Queens · Block 16167 · Lot 99 · 11694

100-00 Beach Channel Drive

1 floors · 407,218 sq ft · built 1969 · class W1 · owner of record: Nyc Department Of Education

59open violations
$0ECB/OATH penalties owed
0HPD class C (immediately hazardous)
181dto Energy and water benchmarking

Get an email when anything changes here

New violations the morning after they're issued, plus deadline reminders. Free for one building.

Compliance deadlines

RequirementDueStatus
Annual parapet observation Check
Local Law 126 · By December 31 each year
What this is

If the building has a parapet facing a street, sidewalk or other public way, a competent person (such as a mason, engineer or architect) must observe it every year and the owner keeps the report for DOB on request. Detached one- and two-family homes are exempt. Agency page

Dec 31, 2026
in 60 days
Keep the report on file (not filed with DOB)
Energy and water benchmarking Likely applies
Local Law 84 · May 1 each year
What this is

Buildings over 25,000 sq ft (this lot shows 407,218 sq ft) report energy and water use for the prior calendar year through ENERGY STAR Portfolio Manager. The city's Covered Buildings List is the final word on which buildings must file. Agency page

May 1, 2027
in 181 days
Annual filing
Building emissions report Likely applies
Local Law 97 · May 1 each year (extensions available)
What this is

Covered buildings file an annual greenhouse gas emissions report certified by a registered design professional. Buildings over their emissions limit owe penalties, so it pays to check early. Agency page

May 1, 2027
in 181 days
Annual filing
Gas piping inspection (2027 cycle) Likely applies
Local Law 152 · During 2027
What this is

Buildings with gas piping (except one- and two-family homes) need a periodic gas piping inspection by a licensed master plumber every four years. Community district 14 is on the 2027 cycle; certification is filed with DOB after the inspection. Buildings with no gas piping file a certification instead. Agency page

Dec 31, 2027
in 425 days
Next cycle year 2027
Energy audit and retro-commissioning (2027) Likely applies
Local Law 87 · Calendar year 2027
What this is

Buildings over 50,000 sq ft file an Energy Efficiency Report every ten years, in the year whose last digit matches the last digit of the tax block (block 16167). Agency page

Dec 31, 2027
in 425 days
Next due 2027
Annual boiler inspection (4 boilers) Applies
Boiler inspection · By December 31 each year
What this is

Boilers are inspected each calendar year and the report is filed in DOB NOW: Safety within 14 days of the inspection (low-pressure boilers in residential buildings of 5 or fewer families are exempt). Latest report on record: 2026-02-17 (Accepted). Agency page

