4 floors · 164,840 sq ft · built 1960 · class W1 · owner of record: Nyc Department Of Parks And Recreation
New violations the morning after they're issued, plus deadline reminders. Free for one building.
| Requirement | Due | Status |
|---|---|---|
| Annual parapet observation Check Local Law 126 · By December 31 each year What this isIf the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page | Dec 31, 2026 in 60 days | Keep the report on file (not filed with DOB) |
| Energy and water benchmarking Likely applies Local Law 84 · May 1 each year What this isBuildings over 25,000 sq ft (this lot shows 164,840 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page | May 1, 2027 in 181 days | Annual filing |
| Building emissions report Likely applies Local Law 97 · May 1 each year (extensions available) What this isCovered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page | May 1, 2027 in 181 days | Annual filing |
| Gas piping inspection (2027 cycle) Likely applies Local Law 152 · During 2027 What this isBuildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 12 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page | Dec 31, 2027 in 425 days | Next cycle year 2027 |
| Energy audit and retro-commissioning (2028) Likely applies Local Law 87 · Calendar year 2028 What this isBuildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 10178). Agency page | Dec 31, 2028 in 791 days | Next due 2028 |
| Annual boiler inspection (3 boilers) Applies Boiler inspection · By December 31 each year What this isBoilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-03-19 (Accepted). Agency page | On file | 2026 reports accepted |
| Issued | Violation | Hearing | Balance |
|---|---|---|---|
| May 27, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ON THE MAIN ROOF AND LOWER ROOF,ROOF MATERIAL HAS BLISTERS FORMING FROM WATER SEEPING THRU IT CREATING TRIPPING HAZARD AND WATER PENETRATION ON CEILIN #35731784Y | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 REISSUE#35725478P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT CELLAR IN BOILER ROOM THERE IS WATER DAMAGE ON FLOOR FROM WATER PENETRATION IN WALLS CREATING STANDING WATER IN ROOM IN SEVERAL A #35731749Z | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 REISSUE#35725477N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:ON 1ST FLOOR IN AUDITORIUM THERE IS CRACK ON CEILING APPROX.8FT LONG.REM:REPAIR AND/OR REPLACE. #35731751H | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NO FIRESTOPPING PER BC 712.3;27-345.NOTED:AT THE CELLAR IN GAS METER ROOM AND ELECTRICMETER ROOM.FIRESTOPPING WAS MISSING AROUND THE PIPES GOING THROUGH CMU #35731754N | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 REISSUE#35725523P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:INTERIOR FPSC DOORS DO NOT SELF-CLOSE PROPERLY AT 2ND FLR-STAIRCASE B 1ST FLR-AUDITORIUM MIDDLE DOOR BASEMENT-EXIT 2 CLASSROOM DOORS #35731748R | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 REISSUE#35725475J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED;EMERGENCY LIGHTS IN GYM WERE NOT OPERATIONAL WHEN T #35731752J | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 FAIURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.USE OF PROHIBITEDDOOR AND/OR HARDWARE PER BC 1008.1.8;27-371(J).NOTED:CLASSROOM#323 HASKICK-STOP INSTALLED ON DOOR & AUDITORIUM DOORS ALSO HAS KICK-STOPS INS #35731755P | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 REISSUE#35725524R EXIT DOOR NOT SELF-CLOSING.NOTED:EXTERIOR DOORS NOT SELF CLOSING PROPERLY AT EXIT#2,3,4,5 AND 8.REM:REPAIR/REPLACE DOOR. #35731753L | Jul 20, 2026 POP/IN-VIO | $0 |
