Brooklyn · Block 7322 · Lot 7 · 11229

1716 Avenue T

6 floors · 60 apartments · 55,800 sq ft · built 1932 · class D4 · owner of record: 1716 Avenue T Realty Llc

20open violations
$41,937ECB/OATH penalties owed
0HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 2026-09-01
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 64 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 64 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 80 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 55,800 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 185 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 185 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 15 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 429 days
Next cycle year 2027
Energy audit and retro-commissioning (2032) Likely applies
Local Law 87 · Calendar year 2032
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 7322). Agency page

Dec 31, 2032
in 2256 days
Next due 2032
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-17 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (18) · $41,937 owed
IssuedViolationHearingBalance
Jul 12, 2023Elevators CLASS - 1
CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS PRESENTS A HAZZARDOUS CONDITION. RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. WHEN SERVICE RESTORE CONTACT NYCDOB AT EIR@BUILDINGS.N
#39090123P
Oct 18, 2023
IN VIOLATION
$1,250
Feb 18, 2023Elevators CLASS - 1
97-X-17 ELEVATOR OUT OF SERVICE. REPAIR AND CALL THE DOB ELEVATOR DIVISION AT (212)393-2144 FOR A RE-INSPECTION.
#39079923X
Apr 26, 2023
IN VIOLATION
$1,250
Aug 22, 2022Elevators CLASS - 1
CLASS 1 ITEM: DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS' SERVICE PRESENTIN CONTROLLER. INSTALL FIREMANS' SERVICE SO DLM IS IN COMPLIANCE WITHSECTION 3.10.12 OF APPENDIX K3. CLASS 2 ITEM: MISSING IN C
#39068563H
Dec 28, 2022
IN VIOLATION
$1,563
Jun 14, 2022Elevators CLASS - 1
PROVIDE BRAILLE'S ON ALL FLOORS., DLM IMPROPERLY INSTALLED ON THIS DEVICE. NO FIREMANS' SERVICE PRESENT IN CONTROLLER. INSTALL FIREMANS' SERVICE SO DLM IS IN COMPLIANCE WITH SECTION 3.10.12 OF APPENDIX K3.
#39064092M
Oct 19, 2022
IN VIOLATION
$1,250
Apr 5, 2022Elevators CLASS - 1
DLM IMPROPERLY INSTALLED ON THIS DEVICE . NO FIREMAN'S SERVICE PRESENT IN CONTROLLER . INSTALL FIREMAN'S SERVICE SO DLM IS IN COMPLIANCE WITH SECTION 3.10.12 OF APPENDIX K3 , APPLY FOR PERMIT AND BE TESTED IN F
#39059560H
Sep 7, 2022
IN VIOLATION
$312
Dec 14, 2021Elevators CLASS - 1
DLM IMPROPERLY INSTALLED ON THIS DEVICE . NO FIREMAN'S SERVICE PRESENT IN CONTROLLER . INSTALL FIREMAN'S SERVICE SO DLM IS IN COMPLIANCE WITH SECTION 3.10.12 OF APPENDIX K3 , FILE FOR APPLICATION AND HAVE IT IN
#39052805P
Jun 24, 2022
IN VIOLATION
$1,250
Jun 9, 2020Elevators CLASS - 1
CLASS 1 ITEM: MISSING DLM AS NOW REQUIRED BY CODE CLASS 2 ITEMS: INOPERATIVE REVERSE PHASE RELAY. SEAL HOIST MACHINE LEAKS. REPAIR MACHINE ROOM LIGHTING
#39023680H
Oct 21, 2020
IN VIOLATION
$1,250
Jun 28, 2019Elevators CLASS - 1
