Bronx · Block 2821 · Lot 1 · 10457

1500 Grand Concourse

6 floors · 96 apartments · 96,990 sq ft · built 1935 · class D1 · owner of record: 1500 Grand Concourseowners Llc

396open violations
$104,999ECB/OATH penalties owed
76HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 2026-09-01
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 68 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 68 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 68 days
Annual
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 84 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 96,990 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 189 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 189 days
Annual filing
Energy audit and retro-commissioning (2031) Likely applies
Local Law 87 · Calendar year 2031
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2821). Agency page

Dec 31, 2031
in 1894 days
Next due 2031
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-01-20 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (35) · $104,999 owed
IssuedViolationHearingBalance
Sep 15, 2026Elevators CLASS - 2
CLASS 2 ITEM: IN-CAR COMMUNICATION IS NOT CONNECTED TO A CONTINUOUSLY STAFFED LOCATION, AS REQUIRED BY NYC BUILDING CODE ASME A17.1 2.27.1.1.
#39204116J
Nov 20, 2026
PENDING
$625
Aug 14, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BLDG EXTERIOR FACADE AND APPURTENANCES. NOTE: AT TIME OF INSPECTION, I OBSERVED EXP #1 WEST(1) BOWING LINTELS MULTI LOC AT DEFECTIVE WINDOW SILLS MULTI LOC.-EXP #2 NORTH AND EXP #3 EAST-CRAC
#35730909Y
Oct 30, 2026
PENDING
$5,000
Jun 24, 2026Unknown CLASS - 1
ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN BASEMENT LAUNDRY RM ELECTRICAL PANEL, RECEPTACLES FOR WASHING MACHINE AND DRYERS ALSO THRU OUT THE B SIDE OF BUILDING SMOKE ALARMS INSTALLED NO PERMIT ON FILE. CHEC
#39193631N
Sep 4, 2026
DEFAULT
$2,530
Jun 24, 2026Unknown CLASS - 2
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN APT 55B THE RECEPTACLE IN LIVING RM HAS THE PRESENT OF WATER INSIDE CAUSING IT NOT TO W
#39193632P
Sep 4, 2026
DEFAULT
$830
Jun 24, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ATOI OBSERVED VERTICAL CRACK IN LAUNDRY ROOM, EXPO #3 FACADE CRACKS WITH MISSING MORTAR JOINTS, DAMAGED AND DETERIORATED, LOOSE BRICKS ABOVE THE LIN
#35667421L
Sep 4, 2026
DEFAULT
$1,280
Jun 24, 2026Unknown CLASS - 1
FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED THE SIDEWALK SHED HAS NO DEDICATED GROUND SHED SHALL BE GROUNDED AT ALL TIME PREVENTING ELECTRICAL SHOCK TO PUBLIC. NEC CODE 590.9/ B.C 3307, PROVIDE GROUNDING
#39193630L
Sep 4, 2026
DEFAULT
$4,830
Jun 24, 2026Construction CLASS - 1
ATOI OBSERVED LAUNDRY ROOM IN BASEMENT WITH NO SPRINKLER SYSTEM INSTALLED PER BC 28-301.1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 90
#39193649L
Sep 4, 2026
DEFAULT
$2,530
Jun 24, 2026Construction CLASS - 1
ATOI OBSERVED LAUNDRY ROOM WHICH HAS NO PERMIT ON FILE PER PC PC 106.1 - PLUMBING WORK, INCLUDING WATER HEATER INSTALLATIONS AND PLUMBING SYSTEM ALTERATIONS, REQUIRES PERMITS., OBTAIN PERMIT
#39193650Z
Sep 4, 2026
DEFAULT
$2,530
Jun 22, 2026Elevators CLASS - 2
CLASS 2: NO EMERGENCY COMMUNICATION DEVICE/TELEPHONE PROVIDED IN ELEVATOR CAR, IN VIOLATION OF ASME A17.1-2013 2.27.1.1 AND 8.6.1.2.1.
#39193221K
Sep 4, 2026
DEFAULT
$655
Oct 9, 2025Construction CLASS - 2
PEDESTRIAN PROTECTION DOES NOT MEET CODE SPECIFICATIONS. OBSERVED MISSING PARAPET PANELS ON SIDEWALK SHED. REMEDY: COMPLY TO CODE SPECIFICATION.
