6 floors · 97,000 sq ft · built 1911 · class N2 · owner of record: Nyc Department Of Homeless Services
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 56 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 97,000 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 177 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 177 days | Annual filing |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 787 days | Next cycle year 2028 |
| Energy audit and retro-commissioning (2033) Likely applies Local Law 87 · Calendar year 2033 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 2613). Agency page | Dec 31, 2033 in 2613 days | Next due 2033 |
| Annual boiler inspection (2 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-06-30 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Oct 5, 2026 | Boilers CLASS - 2 FOUND SMOKE ALARM BYPASSED ON NUMBER ONE BOILER. FEDERAL/ FST250. CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION. #39206744J | Oct 30, 2026 POP/IN-VIO | $0 |
| Oct 20, 2025 | Construction CLASS - 2 OBSERVED FIRE DEPARTMENT CONNECTION CAP OUTSIDE NOT PROPERLY INSTALLED WITH DEBRIS INSIDE. PLASTIC PIPING ON 2 AND 3 FLOORS ON WASTE LINES UNDER THE SINKS. THROUGHOUT BUILDING NOT USING OPEN ENDED TOILET SEATS. #39164100L | Dec 23, 2025 POP/IN-VIO | $0 |
| Oct 20, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). AT T #39164115Y | Dec 23, 2025 POP/IN-VIO | $0 |
| May 15, 2025 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. BUILDING IS A 5STORY ASYLUM CORNER LOT. OBSERVED AT EXPOSURE 1, 2 CRACKED WINDOW SILLS BETWEEN FLOORS 2-3. AT EXPOSURE 4, ON 166 ST, OBSERVED 2 CRACKED WIN #35717036H | Jul 11, 2025 POP/IN-VIO | $0 |
| Mar 23, 2023 | Construction CLASS - 2 -SIGNS OF WATER PENETRATION AND STRUCTURAL DETERIORATION ON WALLS, CEILING, AND ON FLOOR LOCATED AT 4TH FLOOR EMERGENCY EXIT CORNER WALLS LEADING TO ROOF, (A SIDE) STAIRWELL/COIRRIDOR LEADING TO STORAGE CLOSETS #39082135M | Mar 27, 2023 POP/IN-VIO | $0 |
| Mar 23, 2023 | Construction CLASS - 2 OBSERVED ACTIVE WATER LEAK IN THE BOILER ROOM LOCATED AT BASEMENT/CELLAR ( CAST IRON STORM DRAIN)., REPAIR AND/OR REPLACE #39082128Y | Mar 27, 2023 POP/IN-VIO | $0 |
| Mar 22, 2023 | Boilers CLASS - 2 FLAME GLASS MISSING-GAS REGULATOR VENT NOT CAPPED-PRV DISCH PIPES MISSING, BLRS 1 AND 2-THREADS ON DISCHARGE PIPE FOR PRV ON HW TANK-EXPOSED ELECT ON MOTORIZED DAMPER-CONTROL COVERS MISSING ON HW RETURN PIPES-N #39082037Z | Mar 27, 2023 POP/IN-VIO | $0 |
| Apr 6, 2022 | Construction CLASS - 2 NOTED: OBSERVED AT GENERATOR ROOM, CRACKS, SPALLING AND MISSING CEMENT THROUGHOUT CEILING., REPAIR AND/OR REPLACE #39059661R | Apr 19, 2022 POP/IN-VIO | $0 |
| Apr 6, 2022 | Construction CLASS - 2 NOTED: ROOFING MATERIAL OVER "DRILL ROOM" HAS BECOME POROUS AT VARIOUS LOCATIONS ALLOWING WATER TO ENTER THE BUILDING INTO THE "DRILL ROOM", REPAIR AND/OR REPLACE #39059664M | Apr 19, 2022 POP/IN-VIO | $0 |
| Apr 6, 2022 | Construction CLASS - 2 NOTED: OBSERVED AT ROOF, PARAPET WALL BRICKS ARE MISSING MORTAR AT THE JOINT AND COPING STONES., REPAIR AND/OR REPLACE #39059663K | Apr 19, 2022 POP/IN-VIO | $0 |