05M07CU. CEASE USE ITEM. DOOR ZONE RESTRICTOR IS MISSING THIS IS A SAFEY DEVICE TO ENSURE ELEVATOR PASSENGERS SAFETY. RMDY: PROVIDE RESTRICTOR TO RETURN DEVICE TO SERVICE CONTACT NYC.DOB AT 212-393-2435 AND
#38270367N
Feb 20, 2020
IN VIOLATION
$1,250
Nov 8, 2018Elevators CLASS - 2
100 M 07, 57 M 07, 40 O 09, 42 G 11, 100-M-07 PROVIDE READABLE PRINT IN MOTOR-ROOM, 57-M-07 PROVIDE FIRE EXTTINGUSHER TAG, 40-O-09 REMOVE NON-ELEVATOR EQUIPMENT FROM MOTOR.ROOM, 42-G-11 REPLACE IMPROPER FUSES
#38266476K
Jan 22, 2020
IN VIOLATION
$312
Nov 1, 2018Cranes and Derricks CLASS - 2
PARTIAL STOP WORK ORDER FOR SUSPENDED SCAFFOLD ISSUED PURSUANT TO 28- 208.2 AND POSTED AT PREMISES FAILED TO NOTIFY DEPARTMENT PRIOR TO INSTALLATION OF SUSPENDED SCAFFOLD. NOTE: OBSERVED SUSPENDED SCAFFOLD (ROP
#35354229Y
Jan 28, 2019
DEFAULT
$5,000
Oct 30, 2018Elevators CLASS - 1
CU05A10,42G11CU; 57M07,40O09. 05A10-CEASE USE ITEM. DOOR ZONE RESTRICTOR HAS BEEN RENDERED INOPERATIVE. THIS IS A SAFETY DEVICE TO ENSURE ELEVATOR PASSENGERS'SAFETY REPAIR RESTRICTOR AND CONTACT NYCDOB AT EIR
#38266196X
Sep 16, 2019
DEFAULT
$12,500
Oct 2, 2018Construction CLASS - 1
28-207.5 CEASE USE UNLAWFUL ACT. FAILURE TO COMPLY WITH A CEASE USE ORDER OF THE COMMISSIONER DEVICE 3P2446 WAS RETURNED TO SERVICE W/O A RE-INSPECTION BY HIS DEPT TO DETERMINE THAT THE CEASE USE CONDITION(S)
#38266179Y
Jan 16, 2020
IN VIOLATION
$2,500
Oct 1, 2018Elevators CLASS - 1
42G11,29D07,39Y02,39I07,70O02. 42B11-REPLACE ALL FUSES AND ATTACHED PROPERLY SIGNAGE FOR EACH FUSES; 39Y02-CLEAN TO OF CAR (OIL) 70O02-CLEAN PIT; 29D07-SECURE DOOR OPERATOR; 39I07-FIX TOP OF CAR LIGHTS.
#38265331P
Mar 25, 2019
IN VIOLATION
$1,250
Sep 19, 2018Elevators CLASS - 1
97X10 ENTIRE DEVICE INOPERATIVE REPAIR NO ELEVATOR FOR WEEKS.
#38259273P
Dec 10, 2018
IN VIOLATION
$1,250
Aug 3, 2018Elevators CLASS - 1
CEASE USE. 5I11,5B1,8J1,29L10,10E11,5B1. (5I)REPAIR OR REPLACE DOOR ZONE RESTRICTOR(SAFETY DEVICE).(5B)REDUCE GAP BETWEEN STRIKE POST & CAR DOOR.(8J)ADJUST CAR FLOOR TO LANDING SILL LEVEL.(29L)ADJUST RETIRING C
#38261512X
May 6, 2019
IN VIOLATION
$1,250
Mar 23, 2018Elevators CLASS - 1
05I11CU; 16B01,23L10,08V01. 05I-REPAIR INOPERTIVE DOOR ZONE LOCK; THI SIS A SAFTY DEVICE TO PREVENT THE ELEVTOR DOOR FROM OPENING BETWEEN FLOORS SO PEOPLE CANNOT ATTEMPT TO LEAVE LEVATOR WHEN STUCK BETWEEN
#38261503Y
Oct 17, 2018
IN VIOLATION
$5,000
Feb 7, 2018Elevators CLASS - 1
97X17:THE ONLY ELEVATOR IN BLDG(OUT OF SERVICE)UPON INSPECTIONTHE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITON AS PER 1RCNY 11-02.REM:RESTORE TO SERVICE IMMEDIATELY AND NOTIFY NYCDOB THE D
#38260618J
Jun 28, 2018
IN VIOLATION
$1,000
Jan 24, 2018Elevators CLASS - 1
CU-5X10; 3E10,39Y2,56Y2,70O2,71X10,16A10. 5X10-CAR DOOR RESTRICTOR IS INOPERATIVE (BOTH DEVICE); 3E10-NOISE BETWEEN 3 AND 4 FLOOR; 16A10- 2 FLOOR/SLAMMING.
#38260583Z
Jul 18, 2018
DEFAULT
$2,500
DOB (6)
IssuedViolationStatus
Jun 10, 2015ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR-FAILURE TO FILE CATEGORY 1 2014 INSPECTION/TEST
#02107
DOB VIOLATION - ACTIVE
Oct 8, 2010ELEVATOR ANNUAL INSPECTION / TEST

