Bronx · Block 2790 · Lot 10 · 10457

1660 Topping Avenue

6 floors · 75 apartments · 69,600 sq ft · built 1942 · class D1 · owner of record: Parkash 1600 Llc

99open violations
$17,500ECB/OATH penalties owed
21HPD class C (immediately hazardous)
60dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 60 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 60 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 60 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 76 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 69,600 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 181 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 181 days
Annual filing
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

Sep 1, 2027
in 304 days
Registered through 2027-09-01
Energy audit and retro-commissioning (2030) Likely applies
Local Law 87 · Calendar year 2030
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2790). Agency page

Dec 31, 2030
in 1521 days
Next due 2030
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-01 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (21) · $17,500 owed
IssuedViolationHearingBalance
Oct 15, 2026Elevators CLASS - 2
CLASS1 ITEM: ELEVATOR IS STUCK ON 3 FLOOR: RTS FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, SERVICE ELEVATOR EQUIPMENT AS PER CODE BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF
#39207945K
Jan 15, 2027
PENDING
$625
Oct 15, 2026Elevators CLASS - 1
CLASS1 ITEM: BOTH ELEVATOR IS OUT OF SERVIVE: RTS FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, SERVICE ELEVATOR EQUIPMENT AS PER CODE BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT
#39207942P
Jan 15, 2027
PENDING
$1,250
Jan 22, 2026Elevators CLASS - 1
CLASS 1(CU):FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, DOOR LOCK MONITORING SYSTEM ON ELEVATOR INOPERATIVE,REPAIR AND TEST DEVIC
#39174812Z
Apr 3, 2026
IN VIOLATION
$1,250
Aug 6, 2025Elevators CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CLASS 2 ITEMS: 1) MAIN LINE BOX IN THE MOTOR ROOM NOT SECURE (OPENS WHEN POWER IS ON), SECURE. 2) PROVIDE CURRENT MAINTENANCE COMPANY INFORMATION IN THE MO
#39156230J
Feb 20, 2026
IN VIOLATION
$625
Aug 6, 2025Elevators CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE ONLY DEVICE IN THE SECTION OF THE BUILDING IS FOUND TO BE OUT OF SERVICE, CREATIN
#39156229M
Feb 20, 2026
IN VIOLATION
$6,250
Jul 28, 2025Construction CLASS - 2
WORK WITHOUT A PERMIT: AT THE TIME OF INSPECTION, OBSERVED AT APARTMENT 3A, RENOVATION WORK BEING DONE ON THE BATHROOM CEILING. DOB RECORDS INDICATE NO PERMIT ON FILE FOR THE WORK., OBTAIN ALL PERMITS; COMPLY W
#39155093H
Apr 20, 2026
IN VIOLATION
$1,250
Jul 28, 2025Construction CLASS - 2
FTM: ATOI, OBSERVED AT APT 1A A WINDOW MISSING. AT KITCHEN, LARGE PART OF WALL DAMAGED/ MISSING, EXPOSING BRICK AND GAS PIPES. HUGE HOLE IN THE CEILING REVEALING WOODEN JOISTS. AT APT 2A, A CLOSET NEXT TO KITCH
#39155094J
Apr 20, 2026
IN VIOLATION
$1,250
Jul 19, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #2 NORTH-CRACKED BRICK/MORTAR JOINTSBY WINDOWS, 6FL AT SETBACK AND GROUND LEVEL BY STAIRWA.-EXP #3 EAST-CR
#35718350K
Mar 17, 2026
IN VIOLATION
$5,000
Feb 5, 2025Elevators CLASS - 1
CLASS 1: CEASE USE: PLUNGER REMOVED FROM DOOR RESTRICTOR RENDERING IT INOPERATIVE INSTALL & RETEST (CU). DOOR LOCK MONITORING NOT INSTALLED IN THIS CONTROLLER. FILE PERMIT & INSTALL. THIS IS A RECURRING CONDITI
