Manhattan · Block 1873 · Lot 24 · 10025

211 West 101 Street

7 floors · 29,640 sq ft · built 1925 · class N2 · owner of record: Frant Hotel Llc

15open violations
$33,205ECB/OATH penalties owed
0HPD class C (immediately hazardous)
50dto Annual boiler inspection (1 boiler)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 50 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-06-16 (Accepted). Agency page

Dec 31, 2026
in 50 days
1 of 1 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 29,640 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 171 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 171 days
Annual filing
Facade inspection report (Cycle 10C) Applies
Local Law 11 / FISP · Feb 21, 2027 to Feb 21, 2029
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 1, 2 or 3 are in sub-cycle 10C. DOB facade records for this building show $234,900 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2029
in 833 days
Filing window not open yet
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 7 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1146 days
Next cycle year 2029

Open violations

ECB / OATH (21) · $33,205 owed
IssuedViolationHearingBalance
Jun 12, 2026Construction CLASS - 1
ATOI OBSERVED IN BASEMENT UNPERMITTED LAUNDRY ROOM AND FRESH AIR VENT FOR HOUSE TRAP NOT CONNECTED. PER PC 1002.6 - HOUSE TRAPS, WHERE INSTALLED, SHALL BE PROVIDED WITH A FRESH AIR INLET ON THE BUILDING SIDE OF
#39192365P
May 3, 2027
PENDING
$2,500
Jun 11, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED OBSTRUCTION ON FIRE ESCAPES. LOCATED ON FLOORS 5 AND 3. POTENTIAL FIRE HAZARD., REPAIR AND/OR REPLACE
#39192176X
Oct 1, 2026
IN VIOLATION
$1,250
Jun 11, 2026Boilers CLASS - 2
FOUND FEDERAL FST-80 DUAL FUEL BOILER WITH EXPOSED WIRING, DEFECTIVE STEAM GAUGE, MANUFACTURES LABEL MISSING ON SAFETY RELIEF VALVE, CAP MISSING ON GAS REGULATOR ON PILOT ASSEMBLY.
#39192211M
Oct 1, 2026
IN VIOLATION
$1,250
Jun 11, 2026Elevators CLASS - 2
CLASS 2: 1) FIRE EXTINGUISHER SERVICE TAG EXPIRED AS PER NYC FIRE CODE REQUIREMENTS. REMEDY: UPDATE SERVICE TAG. 2) MAINTENANCE LOG NOT UPDATED; REQUIRED RECORDS NOT MAINTAINED AS PER ASME A17.1/CSA B44 8.6.1.4
#39192260Z
Oct 1, 2026
IN VIOLATION
$625
Jun 11, 2026Unknown CLASS - 2
PROHIBITED USE OF ELECTRICAL METALLIC TUBING (EMT). OBSERVED IN REAR OF BUILDING UNDER WALKWAY THAT THE INSTALLATION OF EMT PIPES USED TO POWER LIGHT FIXTURE AND EXIT SIGN. EMT PIPE IS PROHIBITED FOR OUTDOOR US
#39192182M
Oct 1, 2026
IN VIOLATION
$500
Jun 11, 2026Unknown CLASS - 2
FAILURE TO PROVIDE/MAINTAIN SUFFICIENT ACCESS/WORK SPACE ABOUT ELECTRICAL EQUIPMENT. OBSERVED IN THE BASEMENT IN THAT THE MAIN ELECTRICAL EQUIPMENT AND PANELS ARE BLOCKED AND HAS NO ACCESS FOR WORK/ REPAIR AND
#39192181K
Oct 1, 2026
