Manhattan · Block 1145 · Lot 7502 · 10023

160 West 74 Street

6 floors · 18,798 sq ft · built 1920 · class RA · owner of record: 74th St. Propco Llc

11open violations
$20,550ECB/OATH penalties owed
0HPD class C (immediately hazardous)
46dto Annual boiler inspection (1 boiler)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 46 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2022-09-09 (Accepted). Agency page

Dec 31, 2026
in 46 days
1 of 1 without an accepted 2026 report yet
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 7 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1142 days
Next cycle year 2029

Open violations

ECB / OATH (10) · $20,550 owed
IssuedViolationHearingBalance
Aug 6, 2026Construction CLASS - 1
ATOI OBSERVED IN BASEMENT GAS METER ROOM A LEAK ON THE RISER LEADING TO THE BUILDING , CON ED CAME TO SHUT OFF AND LOCK GAS WHICH SUPPLIED HOT WATER HEAT AND GAS DRYERS IN LAUNDRY ROOM, REPAIR AND/REPLACE
#39199451N
Oct 15, 2026
IN VIOLATION
$2,500
Aug 6, 2026Elevators CLASS - 1
CLASS 1 CEASE USE: DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELEVATOR CAR DOORS CAN BE OPENED WHEN THE CAR IS NOT WITHIN THE DESIGNATED DOOR ZONE, CREATING A
#39199416H
Oct 15, 2026
IN VIOLATION
$1,250
Aug 6, 2026Unknown CLASS - 1
ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN KITCHEN NEW 50 AMP ELECTRIC OVEN INSTALLED , THRU OUT THE BASEMENT NEW ELECTRIC HUNG HEATERS INSTALLED, NEW CONDUITS AND PANEL INSTALLED FOR ALL NEW WORK. CHECKED B
#39199457Y
Dec 3, 2026
PENDING
$2,500
Aug 6, 2026Unknown CLASS - 1
MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN THE BOILER RM THAT THE HUNG BOILER HAVE NO REMOTE SHUT DOWN AT THE POINT OF EGRESS. SHUT DOWN IS FOR ALL EMERGENCY USE M.C. 1006.8
#39199458X
Dec 3, 2026
PENDING
$1,600
Aug 6, 2026Construction CLASS - 1
ATOI OBSERVED THROUGHOUT THE BUILDING OBSTRUCTED SPRINKLER HEADS AND LACK OF SPRINKLER COVERAGE WHICH IS CONTRARY TO FGC 903.3.3, REPAIR AND/REPLACE
#39199450L
Dec 3, 2026
PENDING
$2,500
Aug 6, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN KITCHEN SJ CORD PASSING THRU THE CEILING FOR 40 AMP RECEPTACLE, ALSO THRU OUT SEVERAL M
#39199456M
Dec 3, 2026
PENDING
$1,600
Aug 6, 2026Unknown CLASS - 2
FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. OBSERVED THRU OUT BUILDING THE PANELS ON THE FLOORS 1-5 FOR THE SLEEPING AREAS / DORMS NO ARC BREAKERS PROTECTION INSTALLED. NE
#39199460P
Dec 3, 2026
PENDING
$2,400
Aug 6, 2026Plumbing CLASS - 1
ATOI OBSERVED IN BASEMENT HOT WATER HEATER BLOWOFF ARE TIED TOGETHER DRAINING OUT THROUGH A NEIGHBORING BATHROOM SINK TRAP AND ALSO NO FLOOR DRAIN INSIDE MECHANICAL ROOM WHICH IS CONTRARY TO MC 1004.6; 1004.6,
#39199452P
Dec 3, 2026
PENDING
$2,500
Aug 6, 2026Unknown CLASS - 1
ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE ELECTRICAL CLOSET IN THE BASEMENT THE STORAGE OF LADDERS , MOPS, BOXES, FAN BLOWER. ELECTRICAL CLOSETS / RMS SHALL BE D
#39199459H
Oct 15, 2026
IN VIOLATION
$1,200
Dec 3, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS IN LANDRYROOM AND GENERATOR ROOMS. UNPERMITTED PLASTIC
#39169131R
Sep 14, 2026
IN VIOLATION
$2,500
DOB (0)

None open.