| Jan 21, 2022 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED AT TIME OFMY INSPECTION,I OBSERVED AT CELLAR LEVEL IN STORAGE BY BOXES IN SPRINKLER RIIM IN ROOF COLUMN CRACKS IN MASONRYWORK.NO WATER DAMAGE OBSERVE #35644214R | Apr 29, 2022 POP/IN-VIO | $0 |
| Oct 8, 2021 | Construction CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.FAILURETO CORRECT & CERTIFY SUMMONS ECB#39011944Y,ECB#39011945X & ECB#35583878N.AN UNLAWFUL ACTS.FAILURE TO COMPLY W/CODE.MISCELLANEOUS VIOLATION O #35634211M | Jan 7, 2022 POP/IN-VIO | $0 |
| Oct 1, 2021 | Construction CLASS - 1 REISSUE:35587055K DATE OF ISSUE:08/18/21 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE:AT CELLAR LEVEL IN STORAGE BY BOXES AL OF AREA.IN SPRINKLER ROOM.IN ROOF, COLUM CRAKS IN MASONRY WORK NO WATER #35592088N | Jan 7, 2022 POP/IN-VIO | $0 |
| Aug 18, 2021 | Construction CLASS - 1 REISSUE 35558025R FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTE:AT CELLAR LEVEL IN STORAGE/SPRINKLER ROOM CRACKS IN MASONRY CEILING WITH EVIDENCE OF WATER DAMAGE TO STORED MATERIAL.REMEDY:REPAIR A #35587055K | Dec 3, 2021 POP/IN-VIO | $0 |
| Jul 31, 2021 | Construction CLASS - 1 AN UNLAWFUL ACT - FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS #39011945X. REMEDY: COMPLY WITHEC CODE #35583878N | Oct 29, 2021 POP/IN-VIO | $0 |
| Jul 3, 2021 | Construction CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY WITH COMMISSIONERS ORDERS. RECORDS INDICATE NO APP WAS MADE TO CORRECT OR CERTIFY ECB #39011944Y & 39011945X. REMEDY: COMPLY WITH COMMISSIONERS ORDERS #35583676P | Sep 17, 2021 POP/IN-VIO | $0 |
| Jun 28, 2021 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTE:AT CELLAR LEVELIN STORAGE -SPRINKLER ROOM CRACKS IN MASONRY CEILING W/EVIDENCE OF WATER DAMAGE.REMEDY:REPAIR &/OR REPLACE. #35558025R | Oct 29, 2021 POP/IN-VIO | $0 |
| Jun 5, 2021 | Construction CLASS - 1 AN UNLAWFUL ACT-FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS #353600872.REMEDY:COMPLY WITH EC CODE. #35476793K | Aug 20, 2021 POP/IN-VIO | $0 |
| May 21, 2021 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN OCDE COMPLIANT MANNER AT THE TIME OF MY INSPECTION NOTED AT (GROUND) FLOOR STORAGE ROOM MULTIPLE CRACKS IN MASONRY CEILING WITH EVIDENCE OF WATER PENETRATION COMPLY WITH CODE #35561225Z | Sep 3, 2021 POP/IN-VIO | $0 |
| May 5, 2021 | Construction CLASS - 1 UNLAWFUL ACTS.FAILURE TO COMPLY WITH ORDER OF THE COMMISIONER.RECORDS INDICATE NO APPLICATION WAS MADE TO CERTIFY AND CORRECT ECB #35360049H.REMEDY:COMPLY WITH COMMISSIONER'S ORDERS #35547841L | Jul 30, 2021 POP/IN-VIO | $0 |
| Mar 31, 2021 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT TIME OF INSPECTION OBSERVED AT CELLAR LEVEL STORAGE ROOM DETERIORATING CEILING AND EXCESSIVE STORAGE CREATING A FIRE HAZARD. REMEDY:REPAIR/REPLACE #35548148H | Jul 2, 2021 POP/IN-VIO | $0 |
| Dec 14, 2020 | Boilers CLASS - 3 FOUND CIRCULATING PUMP LEAKING IN BOILER ROOM. #39033387H | Dec 30, 2020 POP/IN-VIO | $0 |
| Mar 27, 2020 | Construction CLASS - 1 UNLAWFUL ACTS FAILURE TO COMPLY W/ COMMISSIONERS ORDER. RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT OR CERTIFY ECB #'S 35360049H, 39011944Y, 39011945X AND 35360087Z. REMEDY:COMPLY W/ COMMISSIONERS ORDER #35460958N | Jun 19, 2020 POP/IN-VIO | $0 |
