Bronx · Block 2761 · Lot 43 · 10474

1225 Seneca Avenue

5 floors · 75 apartments · 64,315 sq ft · built 1926 · class C1 · owner of record: Nyc Department Of Homeless Services

42open violations
$0ECB/OATH penalties owed
3HPD class C (immediately hazardous)
Overdueto Annual property registration

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual property registration Applies
HPD registration · September 1 each year
What this is

Residential buildings with three or more units, and one- and two-family homes the owner doesn't occupy, register with HPD every year ($13 fee). An unregistered building can't start a nonpayment case in Housing Court and faces civil penalties. Agency page

OverdueRegistration expired 1994-05-31
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 67 days
Keep the report on file (not filed with DOB)
Bedbug annual filing Applies
Local Law 69 · December 1 to 31 each year
What this is

Owners of multiple dwellings file their bedbug infestation history for the prior year with HPD and post or distribute it to tenants. Agency page

Dec 31, 2026
in 67 days
Annual
Annual boiler inspection (4 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-07-22 (Accepted). Agency page

Dec 31, 2026
in 67 days
1 of 4 without an accepted 2026 report yet
Annual notice: window guards and lead paint Applies
HPD / Health Code · January 1 to 16 each year
What this is

Deliver the annual notice to every unit asking whether a child lives there (window guards for children 10 and under; lead paint for children under 6 in pre-1960 buildings), then follow up on units that don't return it by mid-February. Agency page

Jan 16, 2027
in 83 days
Annual
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 64,315 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 188 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 188 days
Annual filing
Gas piping inspection (2029 cycle) Likely applies
Local Law 152 · During 2029
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 2 is on the 2029 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2029
in 1163 days
Next cycle year 2029
Energy audit and retro-commissioning (2031) Likely applies
Local Law 87 · Calendar year 2031
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2761). Agency page

