Bronx · Block 2947 · Lot 7501 · 10457

1910 Arthur Ave

10 floors · 63,812 sq ft · built 1928 · class RA · owner of record: Arthur Tremont Llc

3open violations
$25,562ECB/OATH penalties owed
0HPD class C (immediately hazardous)
69dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 69 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 69 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 63,812 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 190 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 190 days
Annual filing
Energy audit and retro-commissioning (2027) Likely applies
Local Law 87 · Calendar year 2027
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2947). Agency page

Dec 31, 2027
in 434 days
Next due 2027
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $672,500 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2028
in 486 days
No Cycle 10 report on record yet
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-09-09 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (6) · $25,562 owed
IssuedViolationHearingBalance
Jun 16, 2025Boilers CLASS - 1
FOUND A FEDERAL BOILER #FST-125 OIL FIRED BY A MMG54P BURNER TO BE LEAKING WATER OUT THE REAR DOOR. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT CERT.OF CORRECTIONS
#39151182L
Aug 29, 2025
DEFAULT
$12,500
Aug 15, 2024Boilers CLASS - 2
FOUND A FEDERAL FST125 BOILER LEAKING FROM INSIDE CHAMBER/ BACKFLOW IS LEAKING/ OIL PUMPS MISSING BELT GUARD/ AIR FAN PR0VING SWITCH IS NOT WORKING PROPERLY/CORRECT ALL VIOLATING CONDITIONS/SUBMIT A CERTIFICATE
#39122040N
Nov 1, 2024
DEFAULT
$1,562
Feb 24, 2024Unknown CLASS - 2
I OBSERVED NEW INSTALLATION OF 2-60 AMP WATER HEATERS LOCATED IN UTILITY ROOM. APP X00435389 DOESN'T COVER WORK DONE. CONTRACTOR IS NOT CLAIMING WORK., OBTAIN PERMIT; OBTAIN ELECTRICAL PERMIT
#39106961H
May 3, 2024
DEFAULT
$2,000
Feb 24, 2024Unknown CLASS - 2
I OBSERVED THHN WIRE INSTALLED FREE AIR FROM PANEL OVER GENERATOR TO A DUCT DAMPER SPLICE BOX IN GENERATOR ROOM. APP X00435389 DOESN'T COVER WORK DONE. CONTRACTOR IS NOT CLAIMING WORK., COMPLY WITH EC; FIX ALL
#39106962J
May 3, 2024
DEFAULT
$2,000
Oct 19, 2022Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE7B&8B REPORT OF CRITICAL EXAM DOCUMENTING CONDITION OF EXTERIOR WALL&APPURTENANCES REQUIRED BY28-302.4 FOR CONTROL807938.AGG2 HIST OF NONCOMPLIANCE ON37021666J(AGG2),3
#37022831Z
Oct 16, 2023
IN VIOLATION
$1,250
Jun 1, 2021Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 7B AND 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL#807938.AGG2:HISTORY OF NONCOMPLI
#37021666J
Jan 31, 2022
IN VIOLATION
$6,250
DOB (0)

None open.

DOB NOW Safety (2)
IssuedViolationStatus
Jul 31, 2018Facades FISPNRF
FAILED TO FILE FISP CYCLE 8B TECHNICAL REPORT BY 02/21/2018
Active
Aug 30, 2013Facades FISPNRF
FAILED TO FILE FISP CYCLE 7B TECHNICAL REPORT BY 08/21/2012
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 23, 2026, 10:56 AM ET. BBL 2029477501.