FL LEVEL ABOVE MAIN ENTRANCE. REMEDY: REPAIR AND/OR REPLACE.
#35693233N
Sep 12, 2025
POP/IN-VIO
$0
Aug 26, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:EXP#3(4)STEPS DOWN TO ASPHALT PLAY YARD WERE MISSING HANDRAILS WITH DISTANCE SPAN GREATER THAN 66".ALSO EXISTING HANDRAILS WERE LOOSE ALONG BOTTOM ANC
#35693236Z
Sep 5, 2025
POP/IN-VIO
$0
DOB (2)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#07585
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#07584
DOB VIOLATION - ACTIVE
DOB NOW Safety (10)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 27, 2026, 2:12 PM ET. BBL 2030370079.