#35718265X
Dec 19, 2025
DEFAULT
$10,000
May 23, 2025Construction CLASS - 2
AT TIME OF INSPECTION OF A 6-STORY OCCUPIED BUILDING, I OBSERVED NO SIGN OF CONSTRUCTION ACTIVITIES SIDEWALK SHED ERECTED AROUND BUILDING, DURING MY INSPECTION I NOTICED SIDEWALK SHED HAS MISSING INFORMATION PA
#39540587Z
Aug 1, 2025
DEFAULT
$6,250
May 23, 2025Construction CLASS - 2
AT TIME OF INSPECTION OF A 6-STORY BUILDING, I OBSERVED SIDEWALK SHED ERECTED EXP#1 AND 4 NOT MAINTAIN AS PER CODE BC3307.6.4.10 FOUNDING.ALSO I OBSERVED AT EXP#4 SIDEWALK SHED PARAPET PANEL LOOSING AND MISSING
#39540588K
Aug 1, 2025
DEFAULT
$10,000
May 23, 2025Unknown CLASS - 2
AT TIME OF INSPECTION OF A 6-STORY OCCUPIED BUILDING SIDEWALK SHED ERECTED AROUND BUILDING.UPON REVIEWING DOB NOW AND BIS SYSTEM SHOW PERMIT EXPIRED SINCE 05/05/2025 AND HAS NOT RENEW AS PER CODE REQUIRED.PERMI
#39540586R
Aug 1, 2025
DEFAULT
$6,250
Aug 26, 2024Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS#39054149P ISSUED ON 1/12/2022,AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2).AN ACCEPTABLE CERTIFICA
#37029070P
Nov 29, 2024
DEFAULT
$3,125
Aug 26, 2024Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS#35634164Z ISSUED ON 10/6/2021,AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2).AN ACCEPTABLE CERTIFICA
#37028999J
Nov 29, 2024
DEFAULT
$3,125
Jun 21, 2024Elevators CLASS - 1
THIS IS A RECURRING ISSUE; THE ONLY EELVATOR IN THE SECTION OF THE BUILDING IS OUT OF SERVICE, AFFECTING RESIDENTS CAUSING A HAZARDOUS CONDITION TO HUMAN LIFE
#39117389J
Nov 1, 2024
IN VIOLATION
$3,125
May 23, 2024Elevators CLASS - 1
THIS IS A RECURRING ISSUE WITH THE ELEVATOR, ELEVATOR IS CURRENTLY OUT OF SERVICE, THIS IS THE ONLY ELEVATOR THAT ADDRESS THIS PART OF THE BUILDING CAUSING A HAZARDOUS CONDITION FOR RESIDENTS.
#39115161Y
Aug 2, 2024
DEFAULT
$12,500
May 15, 2024Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS #35547820M ISSUED ON 5/3/2021, AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1 RCNY 102-01(D)(2). AN ACCEPTABLE CERTIF
#37028372X
Aug 16, 2024
DEFAULT
$3,125
May 6, 2024Elevators CLASS - 1
ONLY ELEVATOR IN BUILDING SECTION OUT OF SERVICE. THIS CONDITION AFFECTS NUMEROUS TENANTS, INCLUDING THOSE WITH SPECIAL NEEDS, THEREBY CREATING A CONDITION DANGEROUS TO HUMAN LIFE.
