Bronx · Block 2899 · Lot 1 · 10457

1732 Webster Avenue

4 floors · 21 apartments · 17,548 sq ft · built 1930 · class H6 · owner of record: 1732 Webster Propco Llc

6open violations
$10,625ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 65 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 65 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 81 days
Annual
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueNo current registration found
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 796 days
Next cycle year 2028

Open violations

ECB / OATH (6) · $10,625 owed
IssuedViolationHearingBalance
Mar 30, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED GAS LEAK AT BASEMENT LEVEL. DEFECTIVE UNIT. CON ED B TAGGED IT., REPAIR AND/OR REPLACE
#39182409Z
Jun 5, 2026
IN VIOLATION
$1,250
Mar 30, 2026Boilers CLASS - 2
FOUND AO SMITH GAS HOT WATER HEATER MODEL# BTH-300A NOT OPERABLE., MAINTAIN BOILER; REPAIR OR REPLACE HOT WATER HEATER.
#39182365X
Jun 5, 2026
IN VIOLATION
$1,250
Mar 30, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS THROUGHOUT THE BUILDING. HOLES ARE COVERED WITH VENT COVERS OVER THEM. POTENTIAL HAZARD, CAN AIDE FIRE AND SMOKE IN AN EMERGENCY
#39182410X
Jun 5, 2026
IN VIOLATION
$2,500
Mar 30, 2026Elevators CLASS - 1
CLASS 1 CEASE USE: UPON INSPECTION, MACHINE BRAKE ELECTRICAL SAFETY SWITCHES WERE FOUND INOPERATIVE. THIS CONDITION COMPROMISES THE ELEVATOR'S ABILITY TO SAFELY STOP AND HOLD THE CAR. ELEVATOR SHALL BE REMOVED
#39182476Z
Jun 5, 2026
IN VIOLATION
$1,250
Dec 2, 2024Elevators CLASS - 2
CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. BRAKE MAINTENANCE TAGEXPIRED. PROVIDE ELECTRICAL SCHEMATIC'S FOR THIS EQUIPMENT.
#39131683L
Jul 25, 2025
DEFAULT
$3,125
Aug 30, 2023Elevators CLASS - 1
DOOR RESTRICTOR NOT WORKING PROPERLY; REPAIR ; PHONE
#39093721Z
Dec 1, 2023
IN VIOLATION
$1,250
DOB (1)
IssuedViolationStatus
Oct 17, 2023CONSTRUCTION
COMM'S ORDER APPROX 50' MONOPOLE SIGN STRUCTURE ON LOT. REMEDY: OWNER TO IMMEDIATELY ENGAGE A NYS PE EXPERIENCED W/MONOPOLE SIGN STRUCTURES TO INSPECT STRUCTURE INCLUDING VISUAL INSP. ENGINEERING & MATERIALS TESTING EVALUATION OF ALL COMPONENTS OF STRUCTURE & FOUNDATION ETC IMMEDIATELY NOTIFY DOB OF
#23-02903
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Jan 8, 2026Gas Piping - LL152 FTF-PL-PER
Cycle 2, Sub-cycle A (premises is in Community District 3)
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 27, 2026, 10:25 AM ET. BBL 2028990001.

Look up another building