Brooklyn · Block 1389 · Lot 35 · 11213

1045 Lincoln Place

5 floors · 65,742 sq ft · built 1907 · class W1 · owner of record: Nyc Department Of Education

19open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
61dto Gas piping inspection (2026 cycle)

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Gas piping inspection (2026 cycle) Likely applies
Local Law 152 · During 2026
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 8 is on the 2026 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2026
in 61 days
Due this year
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 61 days
Keep the report on file (not filed with DOB)
Annual boiler inspection (2 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2023-09-26 (Accepted). Agency page

Dec 31, 2026
in 61 days
2 of 2 without an accepted 2026 report yet
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 65,742 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 182 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 182 days
Annual filing
Energy audit and retro-commissioning (2029) Likely applies
Local Law 87 · Calendar year 2029
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 1389). Agency page

Dec 31, 2029
in 1157 days
Next due 2029

Open violations

ECB / OATH (5)
IssuedViolationHearingBalance
Mar 23, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, THERE WAS A BROKEN EXTERIOR WINDOW IN STAIRCASE "F" BETWEEN 2ND AND 1ST FLOOR, IN EXIT #2 VESTIBULE THERE WAS SPALLING AND EFFLO
#35727578L
Apr 17, 2026
POP/IN-VIO
$0
Mar 23, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8; 27-371(J). AT THE TIME OF INSPECTION THE FOLLOWING ROOM DOORS HAD TURN KNOB HANDLES"-308D, 112, 113
#35727576H
Apr 17, 2026
POP/IN-VIO
$0
Mar 23, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION, THE FOLLOWING DOORS WERE NOT SELF-CLOSING:-313, 308D, 304(FRAME WAS SPLIT/DAMAGED) 112, 113, 103, 101, STAIRCASE "D" ON 3RD FLOO
#35727575X
Apr 17, 2026
POP/IN-VIO
$0
Mar 23, 2026Construction CLASS - 2
RE-ISSUED 35691726M. AT THE TIME OF INSPECTION, THE FOLLOWING EMERGENCY LIGHTS WERE INOPERABL:-2 LIGHTS IN LIBRARY, 1-I, C-1, C-2, C-3, C-4,C-5, 3-1. REMEDY: REPAIR/REPLACE LIGHTING.
#35727577J
Apr 17, 2026
POP/IN-VIO
$0
Apr 2, 2025Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.NOTED:IN THE CAFETERIA TWO LIGHTS WERE NOT OPERATIONAL WHEN TESTED.REM:REPAI
#35691726M
Jul 9, 2025
POP/IN-VIO
$0
DOB (5)
IssuedViolationStatus
Sep 16, 2026CONSTRUCTION
FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CRACKED WINDOW PANES ON EXPOSURE #1 SOUTH ELEVATION AND EXPOSURE #4 N.E. CORNER AND AT EXPOSURE #3 NORTH ELEVATION, AT 4TH FLOOR N.E. CORNER AND AT 2ND FLOOR NEAR "EXIT 6" OF BUILDING. REMEDY: REPAIR AND/OR REPLACE
#SR30809NS
DOB VIOLATION - ACTIVE
Sep 16, 2026CONSTRUCTION
EMERGENCY WORK ORDER DUE TO: CRACKED/SPALLING STONES AT EXPOSURE #3 NORTH ELEVATION @ 4FL N.E. CORNER AND AT 2FL NEAR "EXIT 6" OF BUILDING REMEDY: IMMEDIATELY INSTALL SIDEWALK SHEDS @ EXPOSURE #3 NORTH ELEVATION AT N.W. CORNER AND AT EXIT 6 DOORWAY UNDER DIRECTION OF A LICENSED PROFESSIONAL
#SR30810NS
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#09550
DOB VIOLATION - ACTIVE
Nov 14, 2025LOW PRESSURE BOILER
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
#09551
DOB VIOLATION - ACTIVE
Jun 23, 2024FAILURE TO SUBMIT EER
FAILURE TO SUBMIT AN EER PER AD. CODE SEC. 28-308.4 - MULTIPLE YEARS (2023)
#00619
DOB VIOLATION - ACTIVE
DOB NOW Safety (9)
IssuedViolationStatus
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Nov 14, 2025Boiler LBLVIO
VIOLATION ISSUED-FAILURE TO FILE 2024 EXTERNAL LOW PRESSURE INSPECTION
Active
Oct 31, 2025Gas Piping - LL152 FTF-PL-PER
Cycle 1, Sub-cycle C (premises is in Community District 8)
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Jun 23, 2024Retro-Commissioning - LL87 FTF-EN-EARCX
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2018 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Sep 16, 2026DOBCONSTRUCTION: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CRACKED WINDOW PANES ON EXPOSURE #1 SOUTH ELEVATION AND EXPOSURE #4 N.E. CORNER AND AT EXPOSURE #3 NORTH ELEVATION, AT 4TH FLOOR N.E. CORNER AND AT 2ND FLOOR NEAR "EXIT 6" OF BUILDING. REMEDY: REPAIR AND/OR REPLACEOpen
Sep 16, 2026DOBCONSTRUCTION: EMERGENCY WORK ORDER DUE TO: CRACKED/SPALLING STONES AT EXPOSURE #3 NORTH ELEVATION @ 4FL N.E. CORNER AND AT 2FL NEAR "EXIT 6" OF BUILDING REMEDY: IMMEDIATELY INSTALL SIDEWALK SHEDS @ EXPOSURE #3 NORTH ELEVATION AT N.W. CORNER AND AT EXIT 6 DOORWAY UNDER DIRECTION OF A LICENSED PROFESSIONALOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Oct 31, 2026, 9:56 AM ET. BBL 3013890035.