3 floors · 20,268 sq ft · built 2001 · class H3 · owner of record: Sterling & Cie, Llc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 63 days | Keep the report on file (not filed with DOB) |
| Gas piping inspection (2029 cycle) Likely applies Local Law 152 · During 2029 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2029 in 1159 days | Next cycle year 2029 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Jul 10, 2026 | Unknown CLASS - 2 FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL RM AND AT THE MAIN WATER SERVICE NO INSTALLATION OF ELECTRODE GROUND ROD. THIS IS SECOND MEANS OF GROUNDING MUST BE P #39195597H | Apr 13, 2027 PENDING | $2,400 |
| Jul 10, 2026 | Unknown CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF VERIZON TELEPHONE / WIFI EQUIPMENT. ALL ELECTRICAL ROOMS /CLOSET SHALL BE DEDI #39195598J | Apr 13, 2027 PENDING | $1,200 |
| Jul 10, 2026 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HOLE PENETRATION ABOVE DOOR LEADING INTO MECHANICAL ROOM. COVERED UP WENT A VENT COVER. LOCATED AT BASEMENT LEVEL., REPAIR AND/REPLACE #39195603P | Mar 5, 2027 PENDING | $2,500 |
| Jul 10, 2026 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED STORAGE INSIDE MECHANICAL ROOM. (MIRCOWAVE, REFRIGERATOR LOCKERS, CLOTHES, TOOLS) LOCATED AT BASEMENT LEVEL., REPAIR AND/RE #39195602N | Mar 5, 2027 PENDING | $2,500 |
| Feb 17, 2026 | Construction CLASS - 2 FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SUMMONS 39074450M, FILE A CERTIFICATE OF CORRECTION #39177447N | Apr 28, 2026 IN VIOLATION | $1,250 |
| Nov 22, 2022 | Unknown CLASS - 2 I OBSERVED ON THE ROOFTOP LEVEL DEFECTIVE WIRING TO THE LIGHTS SJ CORD IS ONLY PERMITTED IN DAMP LOCATIONS EXPOSURE TO THE ELEMENTS IS CONSIDERED A WET LOCATION. AS PER TABLE IN EC 400.4 PHOTOS TAKEN., PROVIDE #39074452X | Jan 31, 2023 IN VIOLATION | $0 |
| Nov 22, 2022 | Construction CLASS - 2 I OBSERVED ON ALL FLOORS NO REMOTE SHUT-DOWN AT THE EXTERIOR OF THE BOILER ROOMS AS PER MC 1006.8.1; MC1006.8.1, COMPLY WITH CODE; INSTALL REMOTE SHUT-DOWN #39074449P | Jan 31, 2023 IN VIOLATION | $0 |
| Nov 22, 2022 | Unknown CLASS - 2 I OBSERVED IN THROUGHOUT THE CELLAR LEVEL WALL MOUNTED BLOWER UNITS FROM A A.C. SPLIT UNIT, THE WIRING TO THE UNIT IS FLEXIBLE CORD THIS IS NOT PERMITTED AS PERMANENT WIRING, ALSO NOTED IN THE BOILER ROOMS THE #39074453H | Jan 31, 2023 IN VIOLATION | $0 |
| Nov 22, 2022 | Unknown CLASS - 2 I OBSERVED ON THE EXTERIOR OF THE BUILDING A COMPRESSOR UNIT AND IN THE CELLAR LEVEL WALL MOUNTED BLOWER UNITS FROM A SPLIT A.C SYSTEM WITH NEW BRANCH CIRCUIT WIRING EQUIPMENT DISCONNECT AND INTERCONNECT WIRING #39074451Y | Jan 31, 2023 IN VIOLATION | $0 |
| Nov 22, 2022 | Unknown CLASS - 1 I OBSERVED ON THE ROOF THE USE OF EMT OUTDOORS, THE CONDUIT IS ALSO IN A STATE OF CORROSION. ALSO NOTED THE GENERATOR IN A SEVERE STATE OF CORROSION. THIS IS AN IMMEDIATE HAZARD AS CORROSION OF ELECTRICAL EQUIP #39074450M | May 23, 2023 IN VIOLATION | $0 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Oct 2, 2023 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Jul 10, 2026 | ECB | Unknown: FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL RM AND AT THE MAIN WATER SERVICE NO INSTALLATION OF ELECTRODE GROUND ROD. THIS IS SECOND MEANS OF GROUNDING MUST BE P | Open |
| Jul 10, 2026 | ECB | Unknown: ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF VERIZON TELEPHONE / WIFI EQUIPMENT. ALL ELECTRICAL ROOMS /CLOSET SHALL BE DEDI | Open |
| Jul 10, 2026 | ECB | Construction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HOLE PENETRATION ABOVE DOOR LEADING INTO MECHANICAL ROOM. COVERED UP WENT A VENT COVER. LOCATED AT BASEMENT LEVEL., REPAIR AND/REPLACE | Open |
| Jul 10, 2026 | ECB | Construction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED STORAGE INSIDE MECHANICAL ROOM. (MIRCOWAVE, REFRIGERATOR LOCKERS, CLOTHES, TOOLS) LOCATED AT BASEMENT LEVEL., REPAIR AND/RE | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 29, 2026, 8:36 AM ET. BBL 4150010087.