Queens · Block 12335 · Lot 49 · 11434

116-01 Guy R Brewer Blvd

6 floors · 189,693 sq ft · built 2001 · class W1 · owner of record: Nyc Department Of Education

60open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
188dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 67 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 189,693 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 188 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 188 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 432 days
Next cycle year 2027
Energy audit and retro-commissioning (2035) Likely applies
Local Law 87 · Calendar year 2035
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 12335). Agency page

Dec 31, 2035
in 3354 days
Next due 2035
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-16 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (20)
IssuedViolationHearingBalance
May 27, 2026Construction CLASS - 2
REISSUE ON ECB#35725568Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:WATER PENETRATION THROUGH WINDOW AND WINDOW MULLION SEALS AT EXPOSURES#1 AND 4 CORNER CAUSING WATER DAMAGE ON CEILING TILES A
#35733067K
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:FIRE RATEDCLASSROOMS AND SMOKE DOORS NOT SELF-CLOSING PROPERLY DUE TO BINDING,MISSING AND OR FAULTY HARDWARE ON CLASSROOMS 507,501,405 AND 210 INCLUDI
#35733071N
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
REISSUE ON ECB#35725567R FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:MISSING ROOFING MATERIALS WITH HOLES ON SEVERAL LOCATIONS THROUGHOUT ROOF PLAYGROUND CAUSING WATER DAMAGE AND LEAKS INTO ROOM
#35733068M
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:MISSING ROOF WALL FLASHING IN A FEW LOCATIONS ON 4TH FLOOR INTERMEDIATE ROOF LAYING AND DETACHED FROM ROOF WALL OBSERVED UPON INSPECTION.REM:REPAIR AN
#35733074Z
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:MISSING WIRE MESH GLASS FIRE HOSE CABINETS AT STAIR D 1ST FL,STAIR A 2ND FL AND 4TH FLOOR STAIR A OBSERVED UPON INSPECTION.REM:REPAIR AND/OR REPLACE.
#35733073R
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
REISSUE ON ECB#35725566P EXIT DOOR NOT SELF-CLOSING.NOTED:EMERGENCY EXTERIOR EXIT DOORS NOT SELF-CLOSING PROPERLY DUE TO BINDING MISSING ANDOR FAULTY OR RUSTED DOORS ON EXTERIOR DOORS AT EXIT 7 FIRST FL,EXIT 9
#35733069Y
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:MISSING STAIRWELL HANDRAILS ON STAIR E 2ND FL,STAIR C 5TH FL,STAIR C 4TH FL,4TH FL STAIR E AND 4TH FL STAIR A OBSERVED UPON INSPECTION.REM:REPAIR AND/
#35733072P
Jul 15, 2026
POP/IN-VIO
$0
May 27, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371.NOTED:ILLEGAL KICK STOPSINSTALLED ON CLASSROOMS,SMOKE AND EXTERIOR DOORS ON CLASSROOMS 137 1ST
#35733070L
Jul 15, 2026
POP/IN-VIO
$0
Oct 1, 2025Construction CLASS - 2
REISSUE: 35677540N-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ROOF ABOVE #610 HAS LARGE HOLE IN ROOF MATERIALS AND AROUND STACK GOING TO ROOF. REMEDY: COMPLY WITH CODE.
#35725567R
Oct 27, 2025
POP/IN-VIO
$0
Oct 1, 2025Construction CLASS - 2
REISSUE: 35665181M-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. WATER PENETRATION THROUGH WINDOWS AND CORNER OF EXP: 1, 4 AFFECTING CLASSROOM 447, 347, 247. REMEDY: COMPLY WITH CODE.
#35725568Z
Oct 27, 2025
POP/IN-VIO
$0
Oct 1, 2025Construction CLASS - 2
REISSUE: 35677541P-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. EXIT DOORS AT EXIT #4, 7, 19 ARE RUSTED AND NOT CLOSING PROPERLY. REMEDY: COMPLY WITH CODE.
#35725566P
Oct 27, 2025
POP/IN-VIO
$0
Oct 23, 2024Elevators CLASS - 1
: NO DOOR LOCK MONITORING INSTALLED ON THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYC BUILDING CODE. THIS IS A FEATURE WHICH ENSURES PASSENGER SAFETY. FILE APPLICATION, INSTALL DOOR LOCK
#39128209R
Nov 20, 2024
POP/IN-VIO
$0
Aug 30, 2024Elevators CLASS - 1
NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY; FILE APPLICATION, INSTALL DLM A
#39123564Z
Oct 18, 2024
POP/IN-VIO
$0
Jun 28, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. EXIT 4 AND 7, 9DOORS AND DOOR FRAME RUSTED LARGE HOLES IN FRA,E AND DOORS. REMEDY: REPAIR AND/OR REPLACE.
#35677541P
Aug 16, 2024
POP/IN-VIO
$0
Jun 28, 2024Construction CLASS - 2
REISSUE. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SOME PARTS OF ROOF NOT FIXED AREA ABOVE ROOM 610A BOILER ROOMS LARGE HOLE LEFT OPEN AROUND STACK GOING TO ROOF. REMEDY: REPAIR AND/OR REPLACE.
#35677540N
Aug 16, 2024
POP/IN-VIO
$0
Aug 14, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED ROOF IN STATE OF DISREPAIR WITH HOLES AT VARIOUS LOCATIONS AT ROOF GYM THATSNOT IN USE. REPAIR AND/OR REPLACE.
#35665182Y
Nov 3, 2023
POP/IN-VIO
$0
Aug 14, 2023Construction CLASS - 2
REISSUED #35655335R. FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES. WATER PENETRATION THROUGH WINDOWS AND CORNER OF EXP. 1, 4 AFFECTING CLASS ROOM 447, 347, 247. REMEDY: REPAIR AND/OR REPLACE.
#35665181M
Nov 3, 2023
POP/IN-VIO
$0
Jun 8, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.REISSUE35561274P.OBSERVED CAILING PANEL DAMAGE DUE TO WATER PENETRATION@CAFETERIA.RM515,447,347,247.SEAL PENETRATION,REPAIR &OR REPLACE CEILING PANELS.
#35655332L
Sep 13, 2022
POP/IN-VIO
$0
Jun 8, 2022Construction CLASS - 2
FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES.WATER PENETRATION THRUWINDOWS@CORNER OF EXP1,4 AFFECTING CLASSRMS447,347,247.MAINTAIN WATERPROOFING@EXTERIOR WINDOWS.
#35655335R
Sep 13, 2022
POP/IN-VIO
$0
Aug 22, 2017Elevators CLASS - 2
52L14;59T07/52-L-14-SHORTEN HOIST ROPES;59-T-07-PROVIDE BRAKE TAG.
#38256791L
Nov 14, 2017
POP/IN-VIO
$0
DOB (2)
IssuedViolationStatus
Oct 16, 2020ELEVATOR

#9027/691746
DOB VIOLATION - ACTIVE
Oct 3, 2007ELEVATOR

#9444/220299
DOB VIOLATION - ACTIVE
DOB NOW Safety (38)
IssuedViolationStatus
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction
Active
Oct 10, 2025Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2019 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
Aug 11, 2023Elevators FTF-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Report
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 25, 2026, 2:34 PM ET. BBL 4123350049.