#04568
DOB VIOLATION - ACTIVE
Mar 21, 2008LOCAL LAW 10/81 - ELEVATOR

#03243
DOB VIOLATION - ACTIVE
Jan 31, 2005LOCAL LAW 62/91 - BOILERS

#10353
DOB VIOLATION - ACTIVE
Apr 21, 2004LOCAL LAW 10/81 - ELEVATOR

#03082
DOB VIOLATION - ACTIVE
Feb 10, 1997LOCAL LAW 62/91 - BOILERS

#31092
DOB VIOLATION - ACTIVE
DOB NOW Safety (6)
IssuedViolationStatus
Jun 10, 2015Elevators EVCAT1
Active
Oct 8, 2010Elevators VCAT1
Active
Mar 21, 2008Elevators LL1081
Active
Jan 31, 2005Boiler LL6291
Active
Apr 21, 2004Elevators LL1081
Active
Feb 10, 1997Boiler LL6291
Active
HPD (8) · C 0 · B 3 · A 5
IssuedClassViolationCorrect by
Aug 19, 2026AApt 6K · § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 6K, 6th STORYNov 22, 2026
Jun 1, 2026A§ 27-2014 ADM CODE AND DEPT. RULES AND REGULATIONS. SCRAPE AND REMOVE RUST SCALES AND PAINT WITH 2 COATS OF PAINT ALL COMPONENTS AT ALL BALCONIES ALL STORIES AT BUILDING FRONT AT FIRE ESCAPESep 4, 2026
Jun 1, 2026A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING. AT PUBLIC HALL, 6th STORYSep 4, 2026
Jun 1, 2026B§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 6th STORYJul 6, 2026
Jun 1, 2026B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 6th STORYJul 6, 2026
May 23, 2024AApt 6K · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS AND CEILING IN THE ENTIRE APARTMENT LOCATED AT APT 6K, 6th STORY, 1st APARTMENT FROM NORTH AT EASTAug 26, 2024
Aug 2, 2007BApt 5K · § 27-2018 ADM CODE ABATE THE NUISANCE CONSISTING OF VERMIN ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5K, 5th STORY, 1st APARTMENT FROM NORTH AT EASTSep 6, 2007
Jan 7, 1997AApt 5A · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT WALLS AND CEILINGS THRU OUT 5 STY CENTER EAST APT 5A , SECTION '' ''Apr 25, 1997

Issued in the last 120 days

DateSourceWhatNow
Aug 19, 2026HPD A§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 1st ROOM FROM EAST LOCATED AT APT 6K, 6th STORYOpen
Jul 22, 2026HPD C§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 5J, 5th STORY, 2nd APARTMENT FROM SOUTH AT WESTClosed

Check the agency records