Brooklyn · Block 3289 · Lot 27 · 11237

212 Irving Avenue

4 floors · 30,400 sq ft · built 1893 · class W1 · owner of record: Nyc Department Of Education

23open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
62dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 62 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 62 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 30,400 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 183 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 183 days
Annual filing
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-08-03 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (20)
IssuedViolationHearingBalance
Apr 28, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, ALL STAIRS ON THE 1ST FLOOR HAD STORAGE UNDER STAIRS. THE REAR ROOM IN CELLAR HAD LEAKS IN THE CEILING. STEP CRACKS WERE OBSERVE
#35732957H
May 27, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
RE-ISSUE 35717406X. AT THE TIME OF INSPECTION, THERE WAS NO C OF O ON FILE FOR P. S. 86. REMEDY: OBTAIN VALID C OF O OR DISCONTINUE ILLEGAL OCCUPANCY.
#35732956X
May 27, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). AT THE TIME OF INSPECTION, THE FOLLOWING DOORS HAD TURN KNOB HANDLES:-101, 205, 207, 304
#35732954M
May 27, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
RE-ISSUE 35720835L. AT THE TIME OF INSPECTION, THE FOLLOWING EMERGENCYLIGHTS WERE NOT OPERABLE:-BOX #3, #5, #2, #4, #9, 3 LIGHTS IN CAFETERIA. REMEDY: REPAIR AND/OR REPLACE.
#35732955Y
May 27, 2026
POP/IN-VIO
$0
Jul 14, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. REISSUE 335717405Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SEVERAL EMERGENCY LIGHTS THROUGHOUT THE BUILDING NOT WORKING WHEN TESTED. REMEDY
#35720835L
Aug 14, 2025
POP/IN-VIO
$0
Jul 14, 2025Construction CLASS - 2
REISSUE #35677517P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. WATER PENETRATING THROUGH WALL AT BOILER ROOM PAINT POUR AND OTHER VARIOUS AREAS. REMEDY: REPAIRS AND/OR REPLACE.
#35720837P
Aug 14, 2025
POP/IN-VIO
$0
Jul 14, 2025Construction CLASS - 2
REISSUE #35677516N. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. OBSERVED AT ROOF TOP BRICK TO CHIMNIES BUT MISSING BRICK ON ALL SIDE ALSO STOP CRACKS. REMEDY: REPAIR AND/OR REPLACE.
#35720836N
Aug 14, 2025
POP/IN-VIO
$0
Apr 30, 2025Construction CLASS - 2
ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2. 3 STORY BUILDING OCCUPIED AS PS 86 PUBLIC SCHOOL AND NO JOB RECORD SIGNED OFF OR RECORDS OF C OF O ON REC
#35717406X
Jun 5, 2025
POP/IN-VIO
$0
Apr 30, 2025Construction CLASS - 2
REISSUE #35677518R: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER; ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1-27-381. ILLUMINATION EXITS NOT OPERATIONAL WHEN TESTED @ 1ST
#35717405Y
Jun 5, 2025
POP/IN-VIO
$0
May 2, 2024Construction CLASS - 2
REISSUE #35672518Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF MY INSPECTION I OBSERVED WATER PENETRATION THROUGH THE WALL AT THE BOILER ROOM AND THE PAINT ROOM IN VARIOUS AREAS OF THE C
#35677517P
Jun 18, 2024
POP/IN-VIO
$0
May 2, 2024Construction CLASS - 2
REISSUE #35672517M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1: 27-381. AT TIME OF MY INSPECTION I OBSERVED EMERGENCY LIGHT
#35677518R
Jun 18, 2024
POP/IN-VIO
$0
May 2, 2024Construction CLASS - 2
REISSUE #. FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES. AT TIME OF INSPECTION I OBSERVED AT THE ROOF TOP BRICK TO CHIMNIES BOTH MISSING BRICK ON ALL SIDE, ALSO AT EXIT 3" STEP CRACK APPROXIMATELY Y2X1
#35677516N
Jun 18, 2024
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
REISSUE#35655077N FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER 1006.1;27-381.NOTED DEFECTIVE EMERGENCY EXIT LIGHTING AT 1ST FLOOR MAIN EN
#35672517M
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED WATER PENETRATION THROUGH THE WALL AT BOILER ROOM,PAINT ROOM,AND VARIOUS OTHER AREAS OF CELLAR.ALSO AT ROOFTOP BULKHEAD STAIR C.REMEDY:MAKE NECESSARY
#35672518Y
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED AT ROOFTOP BRICK CHIMNIES BOTH MISSING BRICKS ON ALL SIDES.ALSO AT EXIT 3 STEP CRACK APPROX 1/2"X10'L IN THE EXTERIOR WALL.REMEDY:MAKE NECESSARY REPAIRS
#35672519X
Jun 21, 2023
POP/IN-VIO
$0
Apr 18, 2022Construction CLASS - 2
REISSUE#35557936N.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC1006.1;27-381 AT 1ST FLOOR FRONT MAIN ENTRANCE AND BASEMENT STAIR EMERGE
#35655077N
Sep 21, 2022
POP/IN-VIO
$0
Apr 13, 2021Construction CLASS - 2
REISSUE#35486741H FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER ILLUMINATION FOR EXIT DISCHARGES & PUBLIC COORIDORS PER BC 1006-1-27-381EXIT LIGHT AT 1ST FL NEAR MAIN ENTRANCE & AT BASEMENT STAIR ENTRANCE
#35557936N
Sep 8, 2021
POP/IN-VIO
$0
Mar 26, 2020Construction CLASS - 2
REISSUE #35383860Z FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOR EXIST EXIT DISCHARGES AND PUBLIC CORRIDOR PER BC 1006.1&27-381 EXIT LIGHT THROUGHOUT NOT WORKING REPAIR AND OR REPLACE
#35486741H
Oct 14, 2020
POP/IN-VIO
$0
Apr 1, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDOR PER BC 1006.1;27-381. NOTED AT MULTI PURPOSE ROOM LEFT SIDE AND OUTSIDE CAFETERIA IN STAIRWAY C&D
#35383860Z
Jul 29, 2019
POP/IN-VIO
$0
Mar 7, 2018Construction CLASS - 2
OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT C OF O. NOTED: AT CAFETERIA AREA,NO PLACE OF ASSEMBLY C W/O SIGN. REMEDY: COMPLY W/CODE/OBTAIN A PLACE OF ASSEMBLY C OF O.
#35322041X
Jun 11, 2018
POP/IN-VIO
$0
DOB (1)
IssuedViolationStatus
Mar 9, 2026CONSTRUCTION
BOROUGH COMMISSIONER HAS ORDERED ALL WORK STOPPED UNDERPERMIT# B01138719-I1 ON 3/6/26. CONSTRUCTION SUPERINTENDENT WITHDRAWAL. UNABLE TO DETERMINE PERCENTAGE OF WORK DUE TO NO ACCESS. STOP ALL WORK FOR JOB # REFERENCED AND MAKE THE SITE SAFE.
#26-00708
DOB VIOLATION - ACTIVE
DOB NOW Safety (2)
IssuedViolationStatus
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 30, 2026, 1:47 AM ET. BBL 3032890027.