On file2026 reports accepted

Open violations

ECB / OATH (20)
IssuedViolationHearingBalance
Mar 24, 2026Construction CLASS - 2
REISSUE ECB #35678622L. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1; 27-381. NOTED EMERGENCY LIGHTS ON 1ST FLOOR #24, 29, LIB
#35722334M
Apr 10, 2026
POP/IN-VIO
$0
Mar 24, 2026Construction CLASS - 2
REISSUE ECB #35677151J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED SMOKE DOORS ON 1ST FLOOR ROOMS D125C, B, A, HALLWAY CORRIDOR BY C141, C148 NOT FUNCTIONING PROPERLY. REMEDY: REPAIR AND/OR REP
#35722335Y
Apr 10, 2026
POP/IN-VIO
$0
Mar 24, 2026Construction CLASS - 2
REISSUE ECB #35678624P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: STEP CRACKS IN CMU WALL IN GYM. REMEDY: REPAIR AND/OR REPLACE.
#35722333K
Apr 20, 2026
POP/IN-VIO
$0
Mar 24, 2026Construction CLASS - 2
REISSUE ECB #35672986P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED SIGNS OF LEAK/SPALLING PLASTER ON CEILING ROOMS 302, 362, 304, AUDITORIUM. REMEDY: REPAIR AND/OR REPLACE.
#35722337H
Apr 10, 2026
POP/IN-VIO
$0
Mar 24, 2026Construction CLASS - 2
REISSUE ECB #35672987R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED BEHIND ATHLETIC FIELD/PARKING LOT SEAWALL CRACKED/MISSING CONCRETE AND EXPOSED RUSTY RE-BARS. REMEDY: REPAIR AND/OR REPLACE.
#35722336X
Apr 10, 2026
POP/IN-VIO
$0
Mar 24, 2026Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3; 27-345. NOTED IN ELECTRICAL ROOM HOLE IN CMU WALL, APPROX 8"X8". REMEDY: PROVIDE/MAINTAIN FIRE STOPPING.
#35722338J
Apr 10, 2026
POP/IN-VIO
$0
Apr 23, 2024Construction CLASS - 2
REISSUE#35644280P AT 2 & 3 FLOOR ROOFS BLISTERING AND CRACKS THROUGHOUT,1 FLOOR GYM A WALL HAS STEP CRACKS IN CMU,AUDITORIUM CEILING TILES MISSING AND HANDCAP RAILING MISSING BY STAGE COURTYARD BY AUDITORIUM CR
#35678624P
Jul 3, 2024
POP/IN-VIO
$0
Apr 23, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER BC 1006.1;27-381.AT 1 FLOOR EMERGENCY LIGHT 24,29 AND LIBARY ARE NOT FUNCTIONING PROPERLY.REM
#35678622L
Jul 3, 2024
POP/IN-VIO
$0
Apr 23, 2024Construction CLASS - 2
FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT 1 FLOOR ROOMSD125C,B,A HALLWAY CORRIDOR BY C141,AND C148 DOORS ARE NOT FUNCTIONING PROPERLY.REM:REPAIR AND/REPLACE.
#35677151J
Jul 3, 2024
POP/IN-VIO
$0
Apr 23, 2024Construction CLASS - 2
REISSUE#35644278X AT ATHLETIC FIELD PARKING LOT SEAWALL BULKHEAD HAVE CRACKS,SPALLING AND EXPOSED REBAR.BLEACHERS TOP ROW CRACK,MATTS MISSING ON TRACK TRIP HAZARDS.REM:REPAIR AND/OR REPLACE.
#35678623N
Jul 3, 2024
POP/IN-VIO
$0
May 9, 2023Construction CLASS - 2
REISSUE#35644280P(4/13/22)FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT ROOF IN VARIOUS LOCATIONS BUBBLE RETAINING RAINWATER PEELED D IRATER INFITRATION ONTO ROOM 302 DAMISED WATER DAMAGED,SPALLING P
#35672986P
Aug 1, 2023
POP/IN-VIO
$0
May 9, 2023Construction CLASS - 2
REISSUE#35644278X(4/13/22)FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.AT ATHLETIC BUILDING BEHIND BENCH/STANDING PARKING LOTS SEAWALL BULKHEAD AREA SHOW SEVERAL CRACKS,SPALLING WITH EXPOSED RE-BARS AN
#35672987R
Aug 1, 2023
POP/IN-VIO
$0
Apr 13, 2022Construction CLASS - 2
REISSUED #35334418P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT ROOF THROUGHOUT IN VARIOUS LOCATIONS ROOF MATERIALS POPPED/BUBBLED AT ROOM #362 OBSERVED EFFECTS & SIGNS OF WATER PENETRATION N
#35644280P
Jul 26, 2022
POP/IN-VIO
$0
Apr 13, 2022Construction CLASS - 2
REISSUE #35546557J FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED:AT ATHLETIC PARKING LOTS SEA WALL BULKHEAD AREA HAS SEVERAL CRACKS WITH EXPOSED REBARS & REBARS ARE RUSTED.REMEDY:REPAIR AND/OR REP
#35644278X
Jul 26, 2022
POP/IN-VIO
$0
Feb 24, 2021Construction CLASS - 2
REISSUE#35402219Y ISSUED 5/14/2019 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT ATHLETIC FIELDS/PARKING LOTS SEA WALLS/BULKHEAD SHOW CONCRETE SPALLING,CRACKS,EXPOSE RE-BARS STEEL TO RUSTED FACING NORTH
#35546557J
Jun 1, 2021
POP/IN-VIO
$0
Jan 6, 2020Elevators CLASS - 2
11X10(11,X,10)UP DIRECTION BUTTON DOES NOT WORK.
#38272574P
Jun 9, 2020
POP/IN-VIO
$0
May 14, 2019Construction CLASS - 2
REISSUE #35334418P FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT ROOF LEVEL THE ROOF IS LIFTING UP LARGE BUBBLES AND ACTIVE LEAKS PRESENT. RMDY: REPAIR AND/OR REPLACE.
#35402218M
Aug 13, 2019
POP/IN-VIO
$0
May 14, 2019Construction CLASS - 2
REISSUE #35334528X FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. ATHLETIC FIELD PARKING LOT ADJACENT TO BASEBALL FIELD. BULKHEAD/ SEAWALL DAMAGED SECTIONS CRACKED AND COLLAPSED AND PARKING LOT HAS SIN
#35402219Y
Aug 13, 2019
POP/IN-VIO
$0
Jun 11, 2018Construction CLASS - 2
REISSUE OF NOV #35271605P.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT ROOF LEVEL ROOFING MATERIAL UPLIFTED AND BUBBLING.ACTIVE LEAK PRESENT A ROOM E 304 AND AUDITORIUM.REM:COMPLY WITH NOTICE OF VIO
#35334418P
Sep 11, 2018
POP/IN-VIO
$0
Jun 11, 2018Construction CLASS - 2
FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTEDLAT ATHLETIC FIELD PARKING LOT ADJACENT TO BASEBALL FIELD,BULKHEAD/SEAWALL SEVERLY DAMAGED SECTIONS HAVE COLLAPSED SECTIONS OF PARKING LOT HAVE SUNK HOLES.
#35334528X
Sep 11, 2018
POP/IN-VIO
$0
DOB (3)
IssuedViolationStatus
Dec 20, 2021ELEVATOR