#39113571H
Aug 23, 2024
DEFAULT
$6,250
May 1, 2024Elevators CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11
#39113153P
Jul 5, 2024
DEFAULT
$12,500
Mar 19, 2024Construction CLASS - 2
FAILURE TO COMPLY WITH COMMISSIONER'S ORDER CONTAINED IN SUMMONS#39037808P ISSUED ON 3/17/2021,AND FAILURE TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28.201.1 AND 1RCNY 102-01(D)(2).AN ACCEPTABLE CERTIFICA
#37027145L
Aug 2, 2024
IN VIOLATION
$0
Jan 22, 2024Boilers CLASS - 1
CEASE USE ROCKMILLS MP-175DUE TO HAZARDOUS CONDITION, WATER LEAKING OUT OF FRONT AND REAR DOORS OF BOILER, DO NOT OPERATE BOILER UNTIL ALL HAZARDOUS CONDITIONS ARE IMMEDIATELY CORRECTED AND DOB IS NOTIFIED TO R
#39103955H
Jul 21, 2025
IN VIOLATION
$1,250
Dec 8, 2023Elevators CLASS - 2
ELEVATOR CURRENTLT OUT OF SERVICE WITH DOORS OPEN IN THE LOBBY; RESTORE TO SERVICE
#39100976N
Feb 16, 2024
DEFAULT
$3,125
Jul 19, 2022Unknown CLASS - 2
I OBSERVED THROUGH THE BUILDING ON EVERY FLOOR, HALLWAY LIGHT FIXTURES THAT ARE MISSING THE GLASS GLOBE THAT COVERS THE BALLASTS, BULBS, AND WIRING., COMPLY WITH EC; COMPLY WITH ELECTRICAL CODE
#39066244L
Dec 9, 2022
IN VIOLATION
$30
Apr 16, 2022Elevators CLASS - 1
CLASS 1 VIOLATION ISSUED RTS RECURRING, / UPON INSPECTION OF DEVICE IT WAS FOUND TO BE OUT-OF-SERVICE AS PER 1 RCNY 11-02, THE DEVICE PROVIDE SERVICE TO A SIX STORY BUILDING, REMEDY; RESTORE TO SERVICE IMMEDIAT
#39060396N
Aug 5, 2022
IN VIOLATION
$1,563
Mar 30, 2022Boilers CLASS - 2
FOUND EXPOSED WIRES AT CONTROLS, BOILER DOORS FRONT AND REAR NEED TO BE RESEALED, SIGHT GLASS MISSING ON REAR CHAMBER DOOR, BURNER NEEDS TO BE SERVICED, SMOKES DURING MODULATION INTO HIGH FIRE.
#39059148X
Jun 24, 2022
IN VIOLATION
$1,563
Feb 23, 2022Elevators CLASS - 1
OUT OF SERVICE
#39056841K
Jun 3, 2022
IN VIOLATION
$0
Feb 7, 2022Elevators CLASS - 1
UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE. THEY ARE THREE ELEVATOR IN THIS BUILDING. BUT THE ONLY CONNECTION IN THE LOBBY AND BASEMENT. RESTORE TO SERVICE IMMEDIATELY AND CONTACT NYCDOB. AT EIR@BUILDINGS.
#39055671M
Apr 29, 2022
IN VIOLATION
$0
Jan 20, 2022Unknown CLASS - 2
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS, MATERIALS,DEVICES APPLIANCES OR WIRING IN USE.1FL SIDE IN FRONT OF ELEVATOR FIXTURE MISSING CANOPY FIXTURE SOCKETS HANGING&DANGLING COMPLY W/EC CODE
#35644634N
Apr 15, 2022
ADMIT/IN-VIO
$0
Jan 12, 2022Boilers CLASS - 2
FOUND EXPOSED WIRING AT CONTROL, FRONT AND REAR BOILER DOORS NEED TO BE RESEALED, BURNER NEEDS TO BE SERVICED, BOILER ROOM DOOR NOT SELF CLOSING.