#39137572X
Apr 18, 2025
IN VIOLATION
$0
Feb 5, 2025Elevators CLASS - 1
CLASS 1: UPON INSPECTION FOUND DEVICE TO BE OUT OF SERVICE. THIS CREATES A SAFETY HAZZARD TO SPECIAL NEEDS RESIDENTS & FIRST RESPONDERS. RESTORE TO SERVICE REPAIR IMMEDIATELY AS PER 1RCNY 11-02. WHEN SERVICE RE
#39137571Y
Jun 27, 2025
IN VIOLATION
$0
Jan 23, 2025Construction CLASS - 1
FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: OBSERVED SEVERAL ITEMS ON FIRE ESCAPES SUCH AS TRASH, FLOWER POTS, CRATE AT EXPOSURE 2 NORTH ELEVAYION AND EXPOSURE 3, EAST ELEVATION. REMEDY: REMOVE OBSTR
#35689764K
Apr 4, 2025
IN VIOLATION
$0
Jan 23, 2025Construction CLASS - 1
FAILURE TO MAINTAIN EXTERIOR BUILDING FACADE AND APPURTENANCES. NOTE: OBSERVED AT EXPOSURE 1, WEST ELEVATION A CRACKED GLASS WINDOW ON 1ST FLOOR IN COURTYARD AND INADEQUATE SUPPORTED AC UNITS. AT EXPOSURE 2 NOR
#35689763Z
Apr 4, 2025
IN VIOLATION
$0
Apr 11, 2024Local Law CLASS - 2
FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALL AND APPURTENANCES REQUIRED BY 28-302.4 FOR CONTROL #912136. REMEDY: SUBMIT ACCEPTABLE REQU
#37027940K
Aug 23, 2024
IN VIOLATION
$0
Aug 9, 2023Construction CLASS - 2
FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR NOV 38208130H. REMEDY: FILE CERTIFICATE OF CORRECTION.
#39092183X
Nov 3, 2023
IN VIOLATION
$0
Aug 9, 2023Construction CLASS - 2
FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR NOV 38208711X. REMEDY: FILE CERTIFICATE OF CORRECTION.
#39092178L
Nov 3, 2023
IN VIOLATION
$0
Aug 9, 2023Construction CLASS - 2
FAILURE TO CERTIFY: FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR NOV 38231086P. REMEDY: FILE CERTIFICATE OF CORRECTION.
#39092171Z
Nov 3, 2023
IN VIOLATION
$0
Jun 28, 2023Elevators CLASS - 1
CEASE USE DOOR RESTRICTOR NOT WORKING CLASS 2 NO DOOR LOCK MONITORING MAINTANCE LOG RRPLACE CLOSE RELAY MACHINE LESKING PHONE NOT WORKING MISSING COVER ON DOOR OPERATOR
#39089404N
Sep 1, 2023
IN VIOLATION
$0
Jun 28, 2023Elevators CLASS - 2
DOOR OPERATOR COVER PHNE NOT WORKING NO DOOR LOCK MONUTORING UPDATE MAINTANCE LOG MACHINE LEAKING
#39089400X
Sep 1, 2023
IN VIOLATION
$0
Apr 11, 2014Elevators CLASS - 2
10B07/ 15M11/ 21L01/ 29Q03/ 35Q03/ 36Q03/ 39O02/ 40Q03/ 41T07/ 42D06/ 40O02/ 56Y13/ 57L11/ 67M07/ 68B07/ 70O02/ 71X10/ 71Q03/ 75L11/ 77B07/ 10-B-07 PROVIDE ADDTIONAL CAR DOOR GIBBS AS PER CODE EACH DOOR PANEL
#38231086P
May 30, 2014
IN VIOLATION
$0
Jan 25, 2010Elevators CLASS - 2
56/X/13,56/O/02,60/B/07,15/M/07-60-B-07-PROVIDE PROPER LIGHTING IN MOTOR ROOM
#38208711X
May 14, 2010
IN VIOLATION
$0
Dec 8, 2009Elevators CLASS - 2
08V10 56Y13 56O02 7OO02 39Y09 60B07 56F10 32H10 08V10 -ADJUST FLOOR STOPS WERE NEEDED 56Y13 -SEAL OIL LEAK HOISTMACHINE 56002 -CLEAN OIL FROM HOIST MACHINE AND BED PLATE & FL 58F10 HOIST MACHINE HAS BAD WORM GE
#38208130H
Apr 16, 2010
IN VIOLATION
$0
DOB (7)
IssuedViolationStatus
Feb 22, 2023NO REPORT AND / OR LATE FILING (FACADE)
FAILED TO FILE FISP CYCLE 9B TECHNICAL REPORT BY 2/21/2023
#00416
DOB VIOLATION - ACTIVE
Nov 14, 2016(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
#05176
DOB VIOLATION - ACTIVE
Nov 14, 2016(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2014 CAT 1 INSP/TST
#05175
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#04611
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#04610
DOB VIOLATION - ACTIVE
Aug 15, 2012ELEVATOR

