Manhattan · Block 1919 · Lot 53 · 10030

180 West 135 Street

11 floors · 26,400 sq ft · built 1932 · class P3 · owner of record: Ymca Of Greater N Y

54open violations
$7,500ECB/OATH penalties owed
2HPD class C (immediately hazardous)
97dto Facade inspection report (Cycle 10A)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 45 days
Keep the report on file (not filed with DOB)
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $75,000 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2027
in 97 days
No Cycle 10 report on record yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 26,400 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 166 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 166 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 10 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 776 days
Next cycle year 2028
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-09-03 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (30) · $7,500 owed
IssuedViolationHearingBalance
Jul 23, 2026Construction CLASS - 2
NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 FAILURE-TO-MAINTAIN VIOLATION #39145007N ISSUED 4/15/2025 CITING HOLE PENETRATIONS THROUGHOUT THE BUILDING. AT INSPECTION, FIRESTOPPING HAD BEEN NEWLY INSTALLED
#39197380X
Oct 1, 2026
IN VIOLATION
$1,250
Jan 2, 2026Construction CLASS - 2
OBSERVED ON THE ROOF, SIX FLOOR AND BASEMENT LACK FIRESTOPPING AT PENETRATIONS THROUGH WALLS FOR PIPE LINES. ON THE 11 TH FLOOR STAIRCASE STANDPIPE CAP IS OBSTRUCTED BY ELECTRICAL LINE. ON FLOORS 11, 6,7,8,9 SP
#39172209P
Mar 12, 2026
IN VIOLATION
$1,250
Jan 2, 2026Construction CLASS - 2
OBSERVED ON THE 9TH AND 7TH FLOOR SINKS NOT OPERATIONAL. ON THE SIX FLOOR DRINKING FOUNTAIN DRAIN IS NOT INSTALLED PROPERLY. FIRST FLOOR BASEMENT USING PLASTIC CAPS ON STANDPIPE. FIRE PUMP ROOM INSTALLED PIPING
#39172208N
Mar 12, 2026
IN VIOLATION
$1,250
Dec 30, 2025Elevators CLASS - 1
CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION
#39171942N
Mar 5, 2026
IN VIOLATION
$1,250
Dec 30, 2025Elevators CLASS - 1
CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. FOR A REINSPECTION. CLASS 2
#39171943P
Mar 5, 2026
IN VIOLATION
$1,250
Apr 15, 2025Elevators CLASS - 2
CLASS 2 ITEMS: CATEGORY 1 TEST TAG EXPIRED. CLEAN ENTIRE PIT AREA.
#39144950J
Jun 26, 2025
IN VIOLATION
$0
Apr 15, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS THROUGHOUT THE BUILDING. POTENTIAL FIRE HAZARD., PROVI
#39145007N
Jun 26, 2025
IN VIOLATION
$0
Apr 14, 2025Boilers CLASS - 2
FOUND A ROCKMILL MP125 STEAM BOILER SLIGHT LEAK FROM INSIDE THE BOILER/FRESH AIR FAN PROVING SWICTH NOT WORKING PROPELY/ SAFETEY VALVE DRAINTERMINATION TIED TOGETHER AND WITH THREADS AT THE END/BODY DRAIN MISSI
#39144783L
Jun 26, 2025
IN VIOLATION
$0
Apr 14, 2025Boilers CLASS - 2
FOUND ON SITE A TEMPORARY OIL TANK OUTSIDE PERMIT #M00807169-LA NOT SIGNED OF. PERMIT FILLING UNDER PENALTY REVIEW., MAINTAIN BOILER; CORRECT ALL VIOLATING CONDITION/ SUBMIT CERIFICATE OF CORRECTION
#39144799X
Jun 26, 2025
IN VIOLATION
$0
Mar 21, 2025Elevators CLASS - 1
CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, EMAIL THE D.O.B. EIR@BUILDINGS.NYC.GOV. FOR A REINSPECTION
#39142483K
Nov 17, 2025
IN VIOLATION
