5 floors · 11,940 sq ft · built 2014 · class H9 · owner of record: Hillside Hotel Llc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 68 days | Keep the report on file (not filed with DOB) |
| Gas piping inspection (2027 cycle) Likely applies Local Law 152 · During 2027 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2027 in 433 days | Next cycle year 2027 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Oct 15, 2026 | Elevators CLASS - 2 CLASS 2: SUBSTANTIAL WATER ACCUMULATION IN ELEVATOR PIT, AS PER ASME A17.1 8.6.4.7. REMEDY: REMOVE WATER AND CORRECT SOURCE. MAINTENANCE LOG OUTDATED, AS PER ASME A17.1 8.6.1.4. REMEDY: UPDATE REQUIRED RECORDS. #39208084M | Dec 22, 2026 PENDING | $625 |
| Oct 13, 2026 | Unknown CLASS - 2 MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN STAIRWAYS A AND B THE EMERGENCY LIGHTS ARE NOT WORKING. WHEN PUSHING TEST BUTTON 60% OR 70% OF LIGHTS SHOULD LUMINATE. NEC ARTICLE #39207574K | Dec 22, 2026 PENDING | $800 |
| Oct 13, 2026 | Boilers CLASS - 2 ALL FIVE AO SMITH GAS HOT WATER HEATERS ARE MISSING DISCHARGE PIPES ON RELIEF VALVES, ALSO MISSING ACCESSIBLE EMERGENCY SHUT OFF SWITCHES. HEATER #3 MISSING NEUTRALIZER., MAINTAIN BOILER; CORRECT VIOLATING COND #39207591M | Dec 22, 2026 PENDING | $1,250 |
| Oct 13, 2026 | Construction CLASS - 1 ATOI OBSERVED PVC BEING USED ON THE WATER HEATERS INTAKE AND EXHAUST IN THE ROOF MECHANICAL ROOM PVC IS NOT PERMITTED. CONTRARY TO 503.4.1, REPAIR AND/REPLACE #39207625L | Dec 22, 2026 PENDING | $2,500 |
| Oct 13, 2026 | Construction CLASS - 1 ATOI OBSERVED OBSTRUCTED AND PAINTED SPRINKLERS THROUGH OUT THE BUILDING. CONTRARY TO BC 903.3.3 OBSTRUCTED LOCATIONS IN AUTOMATIC FIRE SPRINKLER SYSTEMS. IT MANDATES THAT SPRINKLERS BE POSITIONED TO AVOID OBST #39207626N | Dec 22, 2026 PENDING | $2,500 |
| Oct 13, 2026 | Construction CLASS - 2 ATOI OBSERVED IN THE LAUNDRY ROOM AND LOBBY PVC BEING USED UNDER THE SINKS WASTE PIPING. WHICH IS CONTRARY TO PC 701.9 PLASTIC PIPE. PLASTIC PIPING AND FITTINGS SHALL NOT BE USED., REPAIR AND/OR REPLACE #39207628R | Dec 22, 2026 PENDING | $1,250 |
| Oct 13, 2026 | Construction CLASS - 2 ATOI OBSERVED GALVANIZED PIPING USED ON THE DRYER GAS FEED. NATIONAL GRID ISOLATED AND TAGGED DRIER. CONTRARY TO FGC 403.4.2 - STEEL GAS PIPE SHALL COMPLY WITH ASTM A53 OR OTHER APPROVED STANDARDS. GALVANIZED S #39207627P | Dec 22, 2026 PENDING | $1,250 |
| Oct 13, 2026 | Unknown CLASS - 2 MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON THE ROOF THE HOT WATER TANK ROOM HAS NO REMOTE SHUTDOWN FOR THE HOT WATER TANKS THAT HAS MOTORIZED FAN AND ELECTRIC IGNITION. B.C #39207573Z | Dec 22, 2026 PENDING | $800 |
| Sep 13, 2021 | Boilers CLASS - 2 FOUND UNREGISTERED OIL TANK SUPPLING GENERATOR S/N E-00087410 LOCATED ON ROOF AT 140-17 QUEENS BLVD. JOB# 421431962 NOT SIGNED OFF., MAINTAIN BOILER; CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF #39047540M | Dec 21, 2021 DEFAULT | $0 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Oct 10, 2025 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction | Active |