#ACC101072
DOB VIOLATION - ACTIVE
Nov 30, 2007LOCAL LAW 11/98 - FACADE

#NRF44698
DOB VIOLATION - ACTIVE
DOB NOW Safety (29)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction
Active
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 2, 2026Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Report
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Feb 22, 2023Facades FISPNRF
CYCLE 9B NO REPORT FILED
Active
Nov 14, 2016Elevators ACC1
Active
Nov 14, 2016Elevators ACC1
Active
May 30, 2014Elevators ACC1
Active
May 30, 2014Elevators ACC1
Active
Aug 15, 2012Elevators E
Active
Aug 15, 2012Elevators E
Active
Nov 30, 2007Facades LL1198
CYCLE 6 NO REPORT FILED
Active
HPD (43) · C 21 · B 16 · A 6
IssuedClassViolationCorrect by
Oct 30, 2026BApt 4F · § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER THE CEILING IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH—
Oct 30, 2026BApt 4F · § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH—
Oct 30, 2026AApt 4F · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ.FT AT EAST WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH—
Oct 20, 2026C§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCKING DEVICE AT BUILDING ENTRANCE DOOR , 1st STORYOct 26, 2026
Oct 14, 2026BApt 5F · § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECNov 18, 2026
Oct 14, 2026AApt 5F · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHJan 17, 2027
Oct 14, 2026BApt 5F · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQFT AT EAST WALL, SOUTH WALL, AND AT CEILING IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHNov 18, 2026
Oct 14, 2026BApt 5F · § 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHNov 18, 2026
Oct 14, 2026CApt 5F · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHNov 9, 2026
Oct 14, 2026CApt 5F · § 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR IN THE ENTRANCE LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOct 28, 2026
Oct 14, 2026CApt 5F · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHNov 9, 2026
Oct 14, 2026BApt 5F · § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTINov 18, 2026
Oct 14, 2026AApt 5F · § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL FINISH AT BATH TUB IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHJan 17, 2027
Oct 14, 2026AApt 5F · § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHJan 17, 2027
May 28, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AND IT'S ASSEMBLY AT COMPACTOR CLOSET AT PUBLIC HALL, 6th STORY, SECTION ''SOUTH''Jul 2, 2026
May 28, 2026A§27-2104(B) HMC POST A PROPER NOTICE REGARDING RENT STABILIZATION LAW, IN A FORM APPROVED BY THE COMMISSIONER, IN A CONSPICUOUS LOCATION WITHIN THE COMMON AREA AT THE BUILDINGS ENTRANCE. FOR MORE INFORMATION ABOUT SIGNAGE REQUIREMENTS, PLEASE VISIT: HTTPS://WWW.NYC.GOV/SITE/HPD/SERVICES-AND-INFORMAAug 31, 2026
May 6, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH SET AND ASSEMBLIES AT COMPACTOR CLOSET DOOR AT PUBLIC HALL, 2ND STORY AT SOUTH SECTIONJun 10, 2026
Jul 3, 2025C§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HEAVY DUTY LOCK SET AT BUILDING ENTRANCE DOORJul 9, 2025
Jun 30, 2025CApt 2K · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 2K, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTHJul 26, 2025
Jun 30, 2025CApt 2K · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 2K, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTHJul 26, 2025
Jun 30, 2025BApt 2K · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 30 SQ FT AT NORTH EAST AND SOUTH WALLS IN THE 2nd ROOM FROM EAST LOCATED AT APT 2K, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTHAug 4, 2025
Jun 27, 2025C§ 27-2033 ADM CODE PROVIDE READY ACCESS TO BUILDINGS HEATING SYSTEM DOOR LOCKED AT BOILER ROOMJul 3, 2025
Aug 28, 2023CApt 6D · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 6D, 6th STORY, 2nd APARTMENT FROM WEST AT NORTHSep 23, 2023
Jul 19, 2023CApt 6D · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION AT NORTHAug 14, 2023
Mar 23, 2023BApt 3E · § 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM NORTH AT EASTApr 27, 2023
Mar 15, 2023C§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE INOPERATIVE HINGES AT COMPACTOR CHUTE DOOR AT NORTH WALL AT PUBLIC HALL, 4th STORY, SECTION AT SOUTHMar 29, 2023
Mar 15, 2023C§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE - INOPERATIVE HINGES AT COMPACTOR CHUTE DOOR AT NORTH WALL AT PUBLIC HALL, 3rd STORY, SECTION AT SOUTHMar 29, 2023
Mar 15, 2023C§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE INOPERATIVE HINGES AT COMPACTOR CHUTE DOOR AT NORTH WALL AT PUBLIC HALL, 2nd STORY, SECTION AT SOUTHMar 29, 2023
Mar 15, 2023C§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE - BULKHEAD DOOR MISALIGNED AT FRAME , SECTION AT SOUTHMar 29, 2023
Mar 15, 2023C§ 27-2005, 27-2007, 27-2041.1 HMC: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE AT BULKHEAD EXIT TO ROOF , SECTION AT NORTHMar 29, 2023
Mar 14, 2023BApt 2L · § 27-2056.7, 27-2056.17 AND 27-2056.8 ADM CODE - CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT LOCATED AT APT 2L, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ATApr 18, 2023
Mar 9, 2023CApt 2A · § 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.Mar 13, 2023
Jun 24, 2021BApt 1H · § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTJul 29, 2021
Jun 24, 2021BApt 1H · § 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE .. IN THE ENTIRE APARTMENT LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTJul 29, 2021
Jun 24, 2021CApt 1H · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTJul 20, 2021
Jun 24, 2021BApt 1H · § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTJul 29, 2021
Jun 24, 2021CApt 1H · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTJul 20, 2021
Jun 24, 2021BApt 1H · § 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WESTJul 29, 2021
Mar 18, 2021BApt 1H · § 27-2005, 2007 ADM CODE FIRE EGRESS DEFECTIVE. REMOVE OBSTRUCTING BARS OR UNLAWFUL GATES FROM AT LEAST 1 WINDOW OR PROVIDE APPROVED TYPE GATE IN THE ENTIRE APARTMENT LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''SOUTH''Apr 22, 2021
Mar 10, 2021A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING , NORTH AND SOUTH WALLS AT BULKHEAD , SECTION ''SOUTH''Jun 13, 2021
Mar 2, 2021C§ 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS.Mar 6, 2021
Mar 2, 2021CApt 6C · § 27-2056.8 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY SUBMITTING REQUIRED SUPPORTING DOCUMENTATION AND AFFIDAVITS FOR APARTMENT , IN THE ENTIRE APARTMENT LOCATED AT APT 6C, 6th STORY, 1st APARTMENT FROM WEST AT NORTHMar 6, 2021
Feb 25, 2021CApt 6B · § 27-2056.7 ADM CODE: CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES.Mar 1, 2021