Dec 31, 2031
in 1893 days
Next due 2031

Open violations

ECB / OATH (29)
IssuedViolationHearingBalance
Jun 8, 2026Unknown CLASS - 1
ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED IN THE MAIN ELECTRICAL RM THE STORAGE OF BUILDING MATERIALS LADDER, BROOMS BLACK TRASH BAGS FILLED WITH TRASH AND ELECTRICAL C
#39191638R
Jul 10, 2026
POP/IN-VIO
$0
Jun 8, 2026Unknown CLASS - 1
ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE MAIN ELECTRICAL ONE NEW PANEL INSTALLED 20/40 CKT, THAT REPLACED A EXISTING PANEL. IN THE MAIN BOILER RM ONE NEW WATER BOOSTER PUMP INSTALLED THAT REPLACED EXIS
#39191636N
Jul 10, 2026
POP/IN-VIO
$0
Jun 8, 2026Construction CLASS - 1
3 BOILERS NOT WOKING, RESTROOMS NOT EQUIPED WITH OPEN ENDED TOILET SEATS.PER PC .420.3 WATER CLOSETS SHALL BE EQUIPPED WITH SEATS OF SMOOTH, NONABSORBENT MATERIAL. ALL SEATS OF WATER CLOSETS PROVIDED TOILET SEA
#39191699K
Jul 10, 2026
POP/IN-VIO
$0
Jun 8, 2026Unknown CLASS - 1
FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT. OBSERVED IN THE ELEVATOR MACHINE RM THE DISCONNECT SW THE FUSES WAS INCORRECTLY SIZED FOR THE FOR THE LOAD FEEDERS. THAT ARE #12 AWG SHOULD BE FUSED AT 20 AM
#39191637P
Jul 10, 2026
POP/IN-VIO
$0
Jun 13, 2025Construction CLASS - 1
AT TIME OF INSPECTION I OBSERVED EMERGENCY EGRESS WAY BLOCKED BY BUILDING MAINTENANCE SUPPLIES AND PARTS. ALSO FIRE ESCAPE DROP LADDERS IN BACK OF BUILDING AT EXPOSURE 3 BLOCKED BY MATTRESS AND REFUSE, REMOVE O
#39151012Z
Jul 4, 2025
POP/IN-VIO
$0
Jun 10, 2025Construction CLASS - 2
FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPARTMENT OF BUILDINGS FOR VIOLATION#39086086N, FILE A CERTIFICATE OF CORRECTION; CORRECT ALL VIOLATING CONDITION/SU
#39150565Y
Jul 4, 2025
POP/IN-VIO
$0
Jun 10, 2025Boilers CLASS - 2
I FOUND A HYDROTHERM MR1500BP A MODULAR BOILER WITH TWO BOILER OF THE SIX ARE DISCONNECTED AND A THIRD BOILER IS LEAKING/ THE FRESH AIR MECHANICAL LOUVER IS NOT WORKING PROPELY/CORRECT ALL VIOLATING CONDITION/S
#39150633R
Jul 4, 2025
POP/IN-VIO
$0
Jun 9, 2025Elevators CLASS - 1
: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY
#39150424K
Jul 4, 2025
POP/IN-VIO
$0
Oct 2, 2023Construction CLASS - 2
-CRACKS ON FACADE AND OBOVE WINDOW LENTALS, LEADING TO INTERIOR LEAKS LOCATED AT EXPOSURE 2 & 3 SIDE., REPAIR AND/OR REPLACE
#39096216L
Oct 10, 2023
POP/IN-VIO
$0
Oct 2, 2023Construction CLASS - 2
-SIGNIFICATE BUBLING LOCATED ON ROOF., REPAIR AND/OR REPLACE
#39096213X
Oct 10, 2023
POP/IN-VIO
$0
Oct 2, 2023Construction CLASS - 2
OBSERVED ACTIVE LEAK IN THE BOILER ROOM ON 1 1/4 BALL VALVE ALSO ACTIVE LEAK IN STAFF RESTROOM LOCATED ON GROUND FLOOR. AS PER 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE
#39096245K
Oct 10, 2023
POP/IN-VIO
$0
Oct 2, 2023Construction CLASS - 2
-EMERGENCY FENCE EXIT DOORS AND HARDWARE DO NOT OPEN AND OR UNLATCH, LOCATED AT EXSPOSURE 2 & 3, PROVIDE LEGAL HARDWARE
#39096214H
Oct 10, 2023
POP/IN-VIO
$0
Oct 2, 2023Elevators CLASS - 1
97-X-17=ENTIRE DEVICE INOPERATIVE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY, 11-02, REMEDY REPAIR AND RESTORE DEVICE BACK TO SERVICE AND NOTIFY NYC DO
#38274982N
Oct 27, 2023
POP/IN-VIO
$0
Oct 2, 2023Construction CLASS - 2
-EMERGENCY EXITS DOORS, DO NOT SELF-CLOSE LOCATED AT OFFICE SPACE EXPOSURE 1 AND BOILER ROOM MECHANICAL ROOM. ALSO, EMERGENCY DOOR WINDOW IS BROKEN/CRACKED., REPAIR/REPLACE DOOR
#39096215J
Oct 10, 2023
POP/IN-VIO
$0
May 17, 2023Construction CLASS - 2
