Manhattan · Block 894 · Lot 7505 · 10016

130 East 39th Street

15 floors · 141,803 sq ft · built 1927 · class RC · owner of record: 130 East 39 Llc

14open violations
$40,125ECB/OATH penalties owed
0HPD class C (immediately hazardous)
43dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 6 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 43 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-17 (Accepted). Agency page

Dec 31, 2026
in 43 days
1 of 2 without an accepted 2026 report yet
Facade inspection report (Cycle 10A) Applies
Local Law 11 / FISP · Feb 21, 2025 to Feb 21, 2027
What this is

Buildings taller than six stories file a facade inspection report by a QEWI once every five-year cycle. Tax blocks ending in 4, 5, 6 or 9 are in sub-cycle 10A. DOB facade records for this building show $1,685,950 in late-filing or failure-to-file penalties. Agency page

Feb 21, 2027
in 95 days
No Cycle 10 report on record yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 141,803 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 164 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 164 days
Annual filing
Energy audit and retro-commissioning (2034) Likely applies
Local Law 87 · Calendar year 2034
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 894). Agency page

Dec 31, 2034
in 2965 days
Next due 2034

Open violations

ECB / OATH (19) · $40,125 owed
IssuedViolationHearingBalance
Aug 13, 2026Construction CLASS - 1
AT THE TIME OF INSPECTION OBSERVED THROUGHOUT THE BUILDING, MULTIPLE AUTOMATIC SPRINKLER HEADS WERE OBSERVED OBSTRUCTED. MULTIPLE SPRINKLER HEADS WERE OBSERVED WITH THEIR ESCUTCHEONS/CAPS PAINTED AND OR MISSING
#39200471X
May 17, 2027
PENDING
$2,500
Aug 13, 2026Unknown CLASS - 1
ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT 4 NEW 200 AMP DISCONNECT SW AND 1 1600 AMP DISTRIBUTION INSTALLED WITH BX RISERS. ALSO IN LOBBY AND BASEMENT HUNG ELECTRIC HEATERS INSTALLED WITH BX AN
#39200481J
May 17, 2027
PENDING
$2,500
Aug 13, 2026Elevators CLASS - 1
CLASS 1: 1. DLM MALFUNCTIONING AND NOT PROVIDING REQUIRED DOOR LOCK MONITORING. AS PER ASME A17.1 2.12. REMEDY: REPAIR DLM TO RESTORE PROPER MONITORING. CLASS 2: 2. CAR PRODUCES WHISTLING NOISE WHILE TRAVELING.
#39200564P
Oct 22, 2026
IN VIOLATION
$1,250
Aug 13, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE MAIN LOBBY AND BACK STORAGE AREA EXPOSED BX AND SJ CORD FEEDING HUNG HEATERS SJ COR
#39200480H
May 17, 2027
PENDING
$1,600
Aug 13, 2026Elevators CLASS - 1
CLASS 1 C/U: 1. COMPENSATION CHAIN DRAGGING ON PIT FLOOR, CREATING HAZARDOUS INTERFERENCE WITH PIT EQUIPMENT. AS PER ASME A17.1 2.2. REMEDY: ADJUST AND SECURE COMPENSATION CHAIN TO MAINTAIN COMPLIANT FLOOR CLEA
#39200565R
Oct 22, 2026
IN VIOLATION
$1,250
Aug 13, 2026Unknown CLASS - 1
UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES. OBSERVED THRU OUT HALLWAYS AND CHILDREN PLAY ROOM NO INSTALLATION OF TAMPER RESISTANT RECEPTACLES AND IN THE MECHANICAL RMS NO G
#39200482L
May 17, 2027
PENDING
$1,600
Aug 13, 2026Construction CLASS - 1
AT THE TIME OF INSPECTION OBSERVED ON THE ROOF ON THE COOLING TOWER UNIT A CRACKED VALVE ALSO PIPE CONNECTION MADE WITH FERNCO COUPLES . MC 908.1 - COOLING TOWERS: COOLING TOWERS SHALL BE INSTALLED IN ACCORDANC
#39200470Y
May 17, 2027
PENDING
$2,500
Aug 12, 2025Elevators CLASS - 2
CLASS 2: MISSING LOBBY BRAILLE TAGS, INSTALL. EMRGENCY PHONE VOLUME TOO LOW, ADJUST. CAR OPERATING PANEL KEY SWITCHES LABELS WORN, PROVIDE NEW LABELS.
#39156876Z
Nov 20, 2025
IN VIOLATION
$625
Aug 12, 2025Elevators CLASS - 2
CLASS 2: MISSING DROP CEILING IN THE CAR EXPOSING UNGUARDED LIGHT, INSTALL CLEAR DROP CEILING. MISSING DEVICE ID ON THE CAR OPERATING PANEL, PROVIDE. MISSING IN-CAR EMERGENCY PHONE, INSTALL.
#39156875R
Feb 26, 2026
IN VIOLATION
$625
Aug 12, 2025Elevators CLASS - 2
CLASS 2: MISSING LOBBY BRAILLE TAGS, INSTALL. EMRGENCY PHONE VOLUME TOO LOW, ADJUST. CAR OPERATING PANEL KEY SWITCHES LABELS WORN, PROVIDE NEW LABELS.
#39156874P
Nov 20, 2025
IN VIOLATION
$625
Aug 5, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED HOLE PENETRATIONS THROUGHOUT SPRINKLER CONTROL VALVE ROOMS AND BASEMENT
#39156154R
May 21, 2026
IN VIOLATION
$2,500
Aug 5, 2025Unknown CLASS - 1
FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED NO SECONDARY GROUNDING ELECTRODE. LOCATED IN WATERMAIN ROOM AND THROUGHOUT ELECTRIAL ROOMS., PROPERLY INSTALL GROUND ELECTRO
#39156156K
Nov 20, 2025
DEFAULT
$12,000
Aug 5, 2025Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSE
#39156155Z
May 21, 2026
IN VIOLATION
$2,500
Nov 26, 2024Elevators CLASS - 1
DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL OR EMAILTHE D.O.B. EIR@BUILDINGS.NYC.GOV. ELEVATOR DIVISION AT (212) 393-2144 FOR A RE
#39131389K
Jun 12, 2025
IN VIOLATION
$1,250
Aug 2, 2024Unknown CLASS - 2
I OBSERVED ON THE ROOF THE FAILURE TO INSTALL THE EQUIPMENT GROUND CONDUCTOR AS REQUIRED FOR PERMANENTLY INSTALLED EXTERIOR EQUIPMENT WITH THE USE OF FLEXIBLE WIRING. AS PER EC 350.60 PHOTOS TAKEN.; EC 350.60,
#39120800H
Jun 12, 2025
IN VIOLATION
$800
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE BASEMENT WATER METER ROOM THE ELECTRICAL SERVICE GROUND IN A STATE OF CORROSION, THE CABLE RACEWAY THE TERMINAL LUG AND THE WIRE WERE SHOWING VARIOUS STATES OF RUST. AS PER EC 110.11 ALL ELECT
#39120799J
Jun 12, 2025
IN VIOLATION
$1,600
Aug 2, 2024Unknown CLASS - 1
I OBSERVED ON FLOORS# 3,6,9,12,&15 THE INSTALLATION OF A DATA CABINET TO SUPPLY WIFI THROUGHOUT THE BUILDING, AS PER EC CODE 110.25 THE ELECTRICAL CLOSET SHALL BE DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT
#39120801J
Jun 12, 2025
IN VIOLATION
$1,200
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE ELECTRICAL CLOSETS THE INSTALLATION OF BRANCH CIRCUIT WIRING TO AND RECEPTACLES IN THE DATA CABINETS INSTALLED IN THE ELECTRICAL CLOSETS. NO PERMIT ON FILE IN DOB RECORDS COVERS THIS WORK., OB
#39120797X
Jun 12, 2025
IN VIOLATION
$1,600
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE RESTROOMS ON THE 1ST AND 2ND FLOORS DEFECTIVE GFCI OUTLETS IN USE. ALSO NOTED NO TAMPER RESISTANT OUTLETS IN HALLWAY ACCESSIBLE TO THE CHILDREN AND EXPOSED, ENERGIZED WIRING IN USE IN THE BASE
#39120802L
Dec 12, 2024
IN VIOLATION
$1,600
DOB (0)