$1,250
Jan 16, 2024Plumbing CLASS - 2
AS PER PROVISION OF LAW 28-301.1. FAILURE TO MAINTAIN PLUMBING SYSTEM. FOUND LAVATORY WASTE ON 4TH FL. WOMEN'S ROOM LEAKING AND FAWCETT LOOSE AS PER P.C. 702.1 AND 602.3., REMOVE NON-COMPLYING MATERIAL OR EQUIP
#39103528N
Feb 10, 2025
IN VIOLATION
$0
Jan 5, 2023Unknown CLASS - 2
I OBSERVED IN VARIOUS RESTROOMS AND THE KITCHENS ON FLOORS 4 THROUGH 10 DEFECTIVE, MISWIRED, GFCI OUTLETS, ALSO NOTED IN THE KITCHEN THE OUTLET BOX DISCONNECTED AND UNSECURED., INSTALL GFC1 PROTECTION; PROPERLY
#39077064H
Oct 12, 2023
IN VIOLATION
$0
Jan 5, 2023Construction CLASS - 2
OBSERVED: AT EXPOSURE #1&4,EXIT DOORS, ROOF LEVEL EXIT DOOR AND ELEVATOR ROOM DOOR, DO NO SELF-CLOSING PROPERLY DUE OVERLAPPING DOOR LEAVES, OR SELF CLOSING SYSTEM., REPAIR/REPLACE DOOR
#39077054Y
Sep 14, 2023
IN VIOLATION
$0
Jan 5, 2023Unknown CLASS - 2
I OBSERVED IN THE BASEMENT AREA NEAR THE ELECTRICAL ROOM ROMEX WIRING PASSING THROUGH A WALL SUPPLYING POWER TO A FAN IN A STORAGE CLOSET, ALSO NOTED A DEFECTIVE FLEXIBLE CORD PASSING AROUND A DOORWAY,ALSO NOTE
#39077063X
Oct 12, 2023
IN VIOLATION
$0
Jan 5, 2023Unknown CLASS - 2
I OBSERVED IN THE CORRIDORS ON ALL FLOORS, FAILURE TO PROPERLY TERMINATE THE RACEWAYS SUPPLYING POWER TO THE CEILING LIGHTS AND EMERGENCY LIGHTING THE WIREMOLD RACEWAYS ARE NOT MECHANICALLY CONNECTED AS REQUIRE
#39077062Y
Oct 12, 2023
IN VIOLATION
$0
Jan 5, 2023Construction CLASS - 2
OBSERVED: AT ROOF LEVEL, ELEVATOR ROOM, VARIOUS OPENINGS DUE TO PENETRATION OF PIPES THROUGH WALLS, WALL DAMAGE WITHOUT FIRE STOPPING PROVIDED., PROVIDE/MAINTAIN FIRE STOPPING
#39077052K
Sep 14, 2023
IN VIOLATION
$0
Dec 9, 2022Local Law CLASS - 2
FAILURE TO SUBMIT ACCEPTABLE REQUIRED CYCLE 9A REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL & APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #906681.REMEDY:SUBMIT ACCEPTABLE REQUIRED TE
#37024982P
Apr 20, 2023
IN VIOLATION
$0
May 25, 2022Construction CLASS - 2
AT 6TH/5TH FL, CORRIDORS AND STAIRCASE A&B WITHOUT EMERGENCY LIGHTS INTALLED. ALSO, AT 5TH FL STAIR B & 6TH FL FRONT ELEVATOR, EXISTING EMERGENCY LIGHTS WERE NOT OPERATIONAL WHEN TESTED, REPAIR/REPLACE LIGHTING
#39062849X
Oct 27, 2022
IN VIOLATION
$0
May 25, 2022Construction CLASS - 2
AT CELLAR LEVEL, UTILITY ROOM, VARIOUS OPENINGS DUE TO PENETRATION OF PIPES THROUGH CEILINGS AND WALLS WITHOUT FIRE STOPPING PROVIDED, PROVIDE/MAINTAIN FIRE STOPPING
#39062846K
Oct 27, 2022
IN VIOLATION
$0
May 25, 2022Construction CLASS - 2
AT 6TH/5TH FL, STAIRCASE B METAL STAIR WITH DETERIORATED AND BROKEN STEPS, REPAIR AND/OR REPLACE
#39062848Y
Oct 27, 2022
IN VIOLATION
$0
May 25, 2022Construction CLASS - 2
AT EXPOSURE #1&2,EXIT DOORS DO NO SELF-CLOSING PROPERLY DUE OVERLAPPING DOOR LEAVES, OR MISSING SELF CLOSING SYSTEM., REPAIR/REPLACE DOOR
#39062847M
Oct 27, 2022
IN VIOLATION
$0
Oct 28, 2021Construction CLASS - 2
I OBSERVED IN THE GAS METER ROOM LOCATED IN THE BASEMENT CRACKED AND ALSO BROKEN CAST IRON SANITARY PIPING AND FITTINGS., REPAIR AND/OR REPLACE
#39050232H
May 5, 2022
ADMIT/IN-VIO
$0
Jan 6, 2021Boilers CLASS - 2
PUMP LEAKING . CORRECT VIOLATING CONDITION & SUBMIT A CERTIFICATE OF CORRECTION.
#39034391P
Jul 1, 2021
IN VIOLATION
$0