#39054149P
Mar 4, 2022
STIPULATION/IN-VIO
$8
Oct 6, 2021Unknown CLASS - 2
UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE.TEMPORARY LIGHT FIXTURE TIED INTO EXISTING BRANCH CIRCUIT TO REPLACE DEFECTIVE LIGHT FIXTURE ON A SIDE O
#35634164Z
Jan 7, 2022
STIPULATION/IN-VIO
$400
May 3, 2021Unknown CLASS - 2
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. DEFECTIVE LIGHT FIXTURE ON THE 1ST FL AT THE FRONT OF THE "A" ELEVATOR,THAT LIGHT FIXTURE LIGHT BULBS A
#35547820M
Jul 16, 2021
STIPULATION/IN-VIO
$0
Mar 17, 2021Boilers CLASS - 2
ATOI FOUND CORRODED WATER COLUMN,, BODY DRAINS ON SAFETY RELIEF VALVES MISSING, DISCHARGE PIPES NOT PROPERLY SUPPORTED, FLUE PIPE OUTSIDE OF BOILER ROOM NOT FIRE RATED, BOILER ROOM DOOR DOESN'T OPEN TO EGRESS,
#39037808P
May 7, 2021
STIPULATION/IN-VIO
$0
Oct 20, 2020Unknown CLASS - 2
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENTS, APPARATUS, MATERIALS, DEVICES, APPLIANCES, OR WIRING IN USE. TWO DEFECTIVE LIGHT FIXTURES HANGING ON THE FIRST FLOOR HALLWAY. REMEDY: COMPLY WITH EC CODE
#35461093H
Dec 18, 2020
DEFAULT
$0
Jan 18, 2017Boilers CLASS - 2
28B, B254
#32086593N
Mar 17, 2017
STIPULATION/IN-VIO
$0
DOB (13)
IssuedViolationStatus
Jun 30, 2026CONSTRUCTION
FAILURE TO MAINTAIN BUILDING IN A CODE COMPLAINT MANNER. OBSERVED STEP CRACKS DAMAGED MORTAR JOINTS SPALLED/SPALLING STONE WORK DAMAGED WINDOW LINTELS THROUGHOUT ON EXPOSURE 1 AND 4. REMEDY: REPAIR AND/OR REPLACE
#SR20402XN
DOB VIOLATION - ACTIVE
Oct 9, 2025CONSTRUCTION
FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. OBSERVED STEPCRACKS, DAMAGE MORTAR JOINTS IN MULTIPLE LOCATIONS ON EXPOSURE 1 AND 4. ALSO OBSERVED SPALLED/SPALLING STONE WORK, DAMAGED WINDOW LINTELS ON EXPOSURE 1 IN MULTIPLE LOCATIONS
#SR20403XN
DOB VIOLATION - ACTIVE
Jun 30, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
#30508
DOB VIOLATION - ACTIVE
Apr 25, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
#10023
DOB VIOLATION - ACTIVE
May 2, 2015FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00610
DOB VIOLATION - ACTIVE
Jun 6, 2014FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00529
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#04621
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#04620
DOB VIOLATION - ACTIVE
May 30, 2014(OTHER BLDGS TYPES) - ELEVATOR AFFIRMATION OF CORRECTION
VIO ISSUED TO ELEVATOR - FAIL TO CORRECT DEFECTS ON 2012 CAT 1 INSP/TST
#04622
DOB VIOLATION - ACTIVE
Jun 3, 2013FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#00572
DOB VIOLATION - ACTIVE
May 3, 2012FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#01277
DOB VIOLATION - ACTIVE
Jan 1, 2012FAILURE TO BENCHMARK
FAILURE TO FILE BENCHMARKING REPORT OF ENERGY USE AS PER AD. CODE SEC. 28-309.4
#01093
DOB VIOLATION - ACTIVE
Jan 1, 2009LOCAL LAW 62/91 - BOILERS

#09353
DOB VIOLATION - ACTIVE
DOB NOW Safety (28)
IssuedViolationStatus
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Sep 11, 2024Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Report
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
Jun 30, 2023Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2021 EXTERNAL LOW PRESSURE INSPECTION
Active
Apr 25, 2023Boiler LBLVIO
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2022 INSPECTION REPORT
Active
May 2, 2015Benchmarking - LL84 FTF-EN-BENCH
Active
Jun 6, 2014Benchmarking - LL84 FTF-EN-BENCH
Active
May 30, 2014Elevators ACC1
Active
May 30, 2014Elevators ACC1
Active
May 30, 2014Elevators ACC1
Active
Jun 3, 2013Benchmarking - LL84 FTF-EN-BENCH
Active
May 3, 2012Benchmarking - LL84 FTF-EN-BENCH
Active
Jan 1, 2012Benchmarking - LL84 FTF-EN-BENCH
Active
Jan 1, 2009Boiler LL6291
Active
HPD (323) · C 76 · B 170 · A 77
IssuedClassViolationCorrect by
Oct 22, 2026BApt 55C · § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 55C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECT—
Oct 22, 2026CApt 55C · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 55C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''C''—
Oct 20, 2026CApt 64B · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 64B, 6th STORY, 1st APARTMENT FROM NORTH AT EASTNov 15, 2026
Oct 9, 2026A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT SECTION A AT PUBLIC HALL, 6th STORYJan 12, 2027
