Manhattan · Block 418 · Lot 36 · 10002

108 Forsyth Street

6 floors · 13,000 sq ft · built 2000 · class H3 · owner of record: Sara Park Management Inc

7open violations
$22,812ECB/OATH penalties owed
0HPD class C (immediately hazardous)
791dto Gas piping inspection (2028 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 60 days
Keep the report on file (not filed with DOB)
Gas piping inspection (2028 cycle) Likely applies
Local Law 152 · During 2028
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2028
in 791 days
Next cycle year 2028

Open violations

ECB / OATH (16) · $22,812 owed
IssuedViolationHearingBalance
Jan 21, 2026Construction CLASS - 2
AO SMITH HOT WATER BOILER DATE STAMPED 2023 IS INSTALLED+OPERATING IN THIS COMMERCIAL BUILDING WITHOUT A DOB PERMIT, OBTAIN ALL PERMITS; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION
#39174590M
May 14, 2026
STIPULATION/IN-VIO
$0
Jan 21, 2026Boilers CLASS - 2
AO SMITH BOILER HAS SAFETY VALVE INCORRECTLY INSTALLED+ILLEGAL DRAFT INDUCER+INCORRECT CHIMNEY TERMINATION+INOPERABLE HW TANK#1+BOILER FLUE PIPE HAS BEEN REDUCED, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTI
#39174589P
May 14, 2026
IN VIOLATION
$1,250
Jan 20, 2026Construction CLASS - 1
UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. EXCESSIVE STORAGE IN MECHANICAL/UTILITIES ROOMS (PLYWOOD, ELECTRICAL VERTICAL FAN, BOXES, LOCKERS). LOCATED THROUGHOUT BASEMENT., MAINTAIN STORAGE IN COMPLI
#39174421L
Mar 26, 2026
IN VIOLATION
$2,500
Jan 20, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS THROUGHOUT BASEMENT. PLASTIC COVERING OVER HOLES IN CEILING OF BASEMENT PROHIBITED. PLASTIC COVERING NOT FIRE RATED., REPAIR AND
#39174422N
Oct 1, 2026
IN VIOLATION
$2,500
Jan 20, 2026Construction CLASS - 1
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED WATER HOSE FUNNELED INTO FLUTE PIPING. POTENTIAL HAZARD., REPAIR AND/REPLACE
#39174424R
Oct 1, 2026
IN VIOLATION
$2,500
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE HALLWAYS THROUGHOUT THE BUILDING THE RECEPTACLES NOT TAMPER RESISTANT/PROOF AS REQUIRED BY LL 39/2015. THIS IS AN IMMEDIATE SHOCK HAZARD.; LL 39-2015, COMPLY WITH EC CODE; PROVIDE TAMPER RESIS
#39120695P
Mar 6, 2025
IN VIOLATION
$1,600
Aug 2, 2024Unknown CLASS - 2
I OBSERVED IN THE UNLABELED 200 AMP SWITCH IN THE MAIN ELECTRICAL ROOM THE CROSSING OF THE LINE AND LOAD CONDUCTORS WITHOUT THE REQUIRED GUTTER SPACE AS REQUIRED. THE IMPROPER CONTACT OF THE CONDUCTORS NEGATES
#39120693L
Mar 6, 2025
IN VIOLATION
$400
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE BASEMENT AREA THE USE OF AN EXTENSION CORD FROM THE FIRE ALARM ATS ROOM TO SUPPLY POWER FOR REFRIGERATORS IN THE COMMON AREA. AS PER EC 400.8 NO FLEXIBLE CORD BE USED AS PERMANENT WIRING NOR S
#39120692J
Mar 6, 2025
IN VIOLATION
$1,600
Aug 2, 2024Construction CLASS - 1
WOOD SHELVING FOR OVERHEAD STORAGE OF PIPES AND COSTRUCTION MATERIAL, SECURITY SEATING/CHAIRS IN EMERGENCY EXITS PATHWAY, GARBAGE AND OTHER MATERIALS OBSTRUCTING EMERGENCY EXITS LOCATED THROUGHOUT BUILDING, COR
#39120742Z
Mar 13, 2025
IN VIOLATION
$1,250
Aug 2, 2024Unknown CLASS - 2
I OBSERVED ON THE ROOF IN THE A.C SWITCH NO EQUIPMENT GROUND CONDUCTOR INSTALLED AS REQUIRED FOR FIXED EQUIPMENT AND /OR WITH USE OF LIQUID FLEXIBLE METALLIC CONDUIT. ALSO NOTED THE IMPROPER USE OF THE SWITCHES
#39120694N
Mar 6, 2025
IN VIOLATION
$400
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE MAIN ELECTRICAL ROOM THE EXCESSIVE STORAGE OF CABINETS, LOCKERS, BUILDING MATERIALS AND EQUIPMENT. AS THE EC NO STORAGE IS PERMITTED. ELECTRICAL DISTRIBUTION EQUIPMENT IS ALLOWED ONLY. PHOTOS
#39120696R
Mar 6, 2025
IN VIOLATION
$1,200
Aug 2, 2024Construction CLASS - 2
NO EMERGENCY LIGHTING FOR STAIRCASE A & B THROUGHOUT BIULDING., REPAIR AND/OR REPLACE LIGHTING
#39120748J
Mar 13, 2025
IN VIOLATION
$625
Aug 2, 2024Construction CLASS - 2
ILLEGAL HARDWARE INSTALLED ON DOORS THROUGHOUT BUILDING., PROVIDE LEGAL HARDWARE
#39120749L
Mar 13, 2025
IN VIOLATION
$312
Aug 2, 2024Construction CLASS - 2
NO FIRE-STOPPING FOR HOLE PENETRATIONS ON WALLS AND CEILINGS LOCATED THROUGHOUT BUILDING AND ALL MECHANICAL ROOMS CELLAR LEVEL., PROVIDE/MAINTAIN FIRE STOPPING
#39120747H
Mar 13, 2025
IN VIOLATION
$625
Aug 2, 2024Unknown CLASS - 1
I OBSERVED IN THE MAIN ELECTRICAL ROOM IN THE CENTER 400 AMP DISCONNECT SWITCH THE IMPROPER FUSING OF THE CONDUCTORS, I NOTED THREE DIFFERENT SIZE FUSES, (300, 350, & 400) AMP. ALL FUSES SHALL BE COORDINATED AT
#39120690X
Mar 6, 2025
IN VIOLATION
$4,800
Jul 30, 2024Elevators CLASS - 1
DOOR ZONE RESTRICTOR AND DOOR LOCK MONITORING INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL THE D.O.B. ELEVATOR DIVISION AT (212) 393-2144 FOR A REINSPEC
#39120309H
Dec 26, 2024
IN VIOLATION
$1,250
DOB (3)
IssuedViolationStatus
Feb 23, 1996CONSTRUCTION

#03G03
VIOLATION UNSERVED ECB-WORK WITHOUT PERMIT-ACTIVE
Dec 8, 1995CONSTRUCTION

#B3SI01
VIOLATION UNSERVED ECB-ACTIVE
Jun 12, 1995CONSTRUCTION

#03G02
DOB VIOLATION - ACTIVE
DOB NOW Safety (1)
IssuedViolationStatus
Mar 17, 2026AEUHAZ FTC-AEU-HAZ
Active
HPD (0)

None open.

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 1, 2026, 4:14 PM ET. BBL 1004180036.