| May 27, 2026 | Construction CLASS - 2 REISSUE#35725476L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:AT EXP#4 OVER HANGING UNDERSIDE HAS CRACKS IN CEMENT FINISH OUTSIDE CAFETERIA EXIT DOORS.REM:REPAIR AND/OR REPLACE. #35731750X | Jul 20, 2026 POP/IN-VIO | $0 |
| Sep 22, 2025 | Construction CLASS - 2 REISSUE #35495505K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED EMERGENCY LIGHTS NOT WORKING AT 1ST FL AUDITO #35725475J | Oct 21, 2025 POP/IN-VIO | $0 |
| Sep 22, 2025 | Construction CLASS - 2 REISSUE #35692262H. EXIT DOOR NOT SELF-CLOSING. NOTED EXTERIOR DOORS AT EXIT #2, 3, 4, 5 AND 8 NOT SELF-CLOSING OR OPENING PROPERLY WHEN TESTED. REMEDY: REPAIR/REPLACE DOORS. #35725524R | Oct 20, 2025 POP/IN-VIO | $0 |
| Sep 22, 2025 | Construction CLASS - 2 REISSUE #35692261X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED INTERIOR FPSC DOORS NOT CLOSING PROPERLY AT: 3RD FL STAIR FAND SMOKE DOOR BY 306. 2ND FL STAIR C, 1ST FL STAIR A AND AUDITORIUM E #35725523P | Oct 20, 2025 POP/IN-VIO | $0 |
| Sep 22, 2025 | Construction CLASS - 2 REISSUE 35692264L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT CELLAR LEVEL BOILER ROOM, WATER PENETRATION THROUGH FOUNDATION WALLS AND FLOOR SLAB. SEVERAL AREAS WITH STANDING WATER. REMEDY: #35725478P | Oct 21, 2025 POP/IN-VIO | $0 |
| Sep 22, 2025 | Construction CLASS - 2 REISSUE #35692265N. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT AUDITORIUM, CEILING HAS AN APPROX. 8SQ FT AREA OF SPALLING PLASTER. REMEDY: REPAIR AND/OR REPLACE. #35725477N | Oct 21, 2025 POP/IN-VIO | $0 |
| Sep 22, 2025 | Construction CLASS - 2 REISSUE #35692266P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED EXP #4 OVERHANG UNDERSIDE HAS SPALLING AND CRACKING CEMENT FINISH OUTSIDE THE CAFETERIA EXIT DOORS BY STEPS LEADING TO 167 ST. RE #35725476L | Oct 21, 2025 POP/IN-VIO | $0 |
| Oct 21, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CDOE-COMPLIANT MANNER. NOTED EXP #4 OVERHANGS UNDERSIDE HAS SPALLING AND CRACKING CEMENT FINISH, OUTSIDE THECAFETERIA BY STEPS LEADING TO 167 STREET. REMEDY: REPAIR AND/OR REPLAC #35692266P | Dec 3, 2024 POP/IN-VIO | $0 |
| Oct 21, 2024 | Construction CLASS - 2 REISSUE #35672310P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT CELLAR LEVEL BOILER ROOM, WATER PENETRATION THROUGH FLOOR SLAB AND FPOUNDATION WALLS. SEVERAL LCOATIONS WITH STANDING WATER. A #35692264L | Dec 3, 2024 POP/IN-VIO | $0 |
| Oct 21, 2024 | Construction CLASS - 2 REISSUE #35672311R. EXIT DOOR NOT SELF-CLOSING. NOTED: EXTERIOR DOORS AT EXIT #2, 3, 5, 12 AND KITCHEN REAR EXIT, NOT OPENING OR CLOSING PROPERLY DUE TO DEFECTIVE HARDWARE, RUBBING OR SADDLE, RACHED AND WARPED. #35692262H | Dec 3, 2024 POP/IN-VIO | $0 |
| Oct 21, 2024 | Construction CLASS - 2 FAILURE TO MAINTAIN BUIDLING IN CODE-COMPLIANT MANNER. NOTED AT AUDITORIUM, CEILING HAS AN APPROX. 8SQFT SECTION OF SPALLING PLASTER. REMEDY: REPAIR AND/OR REPLACE. #35692265N | Dec 3, 2024 POP/IN-VIO | $0 |
