Brooklyn · Block 3298 · Lot 1 · 11237

1300 Greene Avenue

4 floors · 165,620 sq ft · built 1976 · class W1 · owner of record: Nyc Department Of Education

27open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
62dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 4 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 62 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 62 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 165,620 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 183 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 183 days
Annual filing
Energy audit and retro-commissioning (2028) Likely applies
Local Law 87 · Calendar year 2028
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 3298). Agency page

Dec 31, 2028
in 793 days
Next due 2028
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-08-03 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (25)
IssuedViolationHearingBalance
Apr 28, 2026Construction CLASS - 2
REISSUE#35717409L AT THE TIME OF INSPECTION CRACKS WERE ON CORRIDOR WALL AT ROOM 315,THERE WAS EFFLORESCENCE IN STAIRCASE H ON 4TH FLOOR ROOM 301 HAS WATER STAIN IN CEILING ROOM 259 HAD BROKEN GLASS PANEL 2ND,3
#35732952Z
Jun 3, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
REISSUE#35717410Z AT THE TIME OF INSPECTION,THE FOLLOWING EXIT DISCHARGE DOORS WERE NOT SELF-CLOSING #9,#5 FRAME WAS FALLING OFF.REM:REPAIR/REPLACE DOOR.
#35732950P
Jun 3, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
REISSUE#35717408J AT THE TIME OF INSPECTION,THE FOLLOWING ELECTRICAL METER ROOM HAS OPENING AT CEILING/WALL WERE THE CLUSTER OF PIPES ARE THGAS METER ROOM HAD PENETRATION OPEN AT CEILING.BOTH ELECTRICAL METER R
#35722399N
Jun 3, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
REISSUE#35717407H AT THE TIME OF INSPECTION,THE FOLLOWING EMERGENCY LIGHTS WERE INOPERABLE LIGHT IN STAIRWELL H BY 3RD FLOOR LIGHTS IN STAIRWELL A ON 3RD/2ND FLOOR LIGHT IN STAIRWELL 4 ON 2ND FLOOR ALL EMERGENC
#35722398L
Jun 3, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
REISSUE#35072839P AT THE TIME OF INSPECTION,THE FOLLOWING DOORS WERE NOT SELF-CLOSING CORRIDOR DOORS NEXT STAIRCASE H ON 4TH FLOOR,457,401,409,351,333,CORRIDOR DOOR NEXT TO 248,253,209 DOOR FROM 2ND FLOOR GYM S
#35722397J
Jun 3, 2026
POP/IN-VIO
$0
Apr 28, 2026Construction CLASS - 2
28-301.1 UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PERFDNY 2008 CODE;FC 803.3.2.AT THE TIME OF INSPECTION,6TH FLOOR CORRIDORNEAR ROOM 443 HAD EXCESSIVE ARTWORK IN EXCESS OF 20% AS PERMITTED.REM:
#35732951R
Jun 3, 2026
POP/IN-VIO
$0
May 1, 2025Construction CLASS - 2
REISSUE #35672837L: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE-STOPPING FOR BC 712.3; 27-543. AT ELECTRICAL ROOM IN CELLAR LEVEL REAR ENTRANCE DOOR LARGE OPENING SURROUNDING CONDUIT PIPES WI
#35717408J
Jun 2, 2025
POP/IN-VIO
$0
May 1, 2025Construction CLASS - 2
REISSUE #35672840M: EXIT DOOR NOT SELF-CLOSING AT MAIN EXIT 7, EXIT 8(KITCHEN) NOT CLOSE PROPERLY WHEN TESTED. REMEDY: REPAIR AND/OR REPLACEDOOR(S).
#35717410Z
Jun 2, 2025
POP/IN-VIO
$0
May 1, 2025Construction CLASS - 2
REISSUE #35672843H; FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: AT 3RD FLOOR LESS OF ROOM HORIZONTAL CRACKS WITH LOOSE/MISSING MORTAR ARE GLAZE SURFACE CMU INTERIOR BLOCK WALLS. REMEDY: REPAIR AND/OR
#35717409L
Jun 2, 2025
POP/IN-VIO
$0
May 1, 2025Construction CLASS - 2
REISSUE #35677520X: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER 1006,1; 27-381. EXISTING EMERGENCY LIGHT(S) ARE NOT OPERATIONAL WHEN T
#35717407H
Jun 2, 2025
POP/IN-VIO
$0
May 3, 2024Construction CLASS - 2
