Manhattan · Block 1644 · Lot 51 · 10035

156 East 117 Street

6 floors · 31 apartments · 29,975 sq ft · built 1920 · class D7 · owner of record: 1875 Lex Llc

17open violations
$162,500ECB/OATH penalties owed
2HPD class C (immediately hazardous)
43dto Bedbug annual filing

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 43 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 59 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 29,975 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 164 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 164 days
Annual filing
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

Sep 1, 2027
in 287 days
Registered through 2027-09-01
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 11 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 408 days
Next cycle year 2027
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-05-29 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (12) · $162,500 owed
IssuedViolationHearingBalance
Oct 22, 2026Quality of Life CLASS - 1
PERMANENT DWELLING OFFERED/USED/CONVERTED FOR OTHER THAN PERMANENT-RESIDENTIAL PURPOSES. C/O #12692 INDICATES PREMISES TO BE LEGALLY APPROVED AS A CLASS A MULTIPLE DWELLING. NOW, UNIT 6E ON THE 6TH FLOOR IS USE
#35731273M
Dec 31, 2026
PENDING
$57,500
Oct 22, 2026Construction CLASS - 1
BC 907.2.8. FAILURE TO PROVIDE FIRE ALARM SYSTEM CLASS "J" FOR TRANSIENT USE AT APT. 6E. PREV ECB #35729287K. REMEDY: DISCONTINUE ILLEGAL USE.
#35731325P
Dec 31, 2026
PENDING
$6,250
Oct 22, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2, 27-954 FOR TRANSIENT USE AT UNIT 6E(6TH FLOOR. PREV ECB #35729286Z. REMEDY: DISCONTIN
#35731326R
Dec 31, 2026
PENDING
$6,250
Oct 22, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OR REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1(2008 CODE), 27-366, BC 1021.1(2014 CODE), BC 1006.3(2022 CODE). PREVIOUS ECB #3572
#35731274Y
Dec 31, 2026
PENDING
$6,250
Jul 23, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF SYSTEM OF AUTOMATIC SPRINKLERS WHEN REQUIRED PER BC 903.2 27-954 FOR TRANSIENTUSE AT APT 2C AT 2 FLOOR.PREVIOUS VIOLATION 35729140X REM:DISCONTINUE
#35729286Z
Apr 15, 2027
$6,250
Jul 23, 2026Construction CLASS - 1
BC 907.2.8 FAILURE TO PROVIDE A FIRE ALARM SYSTEM FOR TRANSIENT USE IN APT 2C AT 2 FLOOR.PREVIOUS VIOLATION 35729141H REM:DISCONTINUE ILLEGAL USE.
#35729287K
Apr 15, 2027
$6,250
Jul 23, 2026Quality of Life CLASS - 1
PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES DEPARTMENT BUILDINGS RECORDS INDICATES BUILDING TO BE LEGALLYAPPROVED AS A CLASS A MULTIPLE DWELLING NOW APARTMENT 112C ON 2 FLOOR
#35729284P
Apr 15, 2027
$57,500
Jul 23, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF REQUIREDNUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1;27-366 BC 1021.1 BC 1006.3 FOR TRANSIENT USE IN APARTMENT 2C AT 2 FLOOR.PREVIOUS VIO
#35729285R
Apr 15, 2027
$6,250
Jul 22, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR AS PER BC 1018.1(2008 CODE); 27-366; BC 1021.1(2014 CODE); BC 1006.3(2022 CODE). FOR TRANSIENT U
#35729139Z
Apr 22, 2027
$2,500
Jul 22, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING BUILDING IN CODE-COMPLIANT MANNER. FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC903.2 AND 27-95, FOR TRANSIENT USE AT APARTMENT #2A ON 2ND FLOOR. REME
#35729140X
Apr 22, 2027
$2,500
Jul 22, 2026Quality of Life CLASS - 2
PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES. DEPARTMENT OF BUILDINGS RECORDS INDICATES BUILDING TO BE LEGALLY APPROVED AS A CLASS "A" MULTIPLE DWELLING. NOW APARTMENT #2A ON 2
#35729138R
Apr 22, 2027
$2,500
Jul 22, 2026Construction CLASS - 1
BC 907.2.8. FAILURE TO PROVIDE A CLASS "J" FIRE ALARM SYSTEM FOR TRANSIENT USE AT APARTMENT #2A ON 2ND FLOOR. REMEDY: DISCONTINUE ILLEGAL OCCUPANCY.
#35729141H
Apr 22, 2027
$2,500
DOB (1)
IssuedViolationStatus
Apr 15, 1991CONSTRUCTION

#D4PR06
DOB VIOLATION - ACTIVE
DOB NOW Safety (0)

None open.