IN VIOLATION
$500
Jun 11, 2026Unknown CLASS - 2
FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE BASEMENT THAT THE MAIN HOUSE ELECTRICAL WATER GROUND CLAMP IS RUSTED AND IS IN A STATE OF DETERIORATION. FAILURE TO GROUND IS POTENTI
#39192180Z
Oct 1, 2026
IN VIOLATION
$2,400
Jun 23, 2025Elevators CLASS - 1
CEASE USE ITEM: DOOR LOCK MONITOR INOPERATIVE. REPAIR. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. ELEVATOR DIVISION AT FOR A REI
#39151687R
Mar 19, 2026
IN VIOLATION
$1,250
Jun 18, 2025Construction CLASS - 1
FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. EXCESSIVE GARBAGE OBSTRUCTING EMERGENCY EXIT PASSAGE WAY. LEADING FROM BASEMENT TO STREET LEVEL AT EXPOSURE 1. POTENTIAL FIRE HAZARD., REMOVE OBSTRUCTION
#39151445Y
Mar 26, 2026
IN VIOLATION
$625
Jun 18, 2025Construction CLASS - 1
WORK WITHOUT A PERMIT. OBSERVED SADDLE VALVE CONNECTION ON SPRINKLER MAIN BEFORE MAIN CHECK VALVE ASSEMBLY CONNECTING FIRE SUPPRESSION WATER TO BOILER. NOT CODE COMPLAINT AS PER RCNY 29-06. THIS WAS DEDICATED F
#39151444M
Nov 6, 2025
IN VIOLATION
$1,250
Jun 18, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATION THROUGHOUT BASEMENT. POTENTIAL HAZARD., PROVIDE/MAINTAI
#39151443K
Mar 26, 2026
IN VIOLATION
$625
Jun 18, 2025Construction CLASS - 1
UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE AT GAS METER AND IN BOILER ROOM, (GARBAGE BUCKET UNDERNEATH GAS METERS.) TOOLBOX AND MINI FRIDGE IN STORED IN BOILER ROOM. POTENTIAL
#39151442Z
Mar 26, 2026
IN VIOLATION
$2,500
Feb 27, 2024Elevators CLASS - 2
SUSPENDED SCAFFOLD INSTALLED AND WITHOUT DEPARTMENT NOTIFICATION OF USE AND OR REMOVEL, GROUNDED LOCATED AT REAR-YARD, EXPOSURE #3, OBTAIN CERTIFICATE OF COMPLIANCE
#39107065Y
Oct 28, 2025
IN VIOLATION
$625
May 20, 2022Unknown CLASS - 1
I OBSERVED ON ALL FLOORS THE CONVENIENCE OUTLETS NOT TAMPER PROOF OR THE TAMPER RESISTANT TYPE. THIS IS AN IMMEDIATE SHOCK HAZARD FOR CHILDREN. ALSO NOTED ON THE ROOFTOP LEVEL DEFECTIVE EQUIPMENT-2 NON-WORKING
#39062557Y
Nov 9, 2023
IN VIOLATION
$1,600
May 20, 2022Construction CLASS - 2
BUILDING ALTERED UNDER AH-1 APPLICATION#102334877 AND OCCUPIED WITHOUT VALID CERTIFICATE OF OCCUPANCY. C OF O EXPIRED, OBTAIN A VALID C OF O OR DISCONTINUE ILLEGAL OCCUPANCY
#39062556M
Oct 6, 2022
IN VIOLATION
$1,250
May 20, 2022Unknown CLASS - 2
I OBSERVED IN THE ELEVATOR MOTOR DISCONNECT THE IMPROPER FUSING OF THE LOAD SIDE CONDUCTORS. THE OVERCURRENT FUSES ARE RATED AT 100 AMPS WHILE THE LOAD SIDE CONDUCTORS #6 ARE NOT RATED FOR THAT AMPACITY. PHOTOS
#39062559H
Nov 9, 2023
IN VIOLATION
$1,200
Jul 29, 2021Construction CLASS - 2
ALTERED/CHANGED BUILDING OCCUPIED WITHOUT VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1;28-118.3.2.NOTED:BUILDING ALTERED UNDER AH-1 APPLICATION#102334877 AND OCCUPIED UNDER EXPIRED TERMPORARY CERTIFICATE OF