Oct 9, 2026B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AT SECTION A AT PUBLIC HALL, 6th STORYNov 13, 2026
Oct 9, 2026B§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLEXIGLASS INSTALLED AT BUILDING ENTRANCE DOOR , 1st STORYNov 13, 2026
Oct 9, 2026B§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING AT SECTION A AT PUBLIC HALL, 6th STORYNov 13, 2026
Oct 9, 2026B§ 27-2005 ADM CODE PROVIDE APPROVED GLASS IN THE PLACE OF BUILDING ENTRANCE DOOR , 1st STORYNov 13, 2026
Oct 9, 2026B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AT SECTION B AT PUBLIC HALL, 1st STORYNov 13, 2026
Oct 9, 2026B§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT SECTION B AT PUBLIC HALL, 1st STORYNov 13, 2026
Oct 9, 2026A§27-2104(B) HMC POST A PROPER NOTICE REGARDING RENT STABILIZATION LAW, IN A FORM APPROVED BY THE COMMISSIONER, IN A CONSPICUOUS LOCATION WITHIN THE COMMON AREA AT THE BUILDINGS ENTRANCE. FOR MORE INFORMATION ABOUT SIGNAGE REQUIREMENTS, PLEASE VISIT: HTTPS://WWW.NYC.GOV/SITE/HPD/SERVICES-AND-INFORMAJan 12, 2027
Oct 9, 2026A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 1st STORYJan 12, 2027
Oct 9, 2026B§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL OUTLET SAFETY COVERS AT ALL WALLS AT PUBLIC HALL, 1st STORYNov 13, 2026
Oct 2, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT EAST AT INTERMEDIATE LANDING AT PUBLIC HALL, 3rd STORY, SECTION ''C''Nov 6, 2026
Oct 2, 2026C§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WIRED GLASS AT MIDDLE SASHWINDOW AT SOUTH WALL AT INTERMEDIATE LANDING AT PUBLIC HALL, 4th STORY, SECTION ''A''Oct 8, 2026
Oct 2, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT SOUTH AT INTERMEDIATE LANDING AT PUBLIC HALL, 4th STORY, SECTION ''A''Nov 6, 2026
Oct 2, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT SOUTH AT INTERMEDIATE LANDING AT PUBLIC HALL, 5th STORY, SECTION ''A''Nov 6, 2026
Oct 2, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT EAST AT INTERMEDIATE LANDING AT PUBLIC HALL, 1st STORY, SECTION ''C''Nov 6, 2026
Oct 2, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT EAST AT INTERMEDIATE LANDING AT PUBLIC HALL, 2nd STORY, SECTION ''C''Nov 6, 2026
Sep 24, 2026BApt K · § 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BASE CABINET AT SINK IN THE KITCHEN LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 29, 2026
Sep 24, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HEAVY DUTY LOCK ASSEMBLY AT VESTIBULE DOOROct 29, 2026
Sep 24, 2026BApt K · § 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT NORTH WALL, AND AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 29, 2026
Sep 24, 2026BApt K · § 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK ASSEMBLY AT DOOR IN THE ENTRANCE LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 29, 2026
Sep 24, 2026BApt K · § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WALL CABINET AT WEST WALL IN THE KITCHEN LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 29, 2026
Sep 24, 2026CApt K · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 20, 2026
Sep 24, 2026BApt K · § 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT WEST WALL IN THE BATHROOM LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 29, 2026
Sep 24, 2026CApt K · HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOct 20, 2026
Sep 14, 2026A§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALLDec 18, 2026
Aug 31, 2026B§ 27-2005 ADM CODE PROVIDE SECURITY IN AN EVENT OF POWER OUTAGE NY MEANS OF HEAVY DUTY LOCK AND ASSEMBLY AT VESTIBLE DOOR , 1st STORY, SECTION ''SOUTH''Oct 5, 2026
Aug 31, 2026A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''SOUTH''Dec 4, 2026
Aug 31, 2026C§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING TWO MOTION ELECTRO MAGNETIC LOCKING DEVICE INSTALLED AT VESTIBLE DOOR , 1st STORY, SECTION ''SOUTH''Sep 6, 2026
Aug 31, 2026B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''SOUTH''Oct 5, 2026
Aug 31, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT DOOR AT ROOF AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''SOUTH''Sep 14, 2026
Aug 11, 2026AApt C61 · § 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT THE CEILING IN THE BATHROOM LOCATED AT APT C61, 2nd STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION ''C''Nov 14, 2026
