Brooklyn · Block 7629 · Lot 30 · 11210

1137 East 29 Street

3 floors · 178,911 sq ft · built 1951 · class W1 · owner of record: Nyc Department Of Parks And Recreation

26open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
164dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 43 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 178,911 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 164 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 164 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 14 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 408 days
Next cycle year 2027
Energy audit and retro-commissioning (2029) Likely applies
Local Law 87 · Calendar year 2029
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 7629). Agency page

Dec 31, 2029
in 1139 days
Next due 2029
Annual boiler inspection (3 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-05 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (13)
IssuedViolationHearingBalance
Jan 28, 2026Construction CLASS - 2
REISSUE: 356847897Y-FAILURE TO MAINTAIN BUILDING IN CODE-CLOSING MANNER. EXIT DOORS NOT SELF-CLOSING @ 1ST FLOOR EXIT #1 EXIT @4 DOORS ALSO.REMEDY: COMPLY WITH CODE.
#35725018Y
Mar 9, 2026
POP/IN-VIO
$0
Jan 28, 2026Construction CLASS - 2
REISSUE: 35684788M-FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ROOM DOORS @ 338, 332, 200 @ 3RD FL. AND GYM DOORS NOT SELF-CLOSING. REMEDY: COMPLY WITH CODE.
#35725019X
Mar 9, 2026
POP/IN-VIO
$0
Feb 26, 2025Construction CLASS - 2
REISSUE #35663514M: FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: OBSERVED ROOM 338, 332 AND 200 @ 3RD FLOORS. NOT OPERATIONAL WHENTESTED DUE TO DEFECTIVE THINGS. HITTING DOOR JAMBS. REMEDY: REPAIR AND
#35684788M
Apr 28, 2025
POP/IN-VIO
$0
Feb 26, 2025Construction CLASS - 2
REISSUE #35663513K: EXIT DOOR NOT SELF-CLOSING OBSERVED @ 1ST FLOOR EXIT ONE 2 DOOR @ VESTIBULE EXIT 4 DOOR NOT CLOSING PROPERLY DUE TO HITTING THE SADDLE. REMEDY: REPAIR AND/OR REPLACE.
#35684789Y
Apr 28, 2025
POP/IN-VIO
$0
Mar 13, 2024Construction CLASS - 2
RE-ISSUE #35674626K. EXIT DOOR NOT SELF-CLOSING. NOTED: OBSERVED ON THE FIRST FLOOR EXIT 4 THE DOORS ARE NOT CLOSING PROPERLY, THE DOOR IS HITTING ON THE SADDLE. REMEDY: REPAIR/REPLACE DOOR.
#35663513K
May 6, 2024
POP/IN-VIO
$0
Mar 13, 2024Construction CLASS - 2
RE-ISSUE #35674625Z. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ON THE THIRD FLOOR ROOM #300, 332 AND 338 THESE DOORS ARENOT CLOSING PROPERLY, THE DOORS ARE HITTING ON THE DOOR FRAME. REMEDY:
#35663514M
May 6, 2024
POP/IN-VIO
$0
Apr 10, 2023Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:DOOR OF RMS 300,332 & 338 NOT WORKING PROPERLY.REMEDY:REPAIR AND/OR REPLACE
#35674625Z
Jul 5, 2023
POP/IN-VIO
$0
Apr 10, 2023Construction CLASS - 2
EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR DOOR AT EXIT 4 & MAIN ENTRANCE TO BUILDING ARE NOT WORKING PROPERLY.REMEDY:REPAIR/REPLACE DOOR
#35674626K
Jul 5, 2023
POP/IN-VIO
$0
Jul 27, 2021Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 27-371(J). OBSERVED:KEY CYLINDER LOCKSETS INSTALLED ON PANIC BAR HARDWARE AT SMOKE DOORS STAIR "C" NE
#35584163Y
Dec 29, 2021
POP/IN-VIO
$0
Mar 2, 2021Elevators CLASS - 2
RESTORE SERVICE TO DEVICE
#39036959H
Apr 16, 2021
POP/IN-VIO
$0
Dec 12, 2019Elevators CLASS - 1
SECURE RIGHT HAND WALL. REPAIR PLATFORM
#39014305L
Dec 20, 2019
POP/IN-VIO
$0
Feb 22, 2018Elevators CLASS - 1
CU2X10,CU1X10,CU21D6; 16I10,5I10,100I10,21D10,12Q3,48Y2,16X10,21H11. 1X10-REPAIR STOP SWITCH ON THE HANDHELD; 2X10-REPAIR ALARM SYSTEM (RUNNING BELL); 21D6-SECURE B FLOOR INTERLOCK; 16I10-1 FLOOR/BOTTOM;
#38261427L
May 7, 2018
POP/IN-VIO
$0
Dec 17, 2010Elevators CLASS - 2
02X10,05B07,05E10,12I10,40B07,48V05,60Q03,69M07,70O02,70Y13. 02X- RUNNING BELL. 05B- OUTSIDE HANDLES. 05E- LUBRICATE. 40B- VENT TO FRESH AIR48V- PRESSURE TEST. 48M- PRESSURE GAUGE
#38214442H
Jan 31, 2011
PENDING
$0
DOB (3)
IssuedViolationStatus
Nov 12, 2019ELEVATOR

#9028/666370
DOB VIOLATION - ACTIVE
Apr 5, 2019ELEVATOR ANNUAL INSPECTION / TEST
VIOLATION ISSUED TO ELEVATOR - FAILURE TO FILE CATEGORY 1 2017 INSPECTION/TEST
#04918
DOB VIOLATION - ACTIVE
May 24, 1999CONSTRUCTION

#314AC02
DOB VIOLATION - ACTIVE
DOB NOW Safety (10)
IssuedViolationStatus
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2021 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Apr 5, 2019Elevators EVCAT1
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 18, 2026, 5:00 AM ET. BBL 3076290030.