Queens · Block 12341 · Lot 31 · 11434

166-01 116 Avenue

3 floors · 50,800 sq ft · built 1928 · class W1 · owner of record: Nyc Department Of Education

17open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
184dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 63 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 50,800 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 184 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 184 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 428 days
Next cycle year 2027
Energy audit and retro-commissioning (2031) Likely applies
Local Law 87 · Calendar year 2031
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 12341). Agency page

Dec 31, 2031
in 1889 days
Next due 2031
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-13 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (8)
IssuedViolationHearingBalance
May 28, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J).NOTED:INSTALLATION OFILLEGAL HARDWARE KICK STOPS ON FIRE RATED CLASSROOM DOORS SMOKE DOORS
#35732057M
Jul 15, 2026
POP/IN-VIO
$0
May 28, 2026Construction CLASS - 2
REISSUE ON ECB#35724682H FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:MISSING AND OR CRACKED WIRE MESH GLASS PANELS IN STAIR WELLS OR VISION PANELS IN STAIR I FROM 3RD TO 2ND FL AND TO 1ST FL IN
#35732054R
Jul 15, 2026
POP/IN-VIO
$0
May 28, 2026Construction CLASS - 2
REISSUE ON ECB#35724679R FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:EMERGENCY ILLUMINATED EXIT DISCHARGES AND EX
#35732056K
Jul 15, 2026
POP/IN-VIO
$0
May 8, 2026Construction CLASS - 2
REISSUE ON ECB#35724680Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NOTED:FIRE RATED CLASSROOM AND SMOKE DOORS NOT SELF-CLOSING DUE TO BINDING MISSING HARDWARE ON CLASSROOMS,326-2 DOORS 321,320,317,3
#35732055Z
Jul 15, 2026
POP/IN-VIO
$0
Sep 25, 2025Construction CLASS - 2
RE-ISSUE #35677482Y. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PERBC 1006.1; 27-381. NOTED: AT GYM, 2 EMERGENCY LIGHTS FOUND INOPERATION
#35724679R
Oct 22, 2025
POP/IN-VIO
$0
Sep 25, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORSMOKE DOORS DO NOT SELF-CLOSE. 3RD FLR-"MAIN GYM ENTRANCE, 2ND FLR-"STAIR E", "STAIR C", STAIR J". 1ST FLR"-"STAIR C". CLASSROOM DOORS DO NO
#35724680Y
Oct 22, 2025
POP/IN-VIO
$0
Sep 25, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: IN "STAIRCASE F" BETWEEM 3RD AND 2ND FLOOR THERE IS GLASS PANEL MISSING. 2ND FLR-RM #223. ALSO HAS GLASS PANEL MISSING ON ENTRANCE DOOR. REMEDY: REP
#35724682H
Oct 22, 2025
POP/IN-VIO
$0
Jun 28, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIORS PER BC 1006.1; 27-381. NOTED: AT GYM, 2 EMERGENCY EXIT LIGHTING FOUND INOPERATIONAL WHEN TESTED
#35677482Y
Sep 27, 2024
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (9)
IssuedViolationStatus
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Jan 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle D (premises is in Community District 12)
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 29, 2026, 12:34 AM ET. BBL 4123410031.

Look up another building