| Oct 21, 2024 | Construction CLASS - 2 REISSUE #35672312Z. FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. NOTED: INTERIOR FPSC DOORS NOT CLOSING PROPERLY, AT: 3RD FL STAIR F, SMOKE DOOR BY ROOM #306 AND CLASSROOM DOORS #327, 2ND FL STAIR B #35692261X | Dec 3, 2024 POP/IN-VIO | $0 |
| May 25, 2023 | Construction CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:THE FOLLOWING DOORS ARE NOT CLOSING PROPERLY DUE 327,3RD FLOOR STAIR F.REM:REPAIR/REPLACE DOOR. #35672312Z | Sep 19, 2023 POP/IN-VIO | $0 |
| May 25, 2023 | Construction CLASS - 2 REISSUE#35657759J FAILURE TO MAINTAIN BUILDING WALL(S)OR APPURTENANCESNOTED:AT CELLAR BOILER ROOM,WATER PENETRATION FROM THE GROUND/WALL.REMMAKE NECESSARY REPAIRS. #35672310P | Sep 19, 2023 POP/IN-VIO | $0 |
| May 25, 2023 | Construction CLASS - 2 EXIT DOOR NOT SELF-CLOSING.NOTED:THE FOLLOWING EXIT DOORS NOT SELF-CLOSING:AT CAFETERIA EXIT 5,EXIT 12 REAR AT KITCHEN,AT CELLAR EXIT 3,AT AUDITORIUM ONE MAIN DOOR.REM:REPAIR/REPLACE DOOR. #35672311R | Sep 19, 2023 POP/IN-VIO | $0 |
| May 27, 2022 | Construction CLASS - 2 REISSUE#35577138R.FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED OBSERVED AT CELLAR LEVEL IN THE BOILER ROOM,THERE IS WATER PENETRATION FROM THE FOUNDATION WALLS.REMEDY:MAINTAIN EXTERIOR BUILDING WAL #35657759J | Sep 6, 2022 POP/IN-VIO | $0 |
| May 18, 2021 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES OBSERVED:@CELLAR LEVEL,WATERPROOF FOUNDATION WALLS ALLOWING WATER PENATRATION SHOWING SIGNS OF CORROSION,DETERIORATION&FLOODING OF BOILER RM.MAINTAIN EXTERIOR B #35577138R | Aug 31, 2021 POP/IN-VIO | $0 |
| May 12, 2020 | Construction CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: ILLUMINATION FOR EXITS,EXIT DISCHARGES & PUBLIC CORRIDORS PER BC 1006.1;27-381. NOTED: EMERGENCY EXIT LIGHTING OBSERVED INOPERATIVE WHEN TESTED AT FOLLOWING LO #35495505K | Aug 25, 2020 POP/IN-VIO | $0 |
None open.
| Issued | Violation | Status |
|---|---|---|
| Oct 29, 2026 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction | Active |
| Oct 29, 2026 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction | Active |
| Oct 10, 2025 | Elevators FTC-VT-CAT1-CO Violation Issued-Failure To File 2024 Cat1 Test Affirmation of Correction | Active |
| Oct 10, 2025 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2024 Periodic Inspection Affirmation of Correction | Active |
| Oct 25, 2024 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device | Active |
| Oct 25, 2024 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device | Active |
| Oct 11, 2024 | Elevators FTC-VT-PER-CO Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device | Active |
| Nov 14, 2023 | Boiler FTC-BE-EXT-LP Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device | Active |
| Aug 25, 2023 | Elevators FTF-VT-PER-CO Violation Issued-Failure To File 2022 Periodic Inspection Report | Active |
None open.
| Date | Source | What | Now |
|---|---|---|---|
| Oct 29, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Periodic Inspection Affirmation of Correction | Open |
| Oct 29, 2026 | DOB Safety | Elevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction | Open |
Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)
City records as of Nov 1, 2026, 3:57 PM ET. BBL 4101780001.