OBSERVED IN BASEMENT/CELLAR UNAPPROVED COUPLING INSTALLED ON PIPPING. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PROPER OPERATING CONDITION IN AC
#39086473N
May 29, 2023
POP/IN-VIO
$0
May 11, 2023Boilers CLASS - 2
AS PER ONE HYDROTHERM BOILER 02 IN CELLAR; NO NAME PLATE-HEAT STRESS FROM FLAME ROLL-OUT ON FRONT COVER-PRESSURE RANGE IN COMPOUND GAGE NOT AS PER BOILER CODE.
#39086084J
May 29, 2023
POP/IN-VIO
$0
May 11, 2023Elevators CLASS - 1
97X10,2X10,1X10,AND 5L10 ENTIRE DEVICE INOPERATIVE MUST REPAIR.ALARM BELL INOPERATIVE ALARM BELL ON STOP SWITCH INOPERATIVE.CAR DOOR GATE DEFECTIVE OFF SADDLE STUCK MUST REPAIR.
#38274826L
Aug 18, 2023
POP/IN-VIO
$0
May 11, 2023Boilers CLASS - 2
PRESSURE RANGE IN COMPOUND GAGE NOT AS PER BOILER CODE-INSULATED COVERING SHOWING SIGNS OF FLAME ROLL-OUT AND HEAT STRESS-INSULATED PANEL MISSING FROM BOILER-ELECTRICAL BOX COVER MISSING.
#39086085L
May 29, 2023
POP/IN-VIO
$0
May 11, 2023Boilers CLASS - 2
AS PER ONE WEIL MCLAIN LGB-9 HOT WATER HEATING BOILER IN BASEMENT. PERMIT NO. X00242139. BOILER NOT REGISTERED., MAINTAIN BOILER; CORRECT VIOLATING CONDITIONS AND CALL FOR AN INSPECTION.
#39086086N
May 29, 2023
POP/IN-VIO
$0
Oct 18, 2021Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING.NOTED:OBSERVED AT ROOF BULKHEAD IN THE "A" BUILDING EXIT DOOR DOES NOT SELF-CLOSE AND REMAINS OPEN WHEN PUSHED,ALSO ALL FINE PROOF SELF CLOSING DOORS IN THE "A" AND "B" BUILDINGS AT A
#35635692R
Jan 21, 2022
POP/IN-VIO
$0
Oct 18, 2021Construction CLASS - 2
I OBSERVED IN THE BOILER ROOM B BOILER IS LEAKING PROFUSELY FROM REAR., REPAIR AND/OR REPLACE
#39049737P
Nov 12, 2021
POP/IN-VIO
$0
Oct 13, 2021Boilers CLASS - 2
FOUND ONE WEIL MCLAIN LGB-9 NOT REGISTERED ON DOB RECORDS,, MAINTAIN BOILER; RE-FILE PERMIT AND CALL FOR INSPECTION.
#39049206X
Oct 15, 2021
POP/IN-VIO
$0
Oct 13, 2021Boilers CLASS - 2
FOUND BOILER B, ON THIS BANK OF BOILERS LEAKING BETWEEN SECTION, REPAIR OR REPLACE, ALSO SAFETY RELIEF VALVE ON SAME BOILER LEAKING.
#39049205Y
Oct 15, 2021
POP/IN-VIO
$0
Jan 6, 2021Boilers CLASS - 2
SAFETY LEAKING ON BOILER ON LEFT SIDE SECOND FROM THE BACK OF BOILER.
#39034399J
Jan 22, 2021
POP/IN-VIO
$0
Oct 31, 2019Construction CLASS - 2
NOTED: OBSERVED THROUGHOUT BUILDINGS A AND B AT VARIOUS FLOORS, FIREPROOF SELF-CLOSING CORRIDOR DOORS ARE RACKED AND OUT OF SQUARE AND REMAIN AJAR DUE TO KNOCKING ON DOOR JAMB, ALSO AT CELLAR IN BUILDING A,B AN
#39012086L
Nov 12, 2019
POP/IN-VIO
$0
May 10, 2019Boilers CLASS - 2
CORROSION ON PIPING, ELECTRICAL BOX COVER FALLING OFF, PRESSURE RELIEF VALVES LEAKING, HOT WATER SUPPLY HEADER LEAKING; CORRECT ALL VIOLATING CONDITIONS , SUBMIT A CERTIFICATE OF CORRECTION.
#39002821J
May 15, 2019
POP/IN-VIO
$0
May 10, 2019Boilers CLASS - 2
AS PER TWO HYDROTHERM BOILERS AT ABOVE LOCATION AND AS PER DOB RECORDS. FAILURE TO FILE A COMPLETE BOILER SAFETY, INITIAL INSPECTION REPORT; SUBMIT A COMPLETE, BOILER SAFETY, INITIAL INSPECTION REPORT.
#39002822L
May 15, 2019
POP/IN-VIO
$0
Oct 6, 2017Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. RE-ISSUE #351128388Y ISSUED: 02/11/2016. NOTE: SPALLING, CRACKS, AND WATER INTRUSION THROUGHOUT FACADE ALSO AT ROOF LEVEL WATER DAMAGE TO ROOF MEMBRANE C
#35293783P
Jan 5, 2018
POP/IN-VIO
$0
Feb 11, 2016Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.SPALLING,CRACKS AND WATER INTRUSION THROUGHOUT FACADE.ALSO AT ROOF BE() WATER AINTRUSTION VISIBLE AT TOP FLOOR APTS, WINDOWS THROUGHOUT LEAKING NOT CLOSING PROP
#35128388X
Apr 1, 2016
POP/IN-VIO
$0
DOB (0)