Aug 6, 2026BApt B62 · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQFT AT EAST AND SOUTH WALL AT SOUTH CLOSET IN THE FOYER LOCATED AT APT B62, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''CENTER'' ORIGINAL VIOLATION 18769345 ISSUED 07-APR-26 HAS BEEN UPGRADSep 10, 2026
Jul 29, 2026AApt C55 · § 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ FT AT CEILING IN THE BATHROOM LOCATED AT APT C55, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''C'', AT SOUTHNov 1, 2026
Jul 29, 2026BApt C55 · § 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT C55, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''C'', AT SOUTHSep 2, 2026
Jul 29, 2026BApt C55 · § 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE DOOR KNOB IN THE ENTRANCE LOCATED AT APT C55, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''C'', AT SOUTHSep 2, 2026
Jul 29, 2026A§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQ. FT AT BULKHEAD NORTH WALLAND CEILING ...BUILDING SEC CNov 1, 2026
Jul 29, 2026BApt C55 · § 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT C55, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTSep 2, 2026
Jul 29, 2026BApt C55 · § 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT C55, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SESep 2, 2026
Jul 27, 2026A§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORYOct 30, 2026
Jul 27, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BUILDING ENTRANCE DOOR FROM VESTIBULE TO PUBLIC HALL AT PUBLIC HALL, 1st STORYAug 10, 2026
Jul 27, 2026B§ 27-2005 ADM CODE PROVIDE CHILD SAFETY COVERS AT ELECTRICAL OUTLETS AT ALL WALLS AT PUBLIC HALL, 1st STORYAug 31, 2026
Jul 27, 2026C§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING INFORMATION AT PUBLIC HALL, 1st STORYAug 2, 2026
Jul 27, 2026A§27-2104(B) HMC POST A PROPER NOTICE REGARDING RENT STABILIZATION LAW, IN A FORM APPROVED BY THE COMMISSIONER, IN A CONSPICUOUS LOCATION WITHIN THE COMMON AREA AT THE BUILDINGS ENTRANCE. FOR MORE INFORMATION ABOUT SIGNAGE REQUIREMENTS, PLEASE VISIT: HTTPS://WWW.NYC.GOV/SITE/HPD/SERVICES-AND-INFORMAOct 30, 2026
Jul 27, 2026A§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORYOct 30, 2026
Jul 24, 2026A§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER., 1st STORYOct 27, 2026
Jul 24, 2026B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT THE CEILING, SOUTH WALL AND EAST WALL AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''C''Aug 28, 2026
Jul 24, 2026A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT THE CEILING, SOUTH WALL AND EAST WALL AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''C''Oct 27, 2026
Jul 24, 2026B§ 27-2005 ADM CODE PROVIDE UBLOCKABLE SLIDE BOLT OR HOOK INSTALLED ON DOOR THAT ALLOWS RE-ENTRY FROM ROOF TO PUBLIC HALL AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''C''Aug 28, 2026
Jul 24, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND ITS ASSEMBLY AT BULKHEAD DOOR AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''C''Aug 28, 2026
Jul 24, 2026C§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE 4TH 5TH AND 6TH BROKEN MARBLE TREAD UP FROM BOTTOM CAUSING A TRIP HAZARD AT PUBLIC HALL STAIRS, 6th STORY, SECTION ''B''Jul 30, 2026
Jul 24, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BULKHEAD DOOR AT 2nd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''B''Aug 7, 2026
Jul 24, 2026C§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM SIGN MISSING , 1st STORYJul 30, 2026
Jul 24, 2026B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LATCH AND ITS ASSEMBLIES AT BULKHEAD DOOR AT 2nd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''B''Aug 28, 2026
Jul 24, 2026B§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT THE CEILING, SOUTH WALL AND EAST WALL AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''C''Aug 28, 2026
Jul 24, 2026C§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT BULKHEAD DOOR AT 3rd PUBLIC HALL BULKHEAD FROM NORTH, 6th STORY, SECTION ''C''Aug 7, 2026
Jul 24, 2026A§27-2045(B)(5) HMC, § 12-01 RCNY POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAILBOX SIGN MISSING , 1st STORYOct 27, 2026
Jul 24, 2026A§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING., 1st STORYOct 27, 2026

Showing 60 of 323. Full list on the agency site.

Issued in the last 120 days

DateSourceWhatNow
Oct 22, 2026HPD B§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 55C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTOpen
Oct 22, 2026HPD CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 55C, 5th STORY, 1st APARTMENT FROM WEST AT NORTH , SECTION ''C''Open
Oct 20, 2026HPD CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 64B, 6th STORY, 1st APARTMENT FROM NORTH AT EASTOpen
Oct 9, 2026HPD A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT SECTION A AT PUBLIC HALL, 6th STORYOpen
Oct 9, 2026HPD B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AT SECTION A AT PUBLIC HALL, 6th STORYOpen
Oct 9, 2026HPD B§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF PLEXIGLASS INSTALLED AT BUILDING ENTRANCE DOOR , 1st STORYOpen
Oct 9, 2026HPD B§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING AT SECTION A AT PUBLIC HALL, 6th STORYOpen
Oct 9, 2026HPD B§ 27-2005 ADM CODE PROVIDE APPROVED GLASS IN THE PLACE OF BUILDING ENTRANCE DOOR , 1st STORYOpen
Oct 9, 2026HPD B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIALS AT CEILING AT SECTION B AT PUBLIC HALL, 1st STORYOpen
Oct 9, 2026HPD B§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT SECTION B AT PUBLIC HALL, 1st STORYOpen
Oct 9, 2026HPD A§27-2104(B) HMC POST A PROPER NOTICE REGARDING RENT STABILIZATION LAW, IN A FORM APPROVED BY THE COMMISSIONER, IN A CONSPICUOUS LOCATION WITHIN THE COMMON AREA AT THE BUILDINGS ENTRANCE. FOR MORE INFORMATION ABOUT SIGNAGE REQUIREMENTS, PLEASE VISIT: HTTPS://WWW.NYC.GOV/SITE/HPD/SERVICES-AND-INFORMAOpen
Oct 9, 2026HPD A§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 1st STORYOpen
Oct 9, 2026HPD B§ 27-2005 ADM CODE REPLACE WITH NEW THE MISSING ELECTRICAL OUTLET SAFETY COVERS AT ALL WALLS AT PUBLIC HALL, 1st STORYOpen
Oct 2, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT EAST AT INTERMEDIATE LANDING AT PUBLIC HALL, 3rd STORY, SECTION ''C''Open
Oct 2, 2026HPD C§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WIRED GLASS AT MIDDLE SASHWINDOW AT SOUTH WALL AT INTERMEDIATE LANDING AT PUBLIC HALL, 4th STORY, SECTION ''A''Open
Oct 2, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT SOUTH AT INTERMEDIATE LANDING AT PUBLIC HALL, 4th STORY, SECTION ''A''Open
Oct 2, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT SOUTH AT INTERMEDIATE LANDING AT PUBLIC HALL, 5th STORY, SECTION ''A''Open
Oct 2, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT EAST AT INTERMEDIATE LANDING AT PUBLIC HALL, 1st STORY, SECTION ''C''Open
Oct 2, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ENTIRE WINDOW FRAME AT EAST AT INTERMEDIATE LANDING AT PUBLIC HALL, 2nd STORY, SECTION ''C''Open
Sep 24, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE BASE CABINET AT SINK IN THE KITCHEN LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOpen
Sep 24, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE HEAVY DUTY LOCK ASSEMBLY AT VESTIBULE DOOROpen
Sep 24, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT NORTH WALL, AND AT EAST WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOpen
Sep 24, 2026HPD B§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK ASSEMBLY AT DOOR IN THE ENTRANCE LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOpen
Sep 24, 2026HPD B§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WALL CABINET AT WEST WALL IN THE KITCHEN LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOpen
Sep 24, 2026HPD CHMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT K, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT SOUTHOpen