| Mar 13, 2020 | Construction CLASS - 1 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN BASEMENT LVL A ROOM @THE RIGHT OF THE LOADING DOCK WITH BOX FULLOF DTORED FILE. THE ARCHED MASONRY CEILING & COLUMNS CRACK & LOOSE MORTAR IN NEED #35475938H | Sep 4, 2020 POP/IN-VIO | $0 |
| Feb 4, 2020 | Construction CLASS - 1 AN UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.FAILURE TO CORRECT AND CERTIFY SUMMONS #35360049H,39011944Y,AND 39011945X.REM:COMPLY WITH EC CODE/OBTAIN PERMIT. #35360087Z | Mar 20, 2020 POP/IN-VIO | $0 |
| Jan 13, 2020 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED:AT TIME OF INSPECTION I OBSERVED AT CELLAR LEVEL SEVERAL ROOM CEMENT COLUMNS HAVE CRACKS OR MISSING CEMENT ALSO CEMENT ARCHED CEILING HAS CRACK THROU #35465565P | Mar 6, 2020 POP/IN-VIO | $0 |
| Dec 19, 2019 | Construction CLASS - 1 UNLAWFUL ACTS. FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. IN 11/12/19,2 ELECTRICAL VIOS WAS ISSUE TO THE RESPONDENT. THE RESPONDENT FAILED TO COMPLY W/ (NYC)ELECTRICAL CODE#400.8,250.4 (ECB'S)#39011944Y #35360049H | Feb 21, 2020 POP/IN-VIO | $0 |
| Nov 26, 2019 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTE AT CELLAR LEVEL FILE/ARCHIVE ROOM SEVERAL CEMENT COLUMNS HAVE CRACK OR MISSING CEMENT ALSO CEMENT ARCHED CEILING HAS CRACKS THROUGHOUT ENTIRE ROOM. RE #35459403L | Jan 17, 2020 POP/IN-VIO | $0 |
| Oct 29, 2019 | Unknown CLASS - 1 I OBSERVED IN THE RECREATION ROOM AND KITCHEN, FLEXIBLE EXTENSION CORDS BEING USED AS A PERMANENT WIRING METHOD POWERING APPLIANCES. VIOLATING SECTION 400.8 IN THE NATIONAL ELECTRICAL CODE ; 400.8, COMPLY WITH #39011944Y | Nov 12, 2019 POP/IN-VIO | $0 |
| Oct 29, 2019 | Unknown CLASS - 1 I OBSERVED IN THE CELLAR THE GROUNDING ELECTRODE CONDUCTOR WATER CLAMP EXTREMELY DETERIORATED TO THE POINT OF DISREPAIR. GROUNDING ELECTRODE CONDUCTOR WATER CLAMP IS CURRENTLY NOT SERVING ITS INTENDED PURPOSE. #39011945X | Nov 12, 2019 POP/IN-VIO | $0 |
| Oct 29, 2019 | Unknown CLASS - 2 I OBSERVED IN THE COMMERCIAL KITCHEN, REGULAR DUPLEX RECEPTACLES THAT ARE NOT GFCI PROTECTED, INSTALL GFC1 PROTECTION #39011946H | Nov 12, 2019 POP/IN-VIO | $0 |
| Oct 18, 2019 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED:AT TIME OF INSPECTION I OBSERVED AT CELLAR FILE/ARCHIVE ROOM CEMENT COLUMNS ARECRACKED IN SEVERAL AREA OF THE COLUMNS ALSO CEMENT CEILING CRACKED IN #35459135Y | Dec 20, 2019 POP/IN-VIO | $0 |
| Jul 13, 2019 | Construction CLASS - 2 FAIURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/ VIOLATION # 35381164Y ISSUED ON 5/1/19 AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. REMEDY:COMPLY WITH #35401152Y | Sep 6, 2019 POP/IN-VIO | $0 |
| May 1, 2019 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED: AT CELLAR IN FILE /ARCHIVE ROOM CEMENT COLUMNS ARE CRACKED IN SEVERAL AREAS OF COLUMNS. CEMENT CEILING ALSO CRACKED IN SEVERAL AREAS THROUGH #35381164X | Jul 5, 2019 POP/IN-VIO | $0 |
| Nov 1, 2018 | Construction CLASS - 2 OPERATION OF A PLACE OF ASSEMBLY WITHOUT A CURRENT CERTIFICATE OF OPERATION.NOTED: OBSERVED AT CATERING-ELEVEN (11) TABLES EACH SEATING 12 PERSONS FOR A TOTAL OF 132 PERSONS NO PLACE OF ASSEMBLY CERTIFICATE #35372207M | Jan 4, 2019 POP/IN-VIO | $0 |