None open.

DOB NOW Safety (8)
IssuedViolationStatus
Oct 28, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 28, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 28, 2026AEUHAZ FTC-AEU-HAZ
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Feb 22, 2022Facades FISPNRF
FAILED TO FILE FISP CYCLE 9A TECHNICAL REPORT BY 02/21/2022
Active
Feb 17, 2017Facades FISP
CYCLE 8A UNSAFE REPORT FILED
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 28, 2026DOB SafetyAEUHAZ: Open
Oct 28, 2026DOB SafetyAEUHAZ: Open
Oct 28, 2026DOB SafetyAEUHAZ: Open
Aug 13, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED THROUGHOUT THE BUILDING, MULTIPLE AUTOMATIC SPRINKLER HEADS WERE OBSERVED OBSTRUCTED. MULTIPLE SPRINKLER HEADS WERE OBSERVED WITH THEIR ESCUTCHEONS/CAPS PAINTED AND OR MISSINGOpen
Aug 13, 2026ECBUnknown: ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE BASEMENT 4 NEW 200 AMP DISCONNECT SW AND 1 1600 AMP DISTRIBUTION INSTALLED WITH BX RISERS. ALSO IN LOBBY AND BASEMENT HUNG ELECTRIC HEATERS INSTALLED WITH BX ANOpen
Aug 13, 2026ECBElevators: CLASS 1: 1. DLM MALFUNCTIONING AND NOT PROVIDING REQUIRED DOOR LOCK MONITORING. AS PER ASME A17.1 2.12. REMEDY: REPAIR DLM TO RESTORE PROPER MONITORING. CLASS 2: 2. CAR PRODUCES WHISTLING NOISE WHILE TRAVELING.Open
Aug 13, 2026ECBUnknown: UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERVED IN THE MAIN LOBBY AND BACK STORAGE AREA EXPOSED BX AND SJ CORD FEEDING HUNG HEATERS SJ COROpen
Aug 13, 2026ECBElevators: CLASS 1 C/U: 1. COMPENSATION CHAIN DRAGGING ON PIT FLOOR, CREATING HAZARDOUS INTERFERENCE WITH PIT EQUIPMENT. AS PER ASME A17.1 2.2. REMEDY: ADJUST AND SECURE COMPENSATION CHAIN TO MAINTAIN COMPLIANT FLOOR CLEAClosed
Aug 13, 2026ECBUnknown: UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES. OBSERVED THRU OUT HALLWAYS AND CHILDREN PLAY ROOM NO INSTALLATION OF TAMPER RESISTANT RECEPTACLES AND IN THE MECHANICAL RMS NO GOpen
Aug 13, 2026ECBConstruction: AT THE TIME OF INSPECTION OBSERVED ON THE ROOF ON THE COOLING TOWER UNIT A CRACKED VALVE ALSO PIPE CONNECTION MADE WITH FERNCO COUPLES . MC 908.1 - COOLING TOWERS: COOLING TOWERS SHALL BE INSTALLED IN ACCORDANCOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 6:09 AM ET. BBL 1008947505.