HPD (12) · C 2 · B 3 · A 7
IssuedClassViolationCorrect by
Apr 22, 2021CApt 3E · § 27-2005, 2007 ADM CODE ARRANGE AND MAKE SELF-CLOSING THE DOORS ... IN THE ENTRANCE LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTHMay 18, 2021
Apr 2, 2019A§ 53, 187, 231 M/D LAW AND DEPARTMENT RULES AND REGULATIONS. PROVIDE A SHOE PROPERLY SECURED TO BOTTOM OF STRING OF DROPLADDER DROP LADDER 3RD FROM NORTH AT BUILDING WEST AT FIRE ESCAPEJul 6, 2019
Sep 4, 2018A§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORYDec 8, 2018
Aug 13, 2014AApt 2B · SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE 2nd WINDOW FRAME FROM WEST AT NORTH WALL, 1st WINDOW FRAME FROM WEST AT NORTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHNov 16, 2014
Aug 13, 2014AApt 2B · SECTION 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION THE 1st RISER FROM EAST AT SOUTH WALL IN THE 4th ROOM FROM EAST AT SOUTH LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHNov 16, 2014
Aug 13, 2014AApt 2B · SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING IN THE 4th ROOM FROM EAST AT NORTH LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHNov 16, 2014
Aug 7, 2014AApt 2B · SECTION 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT ALL PEELING PAINT SURFACES IN THE 4th ROOM FROM EAST AT NORTH, THE 4th ROOM FROM EAST AT SOUTH, THE BATHROOM , THE FOYER LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHNov 10, 2014
Mar 20, 2014CApt 3F · SECTION 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 4th ROOM FROM NORTH LOCATED AT APT 3F, 3rd STORY, 1st APARTMENT FROM NORTH AT EASTMar 28, 2014
Jul 13, 2012BApt 2B · SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING AROUND RISERS IN THE BATHROOM LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHAug 17, 2012
Jul 13, 2012BApt 2B · SECTION 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR WEST WALL IN THE BATHROOM LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHAug 17, 2012
Jul 13, 2012BApt 2B · SECTION 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ESCUTCHEON PLATE AT RISER AT CEILING IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHAug 17, 2012
Jul 13, 2012AApt 2B · SECTION 27-2005 ADM CODE PAINT METAL IN ACCORDANCE WITH DEPT. REGULATION RISER IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 2B, 2nd STORY, 1st APARTMENT FROM WEST AT NORTHOct 16, 2012

Issued in the last 120 days

DateSourceWhatNow
Oct 22, 2026ECBQuality of Life: PERMANENT DWELLING OFFERED/USED/CONVERTED FOR OTHER THAN PERMANENT-RESIDENTIAL PURPOSES. C/O #12692 INDICATES PREMISES TO BE LEGALLY APPROVED AS A CLASS A MULTIPLE DWELLING. NOW, UNIT 6E ON THE 6TH FLOOR IS USEOpen
Oct 22, 2026ECBConstruction: BC 907.2.8. FAILURE TO PROVIDE FIRE ALARM SYSTEM CLASS "J" FOR TRANSIENT USE AT APT. 6E. PREV ECB #35729287K. REMEDY: DISCONTINUE ILLEGAL USE.Open
Oct 22, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.2, 27-954 FOR TRANSIENT USE AT UNIT 6E(6TH FLOOR. PREV ECB #35729286Z. REMEDY: DISCONTINOpen
Oct 22, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OR REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1(2008 CODE), 27-366, BC 1021.1(2014 CODE), BC 1006.3(2022 CODE). PREVIOUS ECB #3572Open
Jul 23, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.LACK OF SYSTEM OF AUTOMATIC SPRINKLERS WHEN REQUIRED PER BC 903.2 27-954 FOR TRANSIENTUSE AT APT 2C AT 2 FLOOR.PREVIOUS VIOLATION 35729140X REM:DISCONTINUEClosed
Jul 23, 2026ECBConstruction: BC 907.2.8 FAILURE TO PROVIDE A FIRE ALARM SYSTEM FOR TRANSIENT USE IN APT 2C AT 2 FLOOR.PREVIOUS VIOLATION 35729141H REM:DISCONTINUE ILLEGAL USE.Closed
Jul 23, 2026ECBQuality of Life: PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES DEPARTMENT BUILDINGS RECORDS INDICATES BUILDING TO BE LEGALLYAPPROVED AS A CLASS A MULTIPLE DWELLING NOW APARTMENT 112C ON 2 FLOORClosed
Jul 23, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.LACK OF REQUIREDNUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1;27-366 BC 1021.1 BC 1006.3 FOR TRANSIENT USE IN APARTMENT 2C AT 2 FLOOR.PREVIOUS VIOClosed
Jul 22, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR AS PER BC 1018.1(2008 CODE); 27-366; BC 1021.1(2014 CODE); BC 1006.3(2022 CODE). FOR TRANSIENT UClosed
Jul 22, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING BUILDING IN CODE-COMPLIANT MANNER. FAILURE TO PROVIDE A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC903.2 AND 27-95, FOR TRANSIENT USE AT APARTMENT #2A ON 2ND FLOOR. REMEClosed
Jul 22, 2026ECBQuality of Life: PERMANENT DWELLING USED/CONVERTED FOR OTHER THAN PERMANENT RESIDENTIALPURPOSES. DEPARTMENT OF BUILDINGS RECORDS INDICATES BUILDING TO BE LEGALLY APPROVED AS A CLASS "A" MULTIPLE DWELLING. NOW APARTMENT #2A ON 2Closed
Jul 22, 2026ECBConstruction: BC 907.2.8. FAILURE TO PROVIDE A CLASS "J" FIRE ALARM SYSTEM FOR TRANSIENT USE AT APARTMENT #2A ON 2ND FLOOR. REMEDY: DISCONTINUE ILLEGAL OCCUPANCY.Closed

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 11:18 AM ET. BBL 1016440051.