DOB NOW Safety (5)
IssuedViolationStatus
Sep 9, 2026AEUHAZ FTC-AEU-HAZ
Active
Sep 9, 2026AEUHAZ FTC-AEU-HAZ
Active
Sep 9, 2026AEUHAZ FTC-AEU-HAZ
Active
Sep 9, 2026AEUHAZ FTC-AEU-HAZ
Active
Sep 9, 2026AEUHAZ FTC-AEU-HAZ
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Sep 9, 2026DOB SafetyAEUHAZ: Open
Sep 9, 2026DOB SafetyAEUHAZ: Open
Sep 9, 2026DOB SafetyAEUHAZ: Open
Sep 9, 2026DOB SafetyAEUHAZ: Open
Sep 9, 2026DOB SafetyAEUHAZ: Open
Aug 6, 2026ECBConstruction: ATOI OBSERVED IN BASEMENT GAS METER ROOM A LEAK ON THE RISER LEADING TO THE BUILDING , CON ED CAME TO SHUT OFF AND LOCK GAS WHICH SUPPLIED HOT WATER HEAT AND GAS DRYERS IN LAUNDRY ROOM, REPAIR AND/REPLACEClosed
Aug 6, 2026ECBElevators: CLASS 1 CEASE USE: DOOR ZONE RESTRICTOR DEVICE FOUND INOPERATIVE AS PER CODE ASME A17.1/CSA B44 - SECTION 2.26.5. ELEVATOR CAR DOORS CAN BE OPENED WHEN THE CAR IS NOT WITHIN THE DESIGNATED DOOR ZONE, CREATING AClosed
Aug 6, 2026ECBUnknown: ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN KITCHEN NEW 50 AMP ELECTRIC OVEN INSTALLED , THRU OUT THE BASEMENT NEW ELECTRIC HUNG HEATERS INSTALLED, NEW CONDUITS AND PANEL INSTALLED FOR ALL NEW WORK. CHECKED BOpen
Aug 6, 2026ECBUnknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN THE BOILER RM THAT THE HUNG BOILER HAVE NO REMOTE SHUT DOWN AT THE POINT OF EGRESS. SHUT DOWN IS FOR ALL EMERGENCY USE M.C. 1006.8Open
Aug 6, 2026ECBConstruction: ATOI OBSERVED THROUGHOUT THE BUILDING OBSTRUCTED SPRINKLER HEADS AND LACK OF SPRINKLER COVERAGE WHICH IS CONTRARY TO FGC 903.3.3, REPAIR AND/REPLACEOpen
Aug 6, 2026ECBUnknown: UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN KITCHEN SJ CORD PASSING THRU THE CEILING FOR 40 AMP RECEPTACLE, ALSO THRU OUT SEVERAL MOpen
Aug 6, 2026ECBUnknown: FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. OBSERVED THRU OUT BUILDING THE PANELS ON THE FLOORS 1-5 FOR THE SLEEPING AREAS / DORMS NO ARC BREAKERS PROTECTION INSTALLED. NEOpen
Aug 6, 2026ECBPlumbing: ATOI OBSERVED IN BASEMENT HOT WATER HEATER BLOWOFF ARE TIED TOGETHER DRAINING OUT THROUGH A NEIGHBORING BATHROOM SINK TRAP AND ALSO NO FLOOR DRAIN INSIDE MECHANICAL ROOM WHICH IS CONTRARY TO MC 1004.6; 1004.6,Open
Aug 6, 2026ECBUnknown: ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE ELECTRICAL CLOSET IN THE BASEMENT THE STORAGE OF LADDERS , MOPS, BOXES, FAN BLOWER. ELECTRICAL CLOSETS / RMS SHALL BE DClosed
Aug 6, 2026ECBElevators: CLASS 2: MAINTENANCE SERVICE LOG MISSING, FAILING TO PROVIDE REQUIRED RECORD OF PERIODIC MAINTENANCE AND TESTING. AS PER ASME A17.1 8.6. REMEDY: PROVIDE CURRENT MAINTENANCE SERVICE LOG AND MAINTAIN ACCURATE RECClosed

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 15, 2026, 12:30 PM ET. BBL 1011457502.