Queens · Block 15001 · Lot 87 · 11434

144-25 153 Lane

3 floors · 20,268 sq ft · built 2001 · class H3 · owner of record: Sterling & Cie, Llc

11open violations
$9,850ECB/OATH penalties owed
0HPD class C (immediately hazardous)
1159dto Gas piping inspection (2029 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 63 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 13 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1159 days
Next cycle year 2029

Open violations

ECB / OATH (10) · $9,850 owed
IssuedViolationHearingBalance
Jul 10, 2026Unknown CLASS - 2
FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL RM AND AT THE MAIN WATER SERVICE NO INSTALLATION OF ELECTRODE GROUND ROD. THIS IS SECOND MEANS OF GROUNDING MUST BE P
#39195597H
Apr 13, 2027
PENDING
$2,400
Jul 10, 2026Unknown CLASS - 1
ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF VERIZON TELEPHONE / WIFI EQUIPMENT. ALL ELECTRICAL ROOMS /CLOSET SHALL BE DEDI
#39195598J
Apr 13, 2027
PENDING
$1,200
Jul 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HOLE PENETRATION ABOVE DOOR LEADING INTO MECHANICAL ROOM. COVERED UP WENT A VENT COVER. LOCATED AT BASEMENT LEVEL., REPAIR AND/REPLACE
#39195603P
Mar 5, 2027
PENDING
$2,500
Jul 10, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED STORAGE INSIDE MECHANICAL ROOM. (MIRCOWAVE, REFRIGERATOR LOCKERS, CLOTHES, TOOLS) LOCATED AT BASEMENT LEVEL., REPAIR AND/RE
#39195602N
Mar 5, 2027
PENDING
$2,500
Feb 17, 2026Construction CLASS - 2
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SUMMONS 39074450M, FILE A CERTIFICATE OF CORRECTION
#39177447N
Apr 28, 2026
IN VIOLATION
$1,250
Nov 22, 2022Unknown CLASS - 2
I OBSERVED ON THE ROOFTOP LEVEL DEFECTIVE WIRING TO THE LIGHTS SJ CORD IS ONLY PERMITTED IN DAMP LOCATIONS EXPOSURE TO THE ELEMENTS IS CONSIDERED A WET LOCATION. AS PER TABLE IN EC 400.4 PHOTOS TAKEN., PROVIDE
#39074452X
Jan 31, 2023
IN VIOLATION
$0
Nov 22, 2022Construction CLASS - 2
I OBSERVED ON ALL FLOORS NO REMOTE SHUT-DOWN AT THE EXTERIOR OF THE BOILER ROOMS AS PER MC 1006.8.1; MC1006.8.1, COMPLY WITH CODE; INSTALL REMOTE SHUT-DOWN
#39074449P
Jan 31, 2023
IN VIOLATION
$0
Nov 22, 2022Unknown CLASS - 2
I OBSERVED IN THROUGHOUT THE CELLAR LEVEL WALL MOUNTED BLOWER UNITS FROM A A.C. SPLIT UNIT, THE WIRING TO THE UNIT IS FLEXIBLE CORD THIS IS NOT PERMITTED AS PERMANENT WIRING, ALSO NOTED IN THE BOILER ROOMS THE
#39074453H
Jan 31, 2023
IN VIOLATION
$0
Nov 22, 2022Unknown CLASS - 2
I OBSERVED ON THE EXTERIOR OF THE BUILDING A COMPRESSOR UNIT AND IN THE CELLAR LEVEL WALL MOUNTED BLOWER UNITS FROM A SPLIT A.C SYSTEM WITH NEW BRANCH CIRCUIT WIRING EQUIPMENT DISCONNECT AND INTERCONNECT WIRING
#39074451Y
Jan 31, 2023
IN VIOLATION
$0
Nov 22, 2022Unknown CLASS - 1
I OBSERVED ON THE ROOF THE USE OF EMT OUTDOORS, THE CONDUIT IS ALSO IN A STATE OF CORROSION. ALSO NOTED THE GENERATOR IN A SEVERE STATE OF CORROSION. THIS IS AN IMMEDIATE HAZARD AS CORROSION OF ELECTRICAL EQUIP
#39074450M
May 23, 2023
IN VIOLATION
$0
DOB (0)

None open.

DOB NOW Safety (1)
IssuedViolationStatus
Oct 2, 2023Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Affirmation of Correction
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Jul 10, 2026ECBUnknown: FAILURE TO PROVIDE ADEQUATE GROUNDING OF ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL RM AND AT THE MAIN WATER SERVICE NO INSTALLATION OF ELECTRODE GROUND ROD. THIS IS SECOND MEANS OF GROUNDING MUST BE POpen
Jul 10, 2026ECBUnknown: ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL ROOM THE INSTALLATION OF VERIZON TELEPHONE / WIFI EQUIPMENT. ALL ELECTRICAL ROOMS /CLOSET SHALL BE DEDIOpen
Jul 10, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. HOLE PENETRATION ABOVE DOOR LEADING INTO MECHANICAL ROOM. COVERED UP WENT A VENT COVER. LOCATED AT BASEMENT LEVEL., REPAIR AND/REPLACEOpen
Jul 10, 2026ECBConstruction: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED STORAGE INSIDE MECHANICAL ROOM. (MIRCOWAVE, REFRIGERATOR LOCKERS, CLOTHES, TOOLS) LOCATED AT BASEMENT LEVEL., REPAIR AND/REOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 29, 2026, 8:36 AM ET. BBL 4150010087.

Look up another building