| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 46 days | Keep the report on file (not filed with DOB) |
| Annual boiler inspection (1 boiler) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2025-05-16 (Accepted). Agency page | Dec 31, 2026 in 46 days | 1 of 1 without an accepted 2026 report yet |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 28,460 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 167 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 167 days | Annual filing |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 10 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 777 days | Next cycle year 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Dec 16, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1 (2014 CODE); 27-542; BC 1008.2 (2022). OBSERVED FLOORS WITH ONLY H #39170724K | Feb 26, 2026 IN VIOLATION | $1,250 |
| Dec 16, 2025 | Construction CLASS - 2 OBSERVED IN THE BASEMENT OPEN ENDED WASTE LINES, A DAMAGE SPRINKLER HEAD, BUSHING FITTING ON GAS LINE AND GAS DRYER VENT GOING THROUGH WINDOW WHICH IS CONTRARY TO CODE SECTIONS FGC 503.3, FGC 403.10.4, BC 101.4 #39170621H | Oct 1, 2026 IN VIOLATION | $1,250 |
| Dec 16, 2025 | Boilers CLASS - 2 FOUND HB SMITH OIL FIRED BOILER MODEL# 28A-10, WITH LEAKING CONDENSATE PUMP, GLASS GAUGE AT CONDENSATE TANK DIRTY, CORRODED PIPING AT COIL. #39170593J | Mar 19, 2026 DEFAULT | $6,250 |
| Mar 14, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE.OBSERVED HOLE PENATRATIONS THROUGHOUT BASEMENT AND FIRST FLOOR. UNPERMITTED PLASTI #39141605P | Nov 7, 2025 IN VIOLATION | $2,500 |
| Mar 14, 2025 | Construction CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STOREAGE UNDERNEATH BOTH STAIRCASES. (BOXES, WOOD SELEVES, BABY PRODUCTS, CLEANING PRODUCTS).POTENTIAL FIRE HAZARDS., MAINTAIN STORAGE IN CO #39141607Z | Nov 7, 2025 IN VIOLATION | $2,500 |
| Mar 12, 2025 | Elevators CLASS - 2 CLASS 2 ITEMS: REPAIR OIL LEAK AND CLEAN HOIST MACHINE. IN-CAR COMMUNICATION INOPERATIVE. PROVIDE AN UPDATED MAINTENANCE LOG. PROVIDE A MAINTENANCE CONTROL PROGRAM. BRAKE MAINTENANCE TAG EXPIRED. PROVED BRAILLE #39141275L | May 22, 2025 IN VIOLATION | $312 |
| Jun 17, 2024 | Elevators CLASS - 1 DOOR ZONE RESTRICTOR BYPASSED. REMEDY: REPAIR / REPLACE. CALL THE D.O.B. FOR REINSPECTION. #39117033Z | Jan 16, 2025 IN VIOLATION | $1,250 |
| Apr 15, 2024 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS AS STATED IN ECB# 39071367H ISSUED ON 10/04/2022 AND CORRECT CONDITIONS AND FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-2., CO #39111658L | Jun 20, 2024 IN VIOLATION | $625 |
| Apr 15, 2024 | Unknown CLASS - 1 I OBSERVED IN THE WATER METER ROOM THE DETERIORATED CONDITION OF THE JUMPER WIRE DUE TO EXCESSIVE HEAT, THIS WAS VERIFIED BY PHYSICAL TOUCHING OF THE WIRE AND VISUAL INSPECTION OF THE INSULATION. THIS IS AN IMM #39111660K | Jun 26, 2025 IN VIOLATION | $1,600 |
| Dec 20, 2023 | Construction CLASS - 1 UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 35657507N ISSUED ON 07/2023 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01., COMPLY W #39101853H | Jan 2, 2025 IN VIOLATION | $625 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Dec 15, 2025 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device | Active |
| Issued | Class | Violation | Correct by |
|---|---|---|---|
| Feb 6, 2020 | C | § 27-2056.4 ADM CODE- CORRECT FAILURE TO NOTIFY OCCUPANTS AND/OR TO INVESTIGATE LEAD-BASED PAINT HAZARDS. | Feb 12, 2020 |
| Feb 4, 2020 | C | § 27-2056.4(H) AND 27-2056.17 ADM CODE -CORRECT FAILURE TO PROVIDE TO THE DEPARTMENT WITHIN 45 DAYS OF DEMAND ALL RECORDS REQUIRED TO BE MAINTAINED BY OWNER PURSUANT TO LOCAL LAW 1 OF 2004 RELATED TO LEAD-BASED PAINT NOTICES, INSPECTIONS AND REMEDIATION/ABATEMENT ACTIVITIES. | Feb 10, 2020 |