| Sep 11, 2018 | Boilers CLASS - 2 50A,50B,50C,50D,50E,50F,50G,50H-AS PER CLASS 2 (B254) 28-301.1. FAILURE TO MAINTAIN. 50A)HOT WATER COIL SAFETY VALVE DRAIN NOT PIPED. 50B)BOILER #2 ACCESS DOOR AND FIRE DOOR MISSING DOG LEGS. 50C)2ND MEANS OF E #32097765Y | Nov 30, 2018 POP/IN-VIO | $0 |
| May 16, 2018 | Unknown CLASS - 2 UNSUITABLE USE OF MATERIALS. OBSERVED IN KITCHEN, SAFETY DISCONNECT SWITCH DIRECTLY ABOVE WASHING DEEP SINKS IS NOT SUITABLE FOR WET LOCATIONS. REM: COMPLY W/ EC CODE. #35331833Z | Jul 20, 2018 POP/IN-VIO | $0 |
| May 11, 2018 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT 5TH STORY NORTH SECTION, THERE IS A HOLE APPROX 2' X 2' AT CEILING. ALSO, IN CELLAR, FILE ROOM, THERE ARE CRACKS IN THE CEILING IN VARIOUS LOCATI #35332076P | Jul 20, 2018 POP/IN-VIO | $0 |
| Apr 27, 2018 | Boilers CLASS - 2 B254,50A,50B,50C,50D,50E,50F,50G. AS PER CLASS 2 (B254) 28.301.1 FAIL URE TO MAINTAIN. 50A-HOT WATER COIL RELIEF VALVES W/O DRAIN PIPES. #01 AND #02; 50B-ELECTRICAL COVER FOR MCDONNELL MILLER SWITCH MISSING #32096760K | Jul 20, 2018 POP/IN-VIO | $0 |
| Sep 26, 2017 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES NOTED:OBSEERVED THROUGHOUT ROOF @VARIOUS LOCNS AROUND PARAPET WALL,LOOSE @DETACHED FLASHINGS THROUGHOUT.REM:MAINTAIN EXTERIOR BLDG WALL. #35290615M | Dec 15, 2017 POP/IN-VIO | $0 |
| May 31, 2017 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: AT TIME OF INSPECTION I OBSERVED ON THE ROOF AT VARIOUS LOCATIONS,LOOSE & DETACHED PARAPET WALL FLASHINGS. REMEDY: MAINTAIN EXTERIOR BLDG WALL. #35267495L | Aug 18, 2017 POP/IN-VIO | $0 |
| Issued | Violation | Status |
|---|---|---|
| Mar 20, 2026 | CONSTRUCTION FTC W/COMMISSIONER'S ORDER CONTROL#348224 DOB#051525PI20303SB DATED 05/15/25 REQUIRING OWNER TO SUBMIT A CORRECTIVE ACTION PLAN W/IN 30 DAYS OF DATE OF INSPECTION.ASO F TODAY 03/20/26 THE REQ'D CAP WAS NOT REC'D. IMMED COMPLY W/COMMISSIONER'S ORDER CONTROL#348244 VIO#051525PI20303SB #PI20301SB | DOB VIOLATION - ACTIVE |
| May 15, 2025 | CONSTRUCTION EMERGENCY WORK ORDER REQ'D. OBSVD SEVERLY HAZARDOUS CONTIONS @ EXP4 SUCH AS MASONRY CRACKS 2 CRACKED GLASS WINDOWS DETERIORATED MORTAR JOINTS @ WINDOW STONEHEADERS & CRACKED/SPALLING @ DECORATIVE COPING STONES @ MULT LOCATIONS. IMMED PROVIDE SAFETY MEASURES TO SECURE/PROT THE PUBLIC.INSTALL S/W SHED #PI20304SB | DOB VIOLATION - ACTIVE |
| May 15, 2025 | CONSTRUCTION CORRECTIVE ACTION PLAN REQ'D. OBSVD @ EXP1 ON FRANKLIN AVE 2 CRACKED/ SPALLED WINDOW SILLS ON 3FL. @ EXP4 ON 166 ST OBSVD 2 CRACKED GLASS WINDOWS BTWN FLR 2-3 A VERT MASONRY CRACKS BTWN 2-4. IMMED RETAIN REG DESIGN PROF TO EVAL ENTIRE BLDG & TO SUMBIT CORRECTIVE ACTION PLAN TO PROACTIVEINSP@BUILDING #PI20303SB | DOB VIOLATION - ACTIVE |
| May 24, 2005 | ELEVATOR #9444/129898 | DOB VIOLATION - ACTIVE |
None open.
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 5, 2026 | ECB | Boilers: FOUND SMOKE ALARM BYPASSED ON NUMBER ONE BOILER. FEDERAL/ FST250. CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION. | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 5, 2026, 8:25 PM ET. BBL 2026130001.