Queens · Block 13406 · Lot 28 · 11434

178-02 147 Avenue

4 floors · 28,228 sq ft · built 2014 · class H9 · owner of record: Universal Hotel Llc

4open violations
$5,500ECB/OATH penalties owed
0HPD class C (immediately hazardous)
184dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 63 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 28,228 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 184 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 184 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1159 days
Next cycle year 2029

Open violations

ECB / OATH (3) · $5,500 owed
IssuedViolationHearingBalance
Jul 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED STORAGE INSIDE OF SPRINKLER ROOM. (GARDEN HOLES, BOXES, CLEANING EQUIPMENT) POTENTIAL FIRE HAZARD, REPAIR AND/REPLACE
#39195688N
Oct 27, 2026
$2,500
Jul 10, 2026Boilers CLASS - 3
@HOT WATER HEATER ROOM @CELLAR>#1 HWH IS INOPERABLE+BOTH CIRCULATORS ARE INCORRECTLY INSTALLED+FLUE PIPE JOINT CLAMP IS MISSING, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION
#39195574P
Oct 27, 2026
PENDING
$500
Jul 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED GAS POWERED EQUIPMENT SNOW BLOWER)INSIDE OF STORAGE ROOM LOCATED AT BASEMENT LEVEL. POTENTIAL FIRE HAZARD, REPAIR AND/REPLACE
#39195689P
Oct 27, 2026
$2,500
DOB (0)

None open.

DOB NOW Safety (2)
IssuedViolationStatus
Apr 20, 2026GHG Emissions - LL97 FTF-EN-LL97320
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Report
Active
HPD (1) · C 0 · B 0 · A 1
IssuedClassViolationCorrect by
May 11, 2026A(A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS.Aug 14, 2026

Issued in the last 120 days

DateSourceWhatNow
Jul 10, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED STORAGE INSIDE OF SPRINKLER ROOM. (GARDEN HOLES, BOXES, CLEANING EQUIPMENT) POTENTIAL FIRE HAZARD, REPAIR AND/REPLACEClosed
Jul 10, 2026ECBBoilers: @HOT WATER HEATER ROOM @CELLAR>#1 HWH IS INOPERABLE+BOTH CIRCULATORS ARE INCORRECTLY INSTALLED+FLUE PIPE JOINT CLAMP IS MISSING, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTIONOpen
Jul 10, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED GAS POWERED EQUIPMENT SNOW BLOWER)INSIDE OF STORAGE ROOM LOCATED AT BASEMENT LEVEL. POTENTIAL FIRE HAZARD, REPAIR AND/REPLACEClosed
Jul 10, 2026ECBElevators: CLASS 2: CATEGORY 1 TEST TAG WAS OUTDATED AS PER ASME A17.1 8.6.1.7, WHICH REQUIRES CURRENT TEST TAGS. REMEDY: UPDATE AND POST A VALID CATEGORY 1 TEST TAG. CATEGORY 5 TEST TAG WAS MISSING AS PER ASME A17.1 8.6.Closed

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 29, 2026, 5:39 PM ET. BBL 4134060028.