May 31, 2018Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT ROOF IN WATERTOWER ROOM,BRICK COLUMN NEXT TO WATER TANK HAS LOOSE BRICKS,CRACKED BRICKS AND ENTIRE COLUMN DETACHED FROM WALL.REM:REPAIR AND/OR REPLACE CO
#35332093R
Jan 11, 2019
IN VIOLATION
$0
May 31, 2018Unknown CLASS - 2
ELECTRICAL WORK W/O A PERMIT. I OBSERVED IN THE MAIN ELECTRICAL ROOM IN THE BASEMENT THE INSTALLATION OF A FIRE PUMP SERVICE SWITCH AND ON THE 4TH AND 9TH FLOOR THE RETROFIT OF EXISTING ELECTRICAL PANELS WITH
#35331850K
Sep 13, 2018
IN VIOLATION
$0
May 31, 2018Unknown CLASS - 2
I OBSERVED IN THE WATER METER ROOM. THE GROUNDING ELECTRODE CONDUCTOR EXTREMELY DETERIORATED AT THE CONNECTION ON THE WATER PIPE. PHOTOS TAKEN. RMDY: PROVIDE PROPER CLEAN CONNECTION ON THE WATER PIPE AS PER
#35331851M
Sep 13, 2018
IN VIOLATION
$0
May 31, 2018Unknown CLASS - 2
I OBSERVED ON THE ROOF AT STAIR BA AND INSIDE THE 5TH AND 6TH FLOOR JANITORIAL CLOSETS; RACEWAYS NOT SUPPORTED AND SUBJECTED TO DAMAGE. PHOTOS TAKEN. RMDY: PROVIDE PROPER SUPPORT OF RACEWAYS.
#35331852Y
Sep 13, 2018
IN VIOLATION
$0
May 31, 2018Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 5/31/18AT ABOVE ADDRESS. NO ADEQUATE VENTILATION IN GAS METER ROOM. RMDY: REPAIR AND OR REPLACE.
#35334110Z
Jan 11, 2019
IN VIOLATION
$0
Aug 18, 2017Construction CLASS - 3
OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR BLDG DEPT RECORDS.C OF O #77527 INDICATES 5TH-9TH STORIES TO BE 35 BEDROOMS;WASH ROOM;TOILETS & SHOWER ROOMS. NOTED: ON 5TH FL ROOM 505 IS OCCUPIED AS OFFICE
#35289914Y
Mar 8, 2018
ADMIT/IN-VIO
$0
Apr 5, 2016Construction CLASS - 3
OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPT RECORDS CERTIFICATE OF OCCUPANCY #M77527 INDICATES 5TH THROUGH 9TH FLRS TO BE 35 BEDROOMS; WASHROOMS, TOILET AND SHOWER ROOM
#35177625L
Oct 13, 2016
IN VIOLATION
$0
DOB (1)
IssuedViolationStatus
Feb 22, 2022NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
#00654
DOB VIOLATION - ACTIVE
DOB NOW Safety (23)
IssuedViolationStatus
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Oct 2, 2026Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Report
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Aug 29, 2025Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Report
Active
Aug 29, 2025Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Report
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Report
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Report
Active
Feb 22, 2022Facades FISPNRF
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
Active
HPD (2) · C 2 · B 0 · A 0
IssuedClassViolationCorrect by
Apr 4, 2024CApt 418 · § 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTIRE APARTMENT LOCATED AT APT 418, 4th STORY, 5th APARTMENT FROM EAST AT SOUTHApr 18, 2024
Feb 1, 2024CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES AT COMMUNITY BATHROOM, 4th STORYFeb 27, 2024

Issued in the last 120 days

DateSourceWhatNow
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test ReportOpen
Jul 23, 2026ECBConstruction: NO CERTIFICATE OF CORRECTION ON FILE FOR CLASS 1 FAILURE-TO-MAINTAIN VIOLATION #39145007N ISSUED 4/15/2025 CITING HOLE PENETRATIONS THROUGHOUT THE BUILDING. AT INSPECTION, FIRESTOPPING HAD BEEN NEWLY INSTALLEDOpen