Issued in the last 120 days

DateSourceWhatNow
Oct 30, 2026HPD B§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER THE CEILING IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTHOpen
Oct 30, 2026HPD B§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTHOpen
Oct 30, 2026HPD A§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ.FT AT EAST WALL IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTHOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of CorrectionOpen
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 20, 2026HPD C§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCKING DEVICE AT BUILDING ENTRANCE DOOR , 1st STORYOpen
Oct 15, 2026ECBElevators: CLASS1 ITEM: ELEVATOR IS STUCK ON 3 FLOOR: RTS FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, SERVICE ELEVATOR EQUIPMENT AS PER CODE BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OFOpen
Oct 15, 2026ECBElevators: CLASS1 ITEM: BOTH ELEVATOR IS OUT OF SERVIVE: RTS FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, SERVICE ELEVATOR EQUIPMENT AS PER CODE BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUTOpen
Oct 14, 2026HPD B§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECOpen
Oct 14, 2026HPD A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD B§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQFT AT EAST WALL, SOUTH WALL, AND AT CEILING IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD B§ 27-2026 ADM CODE REPAIR THE FLUSHING APPARATUS AND MAINTAIN SAME SO AS TO FLUSH EFFECTIVELY THE WATER CLOSET IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR IN THE ENTRANCE LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD B§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTIOpen
Oct 14, 2026HPD A§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE PORCELAIN ENAMEL FINISH AT BATH TUB IN THE BATHROOM LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 14, 2026HPD A§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR IN THE KITCHEN LOCATED AT APT 5F, 5th STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT NORTHOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test ReportOpen