Manhattan · Block 875 · Lot 67 · 10003

17 Gramercy Park South

6 floors · 18,458 sq ft · built 1938 · class H8 · owner of record: School Of Visual Arts Inc

2open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
43dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 43 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-12 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (2)
IssuedViolationHearingBalance
Oct 2, 2020Boilers CLASS - 2
GAS METER ROOM HAS HOLES AND NO FRESH AIR FROM THE OUTDOORS-FRESH AIR FAN NOT INTERLOCKED WITH BOILER; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF CORRECTION
#39029701P
Nov 19, 2020
IN VIOLATION
$0
Oct 2, 2020Boilers CLASS - 2
BOILER FLUE CLEANOUT PLATES HAVE DEFECTIVE GASKETS+BOLTS-FRESH AIR FAN NOT INTERLOCKED-STEAM CONTROL PIPING IS INCORRECT-LOWER REAR FRESH AIR LOUVER 1/2 CLOGGED; CORRECT VIOLATION AND SUBMIT THE CERTIFICATE OF
#39029702R
Nov 19, 2020
IN VIOLATION
$0
DOB (0)

None open.

DOB NOW Safety (0)

None open.

HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 9:25 AM ET. BBL 1008750067.