Brooklyn · Block 2039 · Lot 101 · 11205

21 Auburn Place

8 floors · 112,585 sq ft · built 1952 · class I1 · owner of record: Nyc Health And Hospitals Corporation

59open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
66dto Annual boiler inspection (6 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 66 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (6 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-05-07 (Accepted). Agency page

Dec 31, 2026
in 66 days
3 of 6 without an accepted 2026 report yet
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $996,000 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2027
in 118 days
No Cycle 10 report on record yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 112,585 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 187 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 187 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1162 days
Next cycle year 2029
Energy audit and retro-commissioning (2029) Likely applies
Local Law 87 · Calendar year 2029
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2039). Agency page

Dec 31, 2029
in 1162 days
Next due 2029

Open violations

ECB / OATH (17)
IssuedViolationHearingBalance
Aug 7, 2026Elevators CLASS - 1
CLASS 1 CEASE USE: DOOR LOCK MONITORING SYSTEM INOPERATIVE. ELEVATOR OPERATES WITHOUT PROPER VERIFICATION OF DOOR LOCKS STATUS. AS PER ASME A17.1 SECTION 2.26.9.3. REPAIR OR REPLACE DOOR LOCK MONITORING SYSTEM
#39199781X
Sep 3, 2026
POP/IN-VIO
$0
Jan 28, 2026Elevators CLASS - 1
CLASS 1 CEASE USE ORDER: IN-CAR EMERGENCY STOP SWITCH INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. FOR A REINSPECTION
#39175172Y
Feb 6, 2026
POP/IN-VIO
$0
Oct 1, 2024Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED EXCESSIVE CRACKS ON ROOF IN MECHANICAL ROOM AND BASEMENT ROOM LEVELS., REPAIR AND/REPLACE
#39126356H
Jan 2, 2025
POP/IN-VIO
$0
Oct 1, 2024Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS LOCATED IN UTILITY, MECHANICAL , ROOF LEVEL AND BASEME
#39126355X
Oct 18, 2024
POP/IN-VIO
$0
Oct 1, 2024Construction CLASS - 2
OBSERVED SPRINKLER MAIN NOT PAINTED RED IN THE BOILER ROOM. AS PER 903.6.2 OF THE BUILDING CODE ALTERATIONS. CROSS CONNECTIONS AND RISERS FOR INDEPENDENT (STAND-ALONE) EXISTING SPRINKLER SYSTEMS THAT ARE EXPOSE
#39126371X
Oct 18, 2024
POP/IN-VIO
$0
Dec 29, 2022Elevators CLASS - 1
DEVICE WAS FOUND OUT OF SERVICE RESTORE TO SERVICE IMMEDIATELY. YOU CAN CONTACT NYCDOB AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.
#39076601J
Jan 10, 2023
POP/IN-VIO
$0
Dec 2, 2022Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE8A,9A REPORT OF CRITICAL EXAM DOCUMENTING CONDITION OF EXTERIOR WALL&APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL909505.SUBMIT ACCEPTABLE REQUIRED TECHNICAL REPORT
#37023903N
Feb 8, 2023
POP/IN-VIO
$0
Dec 1, 2022Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFOR
#39076602L
Jan 10, 2023
POP/IN-VIO
$0
Dec 8, 2021Construction CLASS - 3
FAILURE TO POST EXTERIOR BUILDING WALL CONDITION CERTIFICATE AS REQUIRED UNDER 1RCNY103-04(F)AS NOTED:AT TIME OF INSPECTION BUILDING WALL CONDITION CERTIFICATE WAS NOT POSTED IN CONSPICUOUS PLACE ON SITE.REMEDY
#35635149P
May 4, 2022
POP/IN-VIO
$0
Nov 17, 2021Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFOR
#39051307H
Dec 14, 2021
POP/IN-VIO
$0
Nov 17, 2021Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION INSTALL DLM AND PERFOR
#39051309L
Dec 14, 2021
POP/IN-VIO
$0
Mar 4, 2019Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NOTED:OBSERVED AT SOUTHWEST CORNER OF CELLAR WATER PENETRATING THROUGH CONCRETE SLAB ABOVE, ADJACENT TO SIDEWALK HATCH AND FALLING ONTO STEEL BEAM WHICH IS
#35383805X
Jul 1, 2019
POP/IN-VIO
$0
May 18, 2018Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE 8TH ROUND REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #809505.REM:SUBMIT REQUIRED TECHNICAL REPORT.
#37010188K
Sep 10, 2018
POP/IN-VIO
$0
Feb 15, 2018Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: INTERIOR. NOTED: OBSERVED @ CELLAR SOUTH WEST CORNER & SOUTH OF STORAGE & HEATING TANKS, WATER PENETRATING INTO BLDG THROUGH THE CONCRETE SLAB ONTO STEEL BEAMS
#35298046H
Apr 23, 2018
POP/IN-VIO
$0
Mar 9, 2017Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3/9.17 JIM CAPS BEING USED THROUGHOUT BSMT MUST BE HAND CAPPED. PHOTOS TAKEN.REMEDY: REPAIR AND/OR REPLACE.
#35235128N
May 8, 2017
POP/IN-VIO
$0
Mar 9, 2017Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 3/09/17IN THE CAFETERIA ROOM ON THE FIRST FL SPRINKLER HEADS TO CLOSE TO THE SOFFIT. PHOTOS TAKEN. REMEDY: REPAIR AND/OR REPLACE.
#35235127L
May 8, 2017
POP/IN-VIO
$0
Jan 27, 2010Construction CLASS - 2
FAILURE TO FILE AN ARCHITECT/ENGINEER REPORT CERTIFYING EXIT/DIRECTIONAL SIGNS ARE CONNECTED TO EMERGENCY POWER SOURCE/STORAGE BATTERY EQUIPMENT. REMEDY: FILE ARCHITECT/ENGINEER REPORT.
#36012454R
Aug 2, 2010
WRITTEN OFF
$0
DOB (16)
IssuedViolationStatus
May 1, 2024RETAINING WALL
FAILED TO FILE CYCLE 1 TECHNICAL REPORT BY 12/31/2018 PER RCNY 103-09
#00044
DOB VIOLATION - ACTIVE
Feb 22, 2022NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
#01092
DOB VIOLATION - ACTIVE
Feb 5, 2022CONSTRUCTION
EMERGENCY WORK ORDER-DUE TO UNSTABLE WHITE TERRA COTTA FACADE MATERIAL ON THE 6FL, EXP 2, WEST FACING ELEVATION AT THE FRONT ENTRANCE COURTYARD. REMEDY: IMMED PROVIDE SAFETY MEASURES FOR THE FACADE AND REMOVE ANY AND ALL LOOSE MATERIAL FROM THE FACADE
#LLFA01RF
DOB VIOLATION - ACTIVE
Feb 5, 2022CONSTRUCTION
VACATE ORDER-OBSERVED DEFECTIVE FACADE CONDITION ON THE 6FL, EXP 2 WEST FACING ELEVATION AT THE FRONT ENTRANCE COURTYARD. REMEDY: VACATE HOTEL COURTYARD AND MAINTAIN CONTROLLED ACCESS TO SAME
#LLFA01JM
DOB VIOLATION - ACTIVE
Aug 14, 2021ELEVATOR

