Queens · Block 68 · Lot 2 · 11101

21-10 Borden Avenue

1 floors · 55,000 sq ft · built 1963 · class N2 · owner of record: Nyc Department Of Homeless Services

10open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
47dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-09 (Accepted). Agency page

Dec 31, 2026
in 47 days
1 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 55,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Energy audit and retro-commissioning (2028) Likely applies
Local Law 87 · Calendar year 2028
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 68). Agency page

Dec 31, 2028
in 778 days
Next due 2028
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1143 days
Next cycle year 2029

Open violations

ECB / OATH (9)
IssuedViolationHearingBalance
Jan 12, 2026Construction CLASS - 2
OBSERVED NOT HAVING PROPER GAS APPLIANCE SHUT OFF VALVES FOR COOKING EQUIPMENT AND HOT WATER HEATERS. VENTS TO HOT WATER HEATER EXHAUST AND GAS DRYERS NOT USING THE PROPER MATERIAL. USING PVC WASTE LINES FOR WA
#39173500P
Feb 6, 2026
POP/IN-VIO
$0
Jan 12, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DETECTED GAS LEAK AT BOILER ROOM. LOCATED ON FIRST FLOOR., REPAIR AND/REPLACE
#39173509L
Feb 6, 2026
POP/IN-VIO
$0
Jan 12, 2026Construction CLASS - 2
OBSERVED ON THE GROUND FLOOR SPRINKLER HEAD OBSTRUCTED ALSO NO FIRE STOP PROTECTION AROUND PIPE PENETRATION. WATER FOUNTAIN AND WASTE LINE GOING THROUGH ELECTRICAL ROOM WHICH IS CONTRARY TO CODE SECTIONS EC 110
#39173501R
Feb 6, 2026
POP/IN-VIO
$0
Sep 27, 2021Boilers CLASS - 2
DRAFT IND.CANNOT RUN CONTINOUS MUST BE NTERLOCKED ,AND COMBUSTION AIR FAN TO BE INTERLOCKED,THIS IS A WATER HTR WITH H STAMP
#39048200K
Oct 15, 2021
POP/IN-VIO
$0
Jul 24, 2018Plumbing CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: FAILURE TO COM PLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1: 27-911. OBSERVED ON 7/24/18 AT ABOVE ADDRESS SINK IN THE MAINTENANCE ROOM BEING DRAINED IN
#35342349K
Oct 2, 2018
POP/IN-VIO
$0
Aug 18, 2017Construction CLASS - 1
FAILURE TO COMPLY WITH COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION#35272426Y ISSUED ON 07-11-17 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01.FOR WORK W/O PERMIT AT LAUNDR
#35277052L
Nov 21, 2017
POP/IN-VIO
$0
Jul 11, 2017Construction CLASS - 1
WORK W/OUT A PERMIT. OBSERVED IN LAUNDRY ROOM ON MAIN FLR (1 STORY) GAS PLUMBING CONNECTIONS MADE TO DRYERS W/OUT PERMIT. PHOTOS TAKEN. REM: OBTAIN ALL REQUIRED PERMITS.
#35272426Y
Sep 5, 2017
POP/IN-VIO
$0
Jul 11, 2017Plumbing CLASS - 1
FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED FROM DOB RECORDS THAT NO TEST WAS PERFORMED ON PLUMBING GAS CONNECTIONS MADE TO DRYERS IN LAUNDRY ON MAIN FLR. PHOTO TAKEN. REM: PERFORM TEST.
#35272427X
Sep 5, 2017
POP/IN-VIO
$0
Jan 13, 2017Plumbing CLASS - 1
RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPEMTN. AT TIME OF MY INSPECTION I OBSERVED IN THE LAUNDRY ROOM COMMERCIAL GAS FIRED DRYERS BEINGSUPPLIED GAS WITH FLEXIBLE RESIDENTIAL GAS HOSES.PHOTO TAKEN.RMDY:COM
#35226476P
Apr 4, 2017
POP/IN-VIO
$0
DOB (1)
IssuedViolationStatus
Feb 24, 2010CONSTRUCTION

#0203CD
DOB VIOLATION - ACTIVE
DOB NOW Safety (0)

None open.

HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 4:08 PM ET. BBL 4000680002.