#35582478J
Mar 3, 2022
IN VIOLATION
$3,125
Oct 27, 2020Construction CLASS - 2
FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35297915X ISSUED ON 01/22/18 & TO FILE A CERT OF CORRECTION PURSUANT TO 28-201.1 & 1RCNY 102-01. ALTER CHANGED BLDG OCCUPIED W/O A VALID CERT OF OCC
#35521453Y
May 27, 2021
IN VIOLATION
$1,250
Nov 26, 2019Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONER ORDER CONTAINED IN SUMMONS/VIOLAT ON#35297915X ISSUED ON 01-22-2018 AND TO FILE A CERTIFICATE OF CORREC ION PURSUANT TO 28-201.1 AND 1RCNY 102-01.COMPLY WITH COMMISSIONERS OR
#35513266Z
Feb 6, 2020
DEFAULT
$3,125
Sep 13, 2019Construction CLASS - 2
NOTED: BUILDING ALTERED UNDER APPLICATION #102334877 AND OCCUPIED UNDER A TEMPORARY CERTIFICATE OF OCCUPANCY THAT EXPIRED ON JUNE 17, 2003. , OBTAIN A VALID C OF O OR DISCONTINUE ILLEGAL OCCUPANCY
#39009785N
Feb 20, 2020
IN VIOLATION
$4,505
Aug 8, 2018Construction CLASS - 2
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35297915X ISSUED ON 01/22/18 & TO FILE A CERTIFICATE OF OCCUPANCY PURSUANT TO 28-201.1 & 1RCNY 102-01.ALTERD CHANGED BLDG OCCUPIED
#35426955Z
Dec 26, 2019
IN VIOLATION
$1,250
DOB (1)
IssuedViolationStatus
Feb 22, 2024NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
#00377
DOB VIOLATION - ACTIVE
DOB NOW Safety (3)
IssuedViolationStatus
Nov 6, 2026GHG Emissions - LL97 FTF-EN-LL97320
FAILURE TO FILE AN ANNUAL BUILDINGS EMISSIONS REPORT AS REQUIRED BY AD CODE SEC. 28-320.3.7 IN ACCORDANCE WITH 1 RCNY § 103-14.
Active
Dec 8, 2025GHG Emissions - LL97 FTF-EN-LL97320
Active
Feb 22, 2024Facades FISPNRF
FAILED TO FILE FISP CYCLE 9C TECHNICAL REPORT BY 2/21/2024
Active
HPD (4) · C 0 · B 4 · A 0
IssuedClassViolationCorrect by
Apr 20, 2026BApt 704 · § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE 1st ROOM FROM NORTH LOCATED AT B-ROOM 704, 7th STORY, 1st B-ROOM FROM WEST AT NORTHMay 25, 2026
Apr 20, 2026BApt 604 · § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE 1st ROOM FROM NORTH LOCATED AT B-ROOM 604, 6th STORY, 1st B-ROOM FROM WEST AT NORTHMay 25, 2026
Apr 20, 2026BApt 604 · § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE 1st ROOM FROM NORTH LOCATED AT B-ROOM 604, 6th STORY, 1st B-ROOM FROM WEST AT NORTHMay 25, 2026
Apr 20, 2026BApt 704 · § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE 1st ROOM FROM NORTH LOCATED AT B-ROOM 704, 7th STORY, 1st B-ROOM FROM WEST AT NORTHMay 25, 2026

Issued in the last 120 days

DateSourceWhatNow
Nov 6, 2026DOB SafetyGHG Emissions - LL97: FAILURE TO FILE AN ANNUAL BUILDINGS EMISSIONS REPORT AS REQUIRED BY AD CODE SEC. 28-320.3.7 IN ACCORDANCE WITH 1 RCNY § 103-14.Open

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 11, 2026, 8:23 AM ET. BBL 1018730024.