Brooklyn · Block 250 · Lot 7 · 11201

175 Remsen Street

12 floors · 129,520 sq ft · built 1962 · class O6 · owner of record: 175 Remsen Owner Tic 1 Llc

7open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
68dto Annual boiler inspection (2 boilers)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 68 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-05-07 (Accepted). Agency page

Dec 31, 2026
in 68 days
1 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 129,520 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 189 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 189 days
Annual filing
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. DOB facade records for this building show $52,500 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2028
in 485 days
No Cycle 10 report on record yet
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1164 days
Next cycle year 2029
Energy audit and retro-commissioning (2030) Likely applies
Local Law 87 · Calendar year 2030
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 250). Agency page

Dec 31, 2030
in 1529 days
Next due 2030

Open violations

ECB / OATH (3)
IssuedViolationHearingBalance
Sep 16, 2024Boilers CLASS - 3
FEDERAL PLW-100 BOILER=BODY DRAIN PIPES MISSING AT SAFETY VALVES+DEFECTIVE SAIL SWITCH AT FRESH AIR FAN+BOTH BUILDING WATER PRESSURE PUMPS ARE LEAKING INTO BOILER ROOM;CORRECT VIOLATION+SUBMIT CERTIFICATE OF CO
#39124932H
Nov 20, 2024
DEFAULT
$0
Dec 26, 2023Elevators CLASS - 1
CLASS 1 ITEM: 2 FUSES IN DISPATCH CONTROLLER HAVE THE INCORRECT FUSE RATING. CLASS 2 ITEMS:ELEVATOR MAIN GEAR CASE IS LEAKING OIL AND NEEDS REPAIR.
#39102214X
Apr 19, 2024
IN VIOLATION
$0
Dec 11, 2023Construction CLASS - 2
REMOVAL OF PUBLIC PROTECTION FROM UNSAFE FACADE WITHOUT APPROVAL FROM THE DEPARTMENT. -AT TIME OF INSPECTION I OBSERVED THE SIDEWALK SHED PROTECTION REMOVED FROM SITE. THE OWNER DID NOT OBTAIN DEPARTMENT APPROV
#35674313J
Apr 4, 2025
IN VIOLATION
$0
DOB (3)
IssuedViolationStatus
Dec 1, 2023FAILURE TO POST ENERGY GRADE/SCORE
FAILURE TO DISPLAY ENERGY EFFICIENCY SCORE AND ENERGY EFFICIENCY GRADE AS PER ADCODE SEC. 28-309.12.3
#2301032
DOB VIOLATION - ACTIVE
Apr 13, 2020CONSTRUCTION

#E0201WZ
DOB VIOLATION - ACTIVE
Feb 5, 1998ELEVATOR

#668D01
VIOLATION UNSERVED ECB-ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Dec 1, 2023Energy Grade - LL33 FTP-EN-EGRDEA
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 24, 2026, 3:38 PM ET. BBL 3002500007.

Look up another building