None open.

DOB NOW Safety (2)
IssuedViolationStatus
Sep 18, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle B (premises is in Community District 2)
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
HPD (11) · C 3 · B 4 · A 4
IssuedClassViolationCorrect by
Aug 19, 2019CApt 3L · § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) WEST WALL, 1st WINDOW SASH FROM WEST AT NORTH WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 3L, 5th STORY, 1st APARTSep 16, 2019
Aug 19, 2019CApt 3L · § 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PRESUMED LEAD PAINT THAT IS PEELING OR ON A DETERIORATED SUBSURFACE USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) NORTH WALL IN THE 2nd ROOM FROM EAST LOCATED AT APT 3L, 5th STORY, 1st APARTMENT FROM WEST AT NORTHSep 16, 2019
Jul 28, 2006AApt 2 · D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE TILE WALL 1 STY NORTH EAST APT 2 BATHROOM NORTH SECTION. , SECTION '' ''Aug 1, 1982
Jul 28, 2006AApt 1 · D26-10.01 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE TILE WALL 1ST STY APT 1 BATHROOM. , SECTION '' ''Aug 1, 1982
Jul 28, 2006AApt 1 · D26-12.01 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT CEILINGS & WALLS ENTIRE 1ST STY APT 1. , SECTION '' ''Aug 1, 1982
Jul 28, 2006AApt 1 · D26-10.01 ADM CODE PROPERLY REPAIR THE BROKEN OR DEFECTIVE ELECTRIC LIGHT CEILING FIXTURE 1ST STY APT 1 FOYER. , SECTION '' ''Aug 1, 1982
Aug 10, 2000BApt 1 · D26-10.01 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILINGS & WALLS ENTIRE 1ST STY APT 1. , SECTION '' ''Aug 1, 1982
Aug 10, 2000BApt 1 · D26-16.01 ADM CODE REPAIR BY CLOSING SO AS TO BE GAS-TIGHT ALL OPENINGS IN THE WASTE LINE OF KITCHEN SINK 1ST STY APT 1. , SECTION '' ''Aug 1, 1982
Aug 10, 2000CApt 9A · D26-17.07 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES 1ST STY NORTH FRONT APT 9A KITCHEN & BATHROOM ER1. , SECTION '' ''Aug 1, 1982
Aug 10, 2000BApt 7C · D26-10.01 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING 4 STY SOUTH WEST APT 7C BATHROOM. , SECTION '' ''Aug 1, 1982
Aug 10, 2000BApt 7C · D26-10.01 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR CEILING & WALLS 4 STY REAR SOUTH APT 7C BATHROOM SOUTH SECTION. LOCATED AT APT 7CAug 1, 1982

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 25, 2026, 8:40 AM ET. BBL 2027610043.

Look up another building