REISSUE#35672841Y FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.AT TIME OF MY INSPECTION I OBSERVED AT 3RD FLOOR STAIRWEL
#35677520X
Jul 24, 2024
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR DOOR AT MAIN ENTRANCE TO BUILDING EXIT 7, & KITCHEN EXIT 8 NOT WORKING PROPERLY.REMEDY:REPAIR/REPLACE DOOR
#35672840M
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT RIGHT SIDE OF EXP #2 NEAR 3RD FL LEVEL HAS LOOSE & MISSING MORTAR IN VARIOUS AREAS THROUGHOUT.BRICK MISSING AT GROUND LEVEL OUTSIDE EXIT 4.REMEDY:R
#35672843H
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
REISSUE #35650743N NOTED:AT 3RD FL CORRIDOR BY RM 315, RIGHT SIDE OF STAIR H & 2ND FL ADJACENT TO RM 228*(WHITE CMU BLOCKWALL) ALL HAVE CRACKS AND/OR STEP CRACKS IN VARIOUS AREAS.REMEDY:REPAIR AND/OR REPLACE.
#35672838N
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT 4TH FL CORRIDOR BY STAIR H,ROOM 449, 3RD FL CORRIDOR BY STAIR F,G & H, ROOM 307,309,322(LIBRARY)ENTRANCE,RIGHT ROOM INSIDE 322,2ND FL ROOM 205,209
#35672839P
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXIT,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1; 27-381.NOTED:AT 3RD FL STAIRWELL A, 2ND FL GYNASIUM,STAIRWELL B, H, 1ST FL STAIRWELL
#35672841Y
Jun 21, 2023
POP/IN-VIO
$0
Mar 14, 2023Construction CLASS - 2
REISSUE #35650744P NOTED:AT CELLAR LEVEL ELECTRICAL METER ROOM,LARGE HOLES ABOVE ENTRANCE DOOR FROM CONDUITS IN VARIOUS AREAS.REMEDY:PROVIDE/MAINATAIN FIRE STOPPING.
#35672837L
Jun 21, 2023
POP/IN-VIO
$0
Apr 14, 2022Construction CLASS - 2
REISSUE#35557931Y 4/12/2021.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT 3RD FLOOR CORRIDOR BY ROOM 315,4TH FLOOR BY ROOM 424 LARGE STEP PATTERN CRACKS ON CMU BLOCK WALLS.REMEDY:COMPLY WITH CODE.
#35650743N
Sep 21, 2022
POP/IN-VIO
$0
Apr 14, 2022Construction CLASS - 2
REISSUE#35557930M 4/12/2021.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PRE BC712.3;27-345 AT ELECTRICAL ROOM IN BASEMENT EMERGENCY LIGHT CONDUIT PENETRATED WALL WITH NO FIRE STOPPING
#35650744P
Sep 21, 2022
POP/IN-VIO
$0
Apr 12, 2021Construction CLASS - 2
REISSUE#35486745P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER MISSING EMERGENCY LIGHTING AT 1ST FL EXITS ALSO PIPE PENTRATION AT BASEMENT ELECTRICAL ROOM DOES NOT HAVE ADEQUATE FIRE STOPPING.
#35557930M
Sep 8, 2021
POP/IN-VIO
$0
Apr 12, 2021Construction CLASS - 2
REISSUE#35486744N FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION NOTED: AT 3RD FL CORRIDOR OUTSIDE OF ROOM#315,12 FOOT STEP CRACK IN C.M.U. BLOCK WALL. REMEDY: COMPLY WITH CODE.
#35557931Y
Sep 8, 2021
POP/IN-VIO
$0
Mar 27, 2020Construction CLASS - 2
REISSUE#35235629L FAILURE TO MAINTAIN BUILDING WALLS/OR APPURETNANCES RM 315 HORIZONTAL CRACK ON WALL CORRIDOR MAINTAIN BUILDING WALLS
#35486744N
Oct 14, 2020
POP/IN-VIO
$0
Mar 27, 2020Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER LACK OF EMERGENCY LIGHTING FOR EXITS ,EXIT DISCHARGES AND PUBLCI CORRIDOR PER BC 7.2.3;27-345 ELECTRICAL HAS PIPES PENETRATUBF WALL WITH NO FIRESTOPPING REP
#35486745P
Jun 8, 2020
POP/IN-VIO
$0
Mar 8, 2018Construction CLASS - 2
REISSUE#35235629L FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: STEPS CRACK IN THE WALL AT 3RD FL OUTSIDE RM#315 & AT 4TH FL ADJACENT TO RM#424 AT CORRIDOR. REMEDY: COMPLY W/CODE/REPAIR THE WALLS.
#35322042H
Jun 11, 2018
POP/IN-VIO
$0
Apr 5, 2017Construction CLASS - 2
FAILURE TO MAINTAIN BUUILDING WLLS OR APPURTENANCES.NOTED AT 3RD FLR REAR OF ROOM 315 HORIZONTAL CRACK ON WALL 1/4"GAP.REM:MAINTAIN BUILDINGWALLS(EXTERIOR-INTERIOR).
#35235629L
May 15, 2017
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (2)
IssuedViolationStatus
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 30, 2026, 1:52 PM ET. BBL 3032980001.