Bronx · Block 2930 · Lot 75 · 10457

1717 Fulton Avenue

4 floors · 128,000 sq ft · built 1995 · class W1 · owner of record: Nyc Department Of Education

25open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
168dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 47 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 128,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 168 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 168 days
Annual filing
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 778 days
Next cycle year 2028
Energy audit and retro-commissioning (2030) Likely applies
Local Law 87 · Calendar year 2030
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2930). Agency page

Dec 31, 2030
in 1508 days
Next due 2030
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-23 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (11)
IssuedViolationHearingBalance
Jul 8, 2026Construction CLASS - 2
REISSUE ECB#35693528K FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT BASEMENT GAS METER RM C06 AND ELECTRIC METER RM C13 BOTH ROOM WITH STORAGE OF MULTIPLE VARIOUS ITEMS GARAGE PAILS,LADDER,BOXE
#35734759X
Aug 7, 2026
POP/IN-VIO
$0
Jul 8, 2026Construction CLASS - 2
REISSUE ECB#35693526R FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT ROOF/PENT HOUSE NEAR STAIR B SEVERAL PAVER TILES CHIPPED/BROKEN.REM:REPAIR AND/OR REPLACE.
#35734760N
Aug 7, 2026
POP/IN-VIO
$0
Jul 8, 2026Construction CLASS - 2
REISSUE ECB#35693525P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT 3RD FL HALLWAY/RM 310 AND RM 305 WATER DAMAGE TO CEILINGS/WALLS WITH SPALLING/STAINING TILES/PLASTER/PAINT.REM:REPAIR AND/OR
#35734761P
Aug 7, 2026
POP/IN-VIO
$0
Aug 22, 2025Construction CLASS - 2
RE-ISSUE #35688608Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AT PENTHOUSE/ROOF LEVEL NEAR STAIRCASE "B" THEREIS SEVERAL PAVER TILES BROKEN AND CREATING A TRIP HAZARD TO ANYONE. RE
#35693526R
Oct 17, 2025
POP/IN-VIO
$0
Aug 22, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVEDA DESK AND MATERIAL IN GAS METER ROOM DURING TIME OF INSPECTION. REMEDY: REMOVE DESK AND MATERIAL.
#35693528K
Oct 17, 2025
POP/IN-VIO
$0
Aug 22, 2025Construction CLASS - 2
RE-ISSUE #35688609X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVED AT 3RD FLR CORRIDOR BY STAIR "B" AND DIRECTLY ABOVE RM 310 ENTRY DOOR. CEILING IS DAMAGED DUE TO WATER PENETRATIONS CO
#35693525P
Oct 17, 2025
POP/IN-VIO
$0
Sep 11, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: OBSERVEDAT PENTHOUSE/ROOF LEVEL, NEAR STAIRCASE 'B' THERE IS SEVERAL PAVER TILES BROKEN AND CREATING A TRIPPING HAZARD TO ANYONE. REMEDY: REPAIR AND
#35688608Y
Oct 11, 2024
POP/IN-VIO
$0
Sep 11, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTE: OBSERVED AT 3FLR. CORRIDOR BY STAIR 'B' AND DIRECTLY ABOVE RM. 310 ENTRY DOOR. CEILING IS DAMAGED DUE TO WATER PENETRATIONS COMING PENTHOUSE/ROOF ABO
#35688609X
Oct 11, 2024
POP/IN-VIO
$0
Mar 15, 2021Elevators CLASS - 1
CLASS 1 VIOLATION ISSUED, NO DLM INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC, REMEDY; FILE APPLICATION, INSTALL DLM, CLASS 2, VIOLATION ISSUED, IMPROPER CODE DATA TAG, /
#39037737R
Apr 16, 2021
POP/IN-VIO
$0
Sep 18, 2020Elevators CLASS - 1
CLASS 1 VIOLATION RECURRING CONDITION, NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC REMEDY; FILE APPLICATION,INSTALL DLM AND PERFORM AND FILE TEST
#39028910R
Oct 6, 2020
POP/IN-VIO
$0
Feb 27, 2020Elevators CLASS - 1
DOOR ZONE RESTRICTOR NOT WORKING ( CU ) . ALARM BELL NO BUZZER ( CU ). EMERGENCY STOP SWITCH NO BUZZER ( CU ). INTERCOM DID NOT WORK. NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12
#39018513Y
Mar 16, 2020
POP/IN-VIO
$0
DOB (6)
IssuedViolationStatus
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#07850
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#07851
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#26970
DOB VIOLATION - ACTIVE
Jun 20, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
#45027
DOB VIOLATION - ACTIVE
Jul 6, 2021ELEVATOR

#9028/699160
DOB VIOLATION - ACTIVE
Oct 1, 2019RETAINING WALL
FAILED TO FILE CYCLE 1 TECHNICAL REPORT BY 12/31/2018 PER RCNY 103-09
#00456
DOB VIOLATION - ACTIVE
DOB NOW Safety (8)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Apr 23, 2025Retaining Walls
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Jun 20, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION
Active
Oct 1, 2019Retaining Walls FTF-RW-INITL
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 14, 2026, 7:40 PM ET. BBL 2029300075.