Queens · Block 10330 · Lot 110 · 11433

177-08 Liberty Avenue

3 floors · 27,400 sq ft · built 2011 · class H4 · owner of record: Ahi Group, Llc

4open violations
$3,000ECB/OATH penalties owed
0HPD class C (immediately hazardous)
166dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 45 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 27,400 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 166 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 166 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 410 days
Next cycle year 2027
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-07-21 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (2) · $3,000 owed
IssuedViolationHearingBalance
Jul 9, 2026Construction CLASS - 1
ATOI OBSERVED IN BASEMENT LAUNDRY ROOM GAS FLEX LINES BEING USED ON DRYERS AND PVC PIPPING USED ON DRAINAGE FOR WASHING MACHINES. WHICH IS CONTRARY TO CODES (. FGC 411.1(2) & . PC 1101.10 ), REPAIR AND/REPLACE
#39195374K
Mar 10, 2027
$2,500
Jul 8, 2026Boilers CLASS - 3
@HOT WATER STORAGE TANK ROOM 2ND FLOOR>HW RE CIRCULATOR IS INSTALLED INCORRECTLY, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION
#39195283P
Mar 10, 2027
PENDING
$500
DOB (0)

None open.

DOB NOW Safety (3)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 16, 2026, 8:20 PM ET. BBL 4103300110.