6 floors · 13,000 sq ft · built 2000 · class H3 · owner of record: Sara Park Management Inc
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 60 days | Keep the report on file (not filed with DOB) |
| Gas piping inspection (2028 cycle) Likely applies Local Law 152 · During 2028 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 3 is on the 2028 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2028 in 791 days | Next cycle year 2028 |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| Jan 21, 2026 | Construction CLASS - 2 AO SMITH HOT WATER BOILER DATE STAMPED 2023 IS INSTALLED+OPERATING IN THIS COMMERCIAL BUILDING WITHOUT A DOB PERMIT, OBTAIN ALL PERMITS; CORRECT VIOLATION+SUBMIT CERTIFICATE OF CORRECTION #39174590M | May 14, 2026 STIPULATION/IN-VIO | $0 |
| Jan 21, 2026 | Boilers CLASS - 2 AO SMITH BOILER HAS SAFETY VALVE INCORRECTLY INSTALLED+ILLEGAL DRAFT INDUCER+INCORRECT CHIMNEY TERMINATION+INOPERABLE HW TANK#1+BOILER FLUE PIPE HAS BEEN REDUCED, MAINTAIN BOILER; CORRECT VIOLATION+SUBMIT CERTI #39174589P | May 14, 2026 IN VIOLATION | $1,250 |
| Jan 20, 2026 | Construction CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. EXCESSIVE STORAGE IN MECHANICAL/UTILITIES ROOMS (PLYWOOD, ELECTRICAL VERTICAL FAN, BOXES, LOCKERS). LOCATED THROUGHOUT BASEMENT., MAINTAIN STORAGE IN COMPLI #39174421L | Mar 26, 2026 IN VIOLATION | $2,500 |
| Jan 20, 2026 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS THROUGHOUT BASEMENT. PLASTIC COVERING OVER HOLES IN CEILING OF BASEMENT PROHIBITED. PLASTIC COVERING NOT FIRE RATED., REPAIR AND #39174422N | Oct 1, 2026 IN VIOLATION | $2,500 |
| Jan 20, 2026 | Construction CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED WATER HOSE FUNNELED INTO FLUTE PIPING. POTENTIAL HAZARD., REPAIR AND/REPLACE #39174424R | Oct 1, 2026 IN VIOLATION | $2,500 |
| Aug 2, 2024 | Unknown CLASS - 1 I OBSERVED IN THE HALLWAYS THROUGHOUT THE BUILDING THE RECEPTACLES NOT TAMPER RESISTANT/PROOF AS REQUIRED BY LL 39/2015. THIS IS AN IMMEDIATE SHOCK HAZARD.; LL 39-2015, COMPLY WITH EC CODE; PROVIDE TAMPER RESIS #39120695P | Mar 6, 2025 IN VIOLATION | $1,600 |
| Aug 2, 2024 | Unknown CLASS - 2 I OBSERVED IN THE UNLABELED 200 AMP SWITCH IN THE MAIN ELECTRICAL ROOM THE CROSSING OF THE LINE AND LOAD CONDUCTORS WITHOUT THE REQUIRED GUTTER SPACE AS REQUIRED. THE IMPROPER CONTACT OF THE CONDUCTORS NEGATES #39120693L | Mar 6, 2025 IN VIOLATION | $400 |
| Aug 2, 2024 | Unknown CLASS - 1 I OBSERVED IN THE BASEMENT AREA THE USE OF AN EXTENSION CORD FROM THE FIRE ALARM ATS ROOM TO SUPPLY POWER FOR REFRIGERATORS IN THE COMMON AREA. AS PER EC 400.8 NO FLEXIBLE CORD BE USED AS PERMANENT WIRING NOR S #39120692J | Mar 6, 2025 IN VIOLATION | $1,600 |
| Aug 2, 2024 | Construction CLASS - 1 WOOD SHELVING FOR OVERHEAD STORAGE OF PIPES AND COSTRUCTION MATERIAL, SECURITY SEATING/CHAIRS IN EMERGENCY EXITS PATHWAY, GARBAGE AND OTHER MATERIALS OBSTRUCTING EMERGENCY EXITS LOCATED THROUGHOUT BUILDING, COR #39120742Z | Mar 13, 2025 IN VIOLATION | $1,250 |
| Aug 2, 2024 | Unknown CLASS - 2 I OBSERVED ON THE ROOF IN THE A.C SWITCH NO EQUIPMENT GROUND CONDUCTOR INSTALLED AS REQUIRED FOR FIXED EQUIPMENT AND /OR WITH USE OF LIQUID FLEXIBLE METALLIC CONDUIT. ALSO NOTED THE IMPROPER USE OF THE SWITCHES #39120694N | Mar 6, 2025 IN VIOLATION | $400 |
| Aug 2, 2024 | Unknown CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM THE EXCESSIVE STORAGE OF CABINETS, LOCKERS, BUILDING MATERIALS AND EQUIPMENT. AS THE EC NO STORAGE IS PERMITTED. ELECTRICAL DISTRIBUTION EQUIPMENT IS ALLOWED ONLY. PHOTOS #39120696R | Mar 6, 2025 IN VIOLATION | $1,200 |
| Aug 2, 2024 | Construction CLASS - 2 NO EMERGENCY LIGHTING FOR STAIRCASE A & B THROUGHOUT BIULDING., REPAIR AND/OR REPLACE LIGHTING #39120748J | Mar 13, 2025 IN VIOLATION | $625 |
| Aug 2, 2024 | Construction CLASS - 2 ILLEGAL HARDWARE INSTALLED ON DOORS THROUGHOUT BUILDING., PROVIDE LEGAL HARDWARE #39120749L | Mar 13, 2025 IN VIOLATION | $312 |
| Aug 2, 2024 | Construction CLASS - 2 NO FIRE-STOPPING FOR HOLE PENETRATIONS ON WALLS AND CEILINGS LOCATED THROUGHOUT BUILDING AND ALL MECHANICAL ROOMS CELLAR LEVEL., PROVIDE/MAINTAIN FIRE STOPPING #39120747H | Mar 13, 2025 IN VIOLATION | $625 |
| Aug 2, 2024 | Unknown CLASS - 1 I OBSERVED IN THE MAIN ELECTRICAL ROOM IN THE CENTER 400 AMP DISCONNECT SWITCH THE IMPROPER FUSING OF THE CONDUCTORS, I NOTED THREE DIFFERENT SIZE FUSES, (300, 350, & 400) AMP. ALL FUSES SHALL BE COORDINATED AT #39120690X | Mar 6, 2025 IN VIOLATION | $4,800 |
| Jul 30, 2024 | Elevators CLASS - 1 DOOR ZONE RESTRICTOR AND DOOR LOCK MONITORING INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE SERVICE, CALL THE D.O.B. ELEVATOR DIVISION AT (212) 393-2144 FOR A REINSPEC #39120309H | Dec 26, 2024 IN VIOLATION | $1,250 |
| Issued | Violation | Status |
|---|---|---|
| Feb 23, 1996 | CONSTRUCTION #03G03 | VIOLATION UNSERVED ECB-WORK WITHOUT PERMIT-ACTIVE |
| Dec 8, 1995 | CONSTRUCTION #B3SI01 | VIOLATION UNSERVED ECB-ACTIVE |
| Jun 12, 1995 | CONSTRUCTION #03G02 | DOB VIOLATION - ACTIVE |
| Issued | Violation | Status |
|---|---|---|
| Mar 17, 2026 | AEUHAZ FTC-AEU-HAZ | Active |
None open.
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 1, 2026, 4:14 PM ET. BBL 1004180036.