| Oct 10, 2025 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
| Issued | Class | Violation | Correct by |
|---|---|---|---|
| Jul 27, 2026 | A | § 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY | Oct 30, 2026 |
| May 11, 2026 | A | (A) § HMC:FILE ANNUAL BEDBUG REPORT IN ACCORDANCE WITH HPD RULE AS DESCRIBED ON THE BACK OF THIS NOTICE OF VIOLATION OR AS DESCRIBED ON HPDS WEBSITE, WWW.NYC.GOV\HPD, SEARCH BED BUGS. | Aug 14, 2026 |
| Date | Source | What | Now |
|---|---|---|---|
| Oct 15, 2026 | ECB | Elevators: CLASS 2: SUBSTANTIAL WATER ACCUMULATION IN ELEVATOR PIT, AS PER ASME A17.1 8.6.4.7. REMEDY: REMOVE WATER AND CORRECT SOURCE. MAINTENANCE LOG OUTDATED, AS PER ASME A17.1 8.6.1.4. REMEDY: UPDATE REQUIRED RECORDS. | Open |
| Oct 13, 2026 | ECB | Unknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED IN STAIRWAYS A AND B THE EMERGENCY LIGHTS ARE NOT WORKING. WHEN PUSHING TEST BUTTON 60% OR 70% OF LIGHTS SHOULD LUMINATE. NEC ARTICLE | Open |
| Oct 13, 2026 | ECB | Boilers: ALL FIVE AO SMITH GAS HOT WATER HEATERS ARE MISSING DISCHARGE PIPES ON RELIEF VALVES, ALSO MISSING ACCESSIBLE EMERGENCY SHUT OFF SWITCHES. HEATER #3 MISSING NEUTRALIZER., MAINTAIN BOILER; CORRECT VIOLATING COND | Open |
| Oct 13, 2026 | ECB | Construction: ATOI OBSERVED PVC BEING USED ON THE WATER HEATERS INTAKE AND EXHAUST IN THE ROOF MECHANICAL ROOM PVC IS NOT PERMITTED. CONTRARY TO 503.4.1, REPAIR AND/REPLACE | Open |
| Oct 13, 2026 | ECB | Construction: ATOI OBSERVED OBSTRUCTED AND PAINTED SPRINKLERS THROUGH OUT THE BUILDING. CONTRARY TO BC 903.3.3 OBSTRUCTED LOCATIONS IN AUTOMATIC FIRE SPRINKLER SYSTEMS. IT MANDATES THAT SPRINKLERS BE POSITIONED TO AVOID OBST | Open |
| Oct 13, 2026 | ECB | Construction: ATOI OBSERVED IN THE LAUNDRY ROOM AND LOBBY PVC BEING USED UNDER THE SINKS WASTE PIPING. WHICH IS CONTRARY TO PC 701.9 PLASTIC PIPE. PLASTIC PIPING AND FITTINGS SHALL NOT BE USED., REPAIR AND/OR REPLACE | Open |
| Oct 13, 2026 | ECB | Construction: ATOI OBSERVED GALVANIZED PIPING USED ON THE DRYER GAS FEED. NATIONAL GRID ISOLATED AND TAGGED DRIER. CONTRARY TO FGC 403.4.2 - STEEL GAS PIPE SHALL COMPLY WITH ASTM A53 OR OTHER APPROVED STANDARDS. GALVANIZED S | Open |
| Oct 13, 2026 | ECB | Unknown: MISCELLANEOUS VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. OBSERVED ON THE ROOF THE HOT WATER TANK ROOM HAS NO REMOTE SHUTDOWN FOR THE HOT WATER TANKS THAT HAS MOTORIZED FAN AND ELECTRIC IGNITION. B.C | Open |
| Sep 30, 2026 | HPD C | § 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE BATHROOM LOCATED AT B-ROOM 302A, 3rd STORY, 3rd B-ROOM FROM NORTH AT EAST | Closed |
| Jul 27, 2026 | HPD C | § 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE BATHROOM LOCATED AT APT 302, 3rd STORY, 3rd APARTMENT FROM NORTH AT EAST | Closed |
| Jul 27, 2026 | HPD A | § 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY | Closed |
| Jul 27, 2026 | HPD C | § 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY | Closed |
| Jul 27, 2026 | HPD A | § 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Oct 24, 2026, 3:52 PM ET. BBL 4096200060.