RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 69 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 33,912 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 190 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 190 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1165 days
Next cycle year 2029
Annual boiler inspection (1 boiler) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-17 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (5)
IssuedViolationHearingBalance
Feb 13, 2026Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING. NOTE: UPON INSPECTION EXTERIOR DOOR CELLARLEVEL EXIT 3 NOT SELF-CLOSING WHEN TESTED. REMEDY: REPAIR/REPLACE DOOR.
#35728939M
Mar 6, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: UPON INSPECTION LEAK FROM ROOF DRAIN WITH SPALLING SHEET ROCK IN FRONT OF 306 3RD FL CORRIDOR STAIR B. REMEDY: REPAIR AND/OR REPLACE.
#35728938K
Mar 6, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOORS AND/OR HARDWARE PER BC 1008.1.8 27-371. NOTED: UPON INSPECTION EXTERIOR DOOR EXIT 3 CELLAR LEVEL AN INSTALLATION OF AN ASTRICAL. RE
#35728937Z
Mar 6, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
FAILURE TO MAINTAIN IN CODE-COMPLIANT MANNER. NOTED: UPON INSPECTION BULKHEAD DOOR BINDING AND NOT SELF-CLOSING STAIR B AND DETACHED DOOR CLOSURE ON FIRE RATED SMOKE DOOR AT STAIR B 3RD FL, INCLUDING ROOMS 309
#35728941L
Mar 6, 2026
POP/IN-VIO
$0
Feb 13, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: UPON INSECTION ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381 NOT ILLUMINATING WHEN TESTED AT CELLAR LEVEL ABOVE
#35728940J
Mar 6, 2026
POP/IN-VIO
$0
DOB (2)
IssuedViolationStatus
Apr 25, 2023LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2022 EXTERNAL LOW PRESSURE INSPECTION
#24783
DOB VIOLATION - ACTIVE
Dec 31, 2009LOW PRESSURE BOILER

#24336
DOB VIOLATION - ACTIVE
DOB NOW Safety (5)
IssuedViolationStatus
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Apr 25, 2023Boiler LBLVIO
VIOLATION ISSUED FOR FAILURE TO FILE ANNUAL BOILER 2022 INSPECTION REPORT