Bronx · Block 3222 · Lot 100 · 10453

1900 Sedgwick Avenue

3 floors · 59,713 sq ft · built 1986 · class W1 · owner of record: Nyc Department Of Education

20open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
180dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 59 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 59,713 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 180 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 180 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 5 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1155 days
Next cycle year 2029
Energy audit and retro-commissioning (2032) Likely applies
Local Law 87 · Calendar year 2032
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 3222). Agency page

Dec 31, 2032
in 2251 days
Next due 2032
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-03 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (11)
IssuedViolationHearingBalance
Aug 3, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORFPSC DOORS DO NOT SELF-CLOSE PROPERLY. AT LIBRARY, STAFF LOUNGE AND GENERAL OFFICE. CLASSROOM DOORS DO NOT SELF-CLOSE WHEN TESTED AT RM #S-1
#35734649P
Aug 21, 2026
POP/IN-VIO
$0
Aug 3, 2026Construction CLASS - 2
RE-ISSUE #35725296Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIOR FPSC DOORS DO NOT SELF-CLOSE PROPERLY WHEN TESTED AT 2ND FLOOR STAIRCASE "A". CLASSROOM DOORS DO NOT SELF-CLOSE PROPER
#35734647L
Aug 21, 2026
POP/IN-VIO
$0
Aug 3, 2026Construction CLASS - 2
RE-ISSUE #35725297X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED ON THE ROOF, WATER DAMAGE TO ROOF MATERIAL HAS CAUSED IT TO BUBBLE UP WITH WATER. REMEDY: REPAIR AND/OR REPLACE.
#35734646J
Aug 21, 2026
POP/IN-VIO
$0
Aug 3, 2026Construction CLASS - 2
RE-ISSUE #35725295M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ON FIRST FLOOR CAFETERIA IN SERVING AREA "1" LIGHT FIXTURE IS NOT WORKING BECAUSE OF WATER DAMAGE FROM CEILING AROUND LIGHT. RE
#35734648N
Aug 21, 2026
POP/IN-VIO
$0
Sep 9, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:INTERIOR SMOKE DOORS DO NOT SELF-CLOSE PROPERLY.2ND FLR-STAIR A,STAIR B.1ST FLR-LOADING DOCK EXIT DOOR,SMOKE DOOR NEAR 104,EXIT 3 INTERIOR DOOR.CLASSR
#35725296Y
Oct 10, 2025
POP/IN-VIO
$0
Sep 9, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ROOF MATERIAL IS STARTING TO BUBBLE UP DUE TO WATER DAMAGE.SEVERAL LOCATIONS ON THE ROOF.REM:REPAIR AND/OR REPLACE.
#35725297X
Oct 10, 2025
POP/IN-VIO
$0
Sep 9, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:INTERIOR SMOKE DOORS DO NOT SELF-CLOSE PROPERLY.1ST FLR-EXIT 4A,EXIT 5A,GYM DOOR101,SMOKE DOOR NEAR 107,SMOKE DOOR 101.CLASSROOM DOORS DO NOT CLOSE PR
#35725298H
Oct 10, 2025
POP/IN-VIO
$0
Sep 9, 2025Construction CLASS - 2
REISSUE#35689042Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT THE TIME OF INSPECTION OBSERVED & NOTED THAT AT FIRST FLOOR KITCHEN SERVING AREA ONE LIGHT FIXTURE WITH IS DAMAGED DUE TO PREVIOUS LEAK
#35725295M
Oct 10, 2025
POP/IN-VIO
$0
Sep 23, 2024Construction CLASS - 2
REISSUE#35672633J DATE OF ISSUE:07.12.2023 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER AT THE TIME OF INSPECTION OBSERVED & NOTED THAT AT FIRST FLOOR KITCHEN SERVING AREA ONE LIGHT FIXTURE APPROX.2'WX
#35689042Z
Nov 29, 2024
POP/IN-VIO
$0
Jul 12, 2023Construction CLASS - 2
RE-ISSUE #35658011Y FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: OBSERVED ON THE FIRST FLOOR KITCHEN SERVING AREA HAS ONE OF THE LIGHT NOT WORKING DUE TO WATER DAMAGE FROM THE CEILING. REMEDY:
#35672633J
Oct 20, 2023
POP/IN-VIO
$0
Jun 3, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED:OBSERVED@1FL KITCHEN SERVING AREA HAS LIGHT FIXTURE APRX2'WX4'L WHICH IS DAMAGED DUE TO PREV LEAK COMING FROM CEILING RM ISNT WELLLIT CREATING HAZARD.REPAI
#35658011Y
Sep 16, 2022
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (9)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen
Aug 3, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORFPSC DOORS DO NOT SELF-CLOSE PROPERLY. AT LIBRARY, STAFF LOUNGE AND GENERAL OFFICE. CLASSROOM DOORS DO NOT SELF-CLOSE WHEN TESTED AT RM #S-1Open
Aug 3, 2026ECBConstruction: RE-ISSUE #35725296Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIOR FPSC DOORS DO NOT SELF-CLOSE PROPERLY WHEN TESTED AT 2ND FLOOR STAIRCASE "A". CLASSROOM DOORS DO NOT SELF-CLOSE PROPEROpen
Aug 3, 2026ECBConstruction: RE-ISSUE #35725297X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED ON THE ROOF, WATER DAMAGE TO ROOF MATERIAL HAS CAUSED IT TO BUBBLE UP WITH WATER. REMEDY: REPAIR AND/OR REPLACE.Open
Aug 3, 2026ECBConstruction: RE-ISSUE #35725295M. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ON FIRST FLOOR CAFETERIA IN SERVING AREA "1" LIGHT FIXTURE IS NOT WORKING BECAUSE OF WATER DAMAGE FROM CEILING AROUND LIGHT. REOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 2, 2026, 5:50 AM ET. BBL 2032220100.

Look up another building