#9027/713531
DOB VIOLATION - ACTIVE
Dec 20, 2021ELEVATOR

#9027/713532
DOB VIOLATION - ACTIVE
Dec 20, 2021ELEVATOR

#9027/713533
DOB VIOLATION - ACTIVE
DOB NOW Safety (36)
IssuedViolationStatus
Oct 29, 2026Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2025 Cat1 Test Affirmation of Correction
Active
Oct 2, 2026Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2025 Periodic Inspection Report
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Dec 15, 2025Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2024 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 25, 2024Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2023 External Inspection Affirmation of Correction for LP Device
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-PER-CO
Violation Issued-Failure To File 2023 Periodic Inspection Affirmation of Correction
Active
Oct 11, 2024Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2023 Cat1 Test Affirmation of Correction
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2019 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2020 External Inspection Affirmation of Correction for LP Device
Active
Nov 14, 2023Boiler FTC-BE-EXT-LP
Violation Issued-Failure To File 2022 External Inspection Affirmation of Correction for LP Device
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2021 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2018 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2022 Cat1 Test Affirmation of Correction
Active
Oct 23, 2023Elevators FTC-VT-CAT1-CO
Violation Issued-Failure To File 2020 Cat1 Test Affirmation of Correction
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
Aug 25, 2023Elevators FTF-VT-PER-CO
Violation Issued-Failure To File 2022 Periodic Inspection Report
Active
HPD (0)

None open.

Issued in the last 120 days

DateSourceWhatNow
Oct 29, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Cat1 Test Affirmation of CorrectionOpen
Oct 2, 2026DOB SafetyElevators: Violation Issued-Failure To File 2025 Periodic Inspection ReportOpen

Check the agency records

Always confirm on the city's own systems before acting: DOB BIS property profile · DOB NOW · HPD Online · Pay ECB/OATH penalties (CityPay)

City records as of Nov 1, 2026, 7:44 AM ET. BBL 4161670099.