#9027/703362
DOB VIOLATION - ACTIVE
Aug 14, 2021ELEVATOR

#9027/703364
DOB VIOLATION - ACTIVE
Jul 28, 2020ELEVATOR

#9027/685500
DOB VIOLATION - ACTIVE
Jul 28, 2020ELEVATOR

#9027/685509
DOB VIOLATION - ACTIVE
Jul 30, 2019ELEVATOR

#9027/657557
DOB VIOLATION - ACTIVE
Apr 5, 2019ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
#05459
DOB VIOLATION - ACTIVE
May 31, 2018NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 8A TECHNICAL REPORT BY 02/21/2017
#00024
DOB VIOLATION - ACTIVE
May 12, 2005ELEVATOR

#9444128625
DOB VIOLATION - ACTIVE
May 12, 2005ELEVATOR

#9444128624
DOB VIOLATION - ACTIVE
May 12, 2005ELEVATOR

#9444128584
DOB VIOLATION - ACTIVE
Jan 13, 1997LOCAL LAW 10/81 - ELEVATOR

#02810
DOB VIOLATION - ACTIVE
May 31, 1994LOCAL LAW 10/81 - ELEVATOR

#02210
DOB VIOLATION - ACTIVE
DOB NOW Safety (26)
IssuedViolationStatus
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Report
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 2)
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
May 1, 2024Retaining Walls FTF-RW-INITL
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Report
Active
Feb 22, 2022Facades FISPNRF
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
Active
May 20, 2019Elevators EVCAT5
Active
Apr 5, 2019Elevators EVCAT1
Active
May 31, 2018Facades FISPNRF
FAILED TO FILE FISP CYCLE 8A TECHNICAL REPORT BY 02/21/2017
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test ReportOpen
Aug 7, 2026ECBElevators: CLASS 1 CEASE USE: DOOR LOCK MONITORING SYSTEM INOPERATIVE. ELEVATOR OPERATES WITHOUT PROPER VERIFICATION OF DOOR LOCKS STATUS. AS PER ASME A17.1 SECTION 2.26.9.3. REPAIR OR REPLACE DOOR LOCK MONITORING SYSTEMOpen

Check the agency records