Queens · Block 9998 · Lot 110 · 11435

148-22 Archer Avenue

15 floors · 203,782 sq ft · built 2016 · class H2 · owner of record: Archer Ave Realty De, Llc

5open violations
$5,000ECB/OATH penalties owed
0HPD class C (immediately hazardous)
183dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 62 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 203,782 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 183 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 183 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 427 days
Next cycle year 2027
Facade inspection report (Cycle 10B) Applies
Local Law 11 / FISP · Feb 21, 2026 to Feb 21, 2028
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 0, 7 or 8 are in sub-cycle 10B. Agency page

Feb 21, 2028
in 479 days
No Cycle 10 report on record yet
Energy audit and retro-commissioning (2028) Likely applies
Local Law 87 · Calendar year 2028
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 9998). Agency page

Dec 31, 2028
in 793 days
Next due 2028
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-18 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (6) · $5,000 owed
IssuedViolationHearingBalance
Sep 24, 2026Construction CLASS - 2
ATOI OBSERVED IN MECHANICAL ROOMS FLOORS 1 THRU 15 PVC PIPE USED ON HOT WATER HEATERS PER PC 701.9. PLASTIC PIPE. PLASTIC PIPING AND FITTINGS SHALL NOT BE USED., REPAIR AND/OR REPLACE
#39205458Y
Dec 1, 2026
PENDING
$1,250
Sep 24, 2026Construction CLASS - 2
ATIO OBSERVED IN CELLAR LAUNDRY ROOM FLEX PIPE USED ON DRYERS VENTS . PER MC 504.10 RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE CON STRUCTED OF SHEET ST
#39205459X
Dec 1, 2026
PENDING
$1,250
Oct 7, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DISCOVERED CARBON MONOXIDE LEAK AT HOT WATER HEATER TANK AND 3TH AN 4TH FLOORS. POTENTIAL HAZARDS., REPAIR AND/REPLACE
#39162868J
Jul 21, 2026
IN VIOLATION
$2,500
Feb 20, 2025Unknown CLASS - 2
I OBSERVED IN THE ROOF TOP BOILER/ PUMP ROOM THE FAILURE TO PROTECT THE ELECTRICAL EQUIPMENT PUP#3 FROM DETERIORATING AGENTS AS PER EC 110.11. PHOTOS TAKEN.; EC 110.11, COMPLY WITH EC CODE; REPAIR/ REMOVE DETER
#39139152Z
Apr 29, 2025
IN VIOLATION
$0
Feb 20, 2025Unknown CLASS - 2
I OBSERVED IN THE CLOSET ABOVE THE GARAGE EM PANEL THE FAILURE TO PROPERLY TERMINATE THE ELECTRICAL CONDUIT SUPPLYING POWER TO THE STAIRWAY HEATERS. AS REQUIRED THE PROPER CONNECTION PROVIDES BOTH MECHANICAL AN
#39139151R
Apr 29, 2025
IN VIOLATION
$0
Feb 20, 2025Unknown CLASS - 2
I OBSERVED THE WALL SWITCH INSTALLED IN THE BOILER ROOM SHUT OFF THE LIGHTING IN THE CORRIDOR OUTSIDE THIS IS IMPROPER WIRING AS THE HALL SHALL BE ILLUMINATED AT ALL TIMES AT THE POINTS OF EGRESS. PHOTOS TAKEN,
#39139155Y
Apr 29, 2025
IN VIOLATION
$0
DOB (0)

None open.

DOB NOW Safety (0)

None open.

HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Sep 24, 2026ECBConstruction: ATOI OBSERVED IN MECHANICAL ROOMS FLOORS 1 THRU 15 PVC PIPE USED ON HOT WATER HEATERS PER PC 701.9. PLASTIC PIPE. PLASTIC PIPING AND FITTINGS SHALL NOT BE USED., REPAIR AND/OR REPLACEOpen
Sep 24, 2026ECBConstruction: ATIO OBSERVED IN CELLAR LAUNDRY ROOM FLEX PIPE USED ON DRYERS VENTS . PER MC 504.10 RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE CON STRUCTED OF SHEET STOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)