5 floors · 93,205 sq ft · built 1922 · class W1 · owner of record: Nyc Department Of Education
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Gas piping inspection (2026 cycle) Likely applies Local Law 152 · During 2026 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2026 in 62 days | Due this year |
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 62 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 93,205 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 183 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 183 days | Annual filing |
| Energy audit and retro-commissioning (2033) Likely applies Local Law 87 · Calendar year 2033 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2843). Agency page | Dec 31, 2033 in 2619 days | Next due 2033 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-04-07 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Apr 1, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: INTERIORFIRE-PROOF DOORS DO NOT CLOSE PROPERLY WHEN TESTED AT, 3RD FLR-STAIRCASE "B". 2ND FLR-STAIRCASE "C". 1ST FLR-"EXIT 3" INTERIOR GYM DOOR. REM #35722433H | May 15, 2026 POP/IN-VIO | $0 |
| Apr 1, 2026 | Construction CLASS - 2 28-301.1. RE-ISSUE #35719753J. FAILURE TO PROVIDE VENTILATION TO GAS METER PER P115.6(1968), FGC APPENDIX E(E4)(2014 CODE). NOTED: IN CELLAR, GAS METER ROOM DOES NOT HAVE PROPER VENTILATION IN THE ROOM. REMEDY: #35722432X | May 15, 2026 POP/IN-VIO | $0 |
| May 23, 2025 | Construction CLASS - 2 REISSUE #35682961H DATE OF ISSUE: 07-26-2024. FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6(1968 CODE), FGC APPENDIX E(E6)(2014CODE) IN CELLAR GAS METER ROOM NO PROPER VENTILATION OBSERVED AT THE T #35719753J | Jul 11, 2025 POP/IN-VIO | $0 |
| Jul 26, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS.NOTED:EMERGENCY EXIT SIGNS NOT ILLUMIZED AT TIME OF INSPECTION-5F NEXT TO STAIRWAY#3,4FL STAIRWAY #35682963L | Dec 20, 2024 POP/IN-VIO | $0 |
| Jul 26, 2024 | Construction CLASS - 2 28-301.1 REISSUE ECB#35623000Y FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM NOTED:IN CELLAR GAS METER ROOM NOT VENTILATED PROPERLY.REM:COMPLY WITH NOTICE OF VIOLATION. #35682961H | Dec 20, 2024 POP/IN-VIO | $0 |
| Apr 5, 2023 | Construction CLASS - 2 38-301 REISSUE #35578400H FAILURE TO PROVIDE VENTILATION TO GAS METER RM PER P115.6(1968 CODE) FGC APPENDIX E(E4)(2014 CODE).NOTE:OBSERVED AT CELLAR LEVEL GAS METER RM HAS NO VENTILATION FOR FRESH AIR.REMEDY:CO #35673000Y | Jul 7, 2023 POP/IN-VIO | $0 |
| Mar 24, 2022 | Construction CLASS - 2 RE-ISSUE #35553643L FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE) FGC APPENDIX E (E4)(2014 CODE)NOTED:OBSERVED AT (CELLAR)GAS METER ROOM NO VENTILATION FOR FRESH AIR.REMEDY:COMPLY WITH #35578400H | Jul 15, 2022 POP/IN-VIO | $0 |
| Mar 10, 2021 | Construction CLASS - 2 28-301.1 REISSUE: 35235273J FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER 115.6 (1968 CODE) FGC APPENDIX E (E4) 2014. NOTED: NO VENTILATION AT GAS METER ROOM. REMEDY: COMPLY WITH CODE #35553643L | Jun 18, 2021 POP/IN-VIO | $0 |
| Apr 13, 2020 | Construction CLASS - 2 SEC. 28-301.1 FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E 4)(2014 CODE). NOTED: AT GAS METER ROOM,NO FRESH AIR VENTILATION PROVIDED. REMEDY: COMPLY W/NOTICE OF VIOLAT #35490770Z | Aug 7, 2020 POP/IN-VIO | $0 |
| Mar 20, 2019 | Construction CLASS - 2 28-301.1 RE-ISSUE# 35311783L FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2014 CODE) NOTE:AT CELLAR LEVEL IN GAS METER ROOM NO FRESH AIR VENTILATION. REMEDY:COMPLY W #35402405H | Jun 7, 2019 POP/IN-VIO | $0 |
| Feb 6, 2018 | Construction CLASS - 2 28-301.1 REISSUE VIOLATION #35235273J FAILURE TO PROVIDE VENTILATION TO GAS METER ROOM PER P 115.6 (1968 CODE) FGC APPENDIX E (E4)(2014) CODE. NOTE: MISSING VENTILATION WAS OBSERVED OF GAS METER ROOM AT CEL #35311783L | May 18, 2018 POP/IN-VIO | $0 |
| Mar 16, 2017 | Construction CLASS - 2 SEC. 28-301.1 FAILUR TO PROVIDE VENTILATION TO GAS METER ROOM PER P115.6(1968 CODE),FGC APPENDIX E(E4)(2014 CODE). NOTED: MISSING VENTILATION WAS OBSERVED AT GAS METER ROOM AT CELLAR LEVEL. REMEDY: COMPLY W/NOT #35235273J | May 5, 2017 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #06150 | DOB VIOLATION - ACTIVE |
| Nov 14, 2025 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION #06149 | DOB VIOLATION - ACTIVE |
| Jun 20, 2023 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION #43324 | DOB VIOLATION - ACTIVE |
| Jun 20, 2023 | LOW PRESSURE BOILER VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION #45355 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Nov 14, 2025 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device | Active |
| Jun 20, 2023 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION | Active |
| Jun 20, 2023 | Boiler LBLVIO VIOLATION ISSUED-FAILURE TO FILE 2019 EXTERNAL LOW PRESSURE INSPECTION | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 30, 2026, 1